Posted on Leave a comment

Danfoss VLT® AutomationDrive FC 360 Series User Manual Operation Guide

The Danfoss VLT® AutomationDrive FC 360 series is a powerful and versatile frequency converter suitable for a wide range of industrial control applications. This article will provide a detailed operation guide for this series of frequency converters, covering the control panel functions, parameter operations, terminal control, and fault code handling.

FC360 front image

I. Control Panel Function Introduction

The Danfoss VLT® AutomationDrive FC 360 series offers two types of control panels: the Numeric Local Control Panel (NLCP) and the Graphical Local Control Panel (GLCP), to meet the needs of different users.

1.1 Basic Control Panel Operations

  • Numeric Local Control Panel (NLCP):
    • Display: Shows current operating parameters and status.
    • Menu Key: Switches between status menu, quick menu, and main menu.
    • Navigation Keys and Indicators: Used for parameter selection and value adjustment, with indicators showing the converter status.
    • Operation Keys: Including [Hand On], [Auto On], [Reset], etc., for manual start, automatic start, and reset operations.
  • Graphical Local Control Panel (GLCP):
    • Similar functions to NLCP but with a larger display for richer information and multi-language support.
FC360 side image

1.2 Parameter Copying and Restoration

  • Parameter Copying:
    1. Upload parameters from Converter A to the control panel: On Converter A, enter the main menu, select “LCP Copy” function, and upload parameters to LCP.
    2. Download parameters from the control panel to Converter B: On Converter B, enter the main menu, select “LCP Copy” function, and download parameters from LCP to the converter.
  • Parameter Initialization:
    Enter the main menu, select the “Operating Mode” parameter, set it to “Initialize” and execute, or reset parameters to factory defaults.
  • Encryption and Parameter Level Settings:
    Protect parameters from unauthorized changes by setting a password (parameter 0-60). Additionally, parameters 0-10 and 0-11 can be used to set the validity and editing permissions of different menus.
  • Compressor Control Parameter Settings:
    Adjust startup parameters (e.g., 1-75 Startup Speed, 1-76 Startup Current), stop parameters (e.g., 1-80 Stop Function), and acceleration/deceleration times (e.g., 3-41 Ramp 1 Acceleration Time) according to compressor application requirements.
Danfoss FC-360 series frequency converter basic wiring diagram

II. Terminal Forward/Reverse Control and External 4-20mA Frequency Setting

2.1 Forward/Reverse Control

  • Wiring:
    • Forward Control: Connect the control signal to terminal 18 (Digital Input [8] Start).
    • Reverse Control: Connect the control signal to terminal 19 (Digital Input [10] Reverse).
  • Parameter Settings:
    • Enter the Digital Input parameter group (5-1*), and set the functions of terminals 18 and 19 to start and reverse, respectively.

2.2 External 4-20mA Frequency Setting

  • Wiring:
    • Connect the external 4-20mA signal to terminal 53 or 54 (depending on the analog input configuration).
  • Parameter Settings:
    1. Enter the Analog Input parameter group (6-1* or 6-2*), and configure terminal 53 or 54 as a current input mode.
    2. Set the minimum and maximum values for the analog input (e.g., 6-10 Terminal 53 Low Voltage, 6-11 Terminal 53 High Voltage), as well as the corresponding feedback or reference value.
    3. In the Reference parameter group (3-1*), select the external analog input as one of the reference sources.

III. Fault Code Handling

The Danfoss VLT® AutomationDrive FC 360 series provides extensive fault codes to help users quickly locate and resolve issues.

  • Common Fault Codes and Meanings:
    • Alarm 14: Earth Fault: Output phase is discharging to earth through the cable between the motor and the converter or the motor itself.
    • Alarm 16: Short Circuit: Short circuit occurs in the motor or motor circuit.
    • Alarm 30: Motor Phase U Missing: Motor U phase is missing between the converter and the motor.
    • Alarm 61: Feedback Error: Deviation exists between the calculated speed and the speed measurement value from the feedback device.
  • Fault Handling:
    • Refer to the fault diagnosis section in the user manual based on the fault code, check the corresponding circuit connections, motor status, and parameter settings.
    • After resolving the fault, perform a reset operation through the control panel or an external reset signal to restore normal operation of the converter.

IV. Conclusion

The Danfoss VLT® AutomationDrive FC 360 series user manual provides a comprehensive operation guide, covering control panel functions, parameter operations, terminal control, and fault code handling. By mastering these operation guides, users can better use and maintain the frequency converter, ensuring its stable and reliable operation in various industrial control scenarios. In practical applications, users should also flexibly adjust parameter settings and control strategies based on specific application requirements and field environments to achieve optimal control effects.

Posted on Leave a comment

User Manual Guide for Hilectro Hi2xx Series Servo Drives

The Hilectro Hi2xx series servo drives are high-performance AC servo drives specifically designed for injection molding machines. This manual aims to provide users with a detailed operation guide, including product overview, safe operation, mechanical installation, electrical connection, parameter setting, troubleshooting, and more.

Function diagram of Hi2xx servo control panel

Product Overview

The Hilectro Hi2xx series servo drives are engineered to deliver precision control and high efficiency, making them ideal for the demanding applications of injection molding machines. These drives come with advanced features such as multiple communication protocols, rich I/O interfaces, and robust protection mechanisms to ensure reliable and stable operation.

Safety Precautions

General Safety Instructions:

  • The drives contain voltages that can be lethal. Always ensure safe and correct operation to minimize risks to personal safety and equipment.
  • During transportation, installation, and storage, prevent physical damage to the drives. Do not remove or bend the components and covers.
  • Store the drives in their original packaging and avoid exposing them to humid, high-temperature environments or direct sunlight for prolonged periods.

Operational Safety:

  • Before powering on, check that the power voltage matches the drive’s rated voltage, ensure correct wiring of inputs and outputs, and inspect for any short circuits. Always cover the drive before powering on.
  • During operation, avoid touching the heat sink or discharge resistors. Non-technical personnel should not detect signals while the drive is running.
  • After powering off, do not perform parameter storage operations as the capacitors may still hold high voltage for up to 5 minutes.

Mechanical Installation

Installation Environment:

  • Choose an installation location with good ventilation and away from sources of heat, vibration, and dust.

Installation Space and Direction:

  • Ensure adequate space around the drive for heat dissipation. Refer to the manual for specific spacing requirements based on the drive’s power rating.
  • Install the drive vertically to facilitate heat dissipation. If multiple drives are installed, use a side-by-side arrangement.
Hi260HI262 servo standard wiring diagram

Electrical Connection

System Peripheral Connection:

  • Connect the drive to the surrounding machinery using appropriate devices such as circuit breakers, contactors, input reactors, and filters to ensure safe and reliable operation.

Main Circuit Wiring:

  • Refer to the wiring diagrams in the manual for connecting the main circuit terminals. Use the recommended copper wire size based on the drive’s power rating.
  • Ensure that the grounding terminal (PE) is reliably grounded with a resistance value less than 10Ω.

Control Circuit Connection:

  • Connect the control circuit wires according to the control board terminal layout. Pay attention to the signal levels and wiring requirements of each terminal.

Parameter Setting

The Hi2xx series servo drives provide a wide range of parameters for users to configure according to their specific needs. These parameters can be divided into several groups, such as Running Parameters (RU), Application Parameters (AP), Protection Parameters (PN), Motor Parameters (DR), etc.

Commonly Used Parameters:

  • RU.01: Target Speed 1 (unit: r/min)
  • AP.00: Command Source (e.g., 0: Terminal + Operator, 1: Terminal, 2: Bus)
  • AP.01: Speed Command Source (e.g., 0: Local, 1: Analog Input 1, 2: Analog Input 2)
  • PN.00: Motor Overload Protection Enable (0: Disable, 1: Enable)
  • DR.02: Motor Rated Power (unit: kW)

To set these parameters, users can use the built-in operation panel or connect to the drive via a computer using communication interfaces such as CAN or EtherCAT.

Troubleshooting

The manual provides detailed descriptions and troubleshooting methods for common faults and warnings. For example:

Fault Code Er053 (Drive Undervoltage):

  • Possible Causes: Input power voltage is too low or fluctuates greatly.
  • Solutions: Check the input power voltage and ensure it meets the drive’s requirements. If the voltage fluctuates, consider adding a voltage stabilizer.

Warning Code 18 (Drive Undervoltage Warning):

  • Solutions: Monitor the input power voltage and take necessary measures to stabilize it.

Conclusion

The Hilectro Hi2xx series servo drives offer advanced performance and flexibility, making them an excellent choice for injection molding machine applications. By following this user manual guide, users can safely and effectively install, configure, and troubleshoot these drives to achieve optimal performance. Always refer to the manual for detailed information and specifications when performing any operation on the drives.

Posted on Leave a comment

User Guide for ABB DCS550 Series DC Drives

I. Functions of the DCS550 Control Panel and Local Start/Speed Adjustment

1.1 Control Panel Overview The DCS550 control panel (DCS Control Panel) is used for monitoring, operation, and parameter configuration of the drive. Its main features include:

  • Start/Stop Button: Used to start or stop the drive.
  • LOC/REM Button: Switches between Local (LOC) and Remote (REM) control modes.
  • Navigation and Confirm Keys: Used for navigating parameter menus and adjusting settings.
  • Display Screen: Displays operational status, alarm messages, and parameter values.
  • Quick Menu: Provides quick access to key parameter settings and fault diagnostics.
DCS550 physical terminal wiring diagram

1.2 Local Start and Speed Adjustment

  • Ensure the drive is in Local mode (display shows “L”).
  • Press the Start button to run the drive.
  • Use the navigation keys to adjust the speed setpoint.

1.3 Field Circuit Parameter Configuration

  • The field voltage output can be measured across the F+ and F- terminals. Set the following parameters based on the motor’s rated values:
    • FldCtrlMode (44.01): Configure the field control mode as “Automatic” or “Constant Voltage.”
    • FldMaxCur (44.02): Set the maximum field current.
    • FldVoltNom (44.03): Set the nominal field voltage.

1.4 Armature Circuit Parameter Configuration

  • Key parameters for the armature circuit include:
    • ArmVoltMax (43.01): Set the maximum armature voltage.
    • ArmCurrMax (43.02): Set the maximum armature current.
    • RampUp/RampDown (42.01/42.02): Configure acceleration and deceleration times for current and speed.
DCS550 labeled wiring diagram

1.5 Speed Feedback Parameter Configuration

  • Speed feedback can be provided via encoder signals or analog signals:
    • SpeedRefSel (20.02): Select the speed reference signal source.
    • EncoderPPR (45.03): Set the pulses per revolution (PPR) for the encoder.

1.6 Auto-Tuning of Parameters

  • Follow these steps for parameter auto-tuning:
    1. Ensure the motor and load are properly connected.
    2. Access the auto-tuning menu and enable AutoTune (22.01).
    3. The system will automatically adjust control parameters and display “OK” upon completion.

1.7 Fan Parameter Configuration

  • Fan control can be enabled or disabled using parameter MotFanCtrl (10.06).
  • FanTest (10.07): Test the fan to ensure proper operation.
  • FanCtrlMode (10.08): Select “Automatic” or “Continuous” control mode.

II. How to Achieve Forward and Reverse Control in Remote Mode

2.1 Wiring Instructions

  • Forward/Reverse Control Signals:
    • Connect the forward and reverse signals to DI1 and DI2 terminals on X4 (used for forward and reverse operations, respectively).
    • If an external emergency stop is required, connect the signal to DI5.
  • Speed Reference Signal:
    • Use an analog input and connect the speed reference signal to AI1 on X2.

2.2 Parameter Configuration

  • Remote Control Mode:
    • Set CommandSel (10.01) to “MainCtrlWord” to enable remote control commands.
  • Forward/Reverse Logic:
    • Configure RevEnable (20.03) to allow reverse operation.
    • Assign forward/reverse input signals to DI1/DI2.
  • Speed Reference Configuration:
    • Set Ref1Sel (11.03) to AI1 for speed reference input.
  • Acceleration/Deceleration Times:
    • Adjust RampUp (42.01) and RampDown (42.02) as needed for the application.

Physical image of DCS550

III. Fault Codes, Their Meanings, and Solutions

The DCS550 displays fault codes to indicate abnormal conditions. Below are common fault codes and their troubleshooting methods:

3.1 Common Fault Codes

  • F001: Overcurrent Fault
    • Cause: Armature current exceeds the maximum set value.
    • Solution:
      • Check if the motor load is too heavy.
      • Verify the correctness of the armature circuit wiring.
      • Decrease acceleration/deceleration times.
  • F002: Overvoltage Fault
    • Cause: Armature voltage exceeds the allowable range.
    • Solution:
      • Check the stability of the power supply voltage.
      • Increase the capacity of the DC power filter.
  • F003: Encoder Fault
    • Cause: Encoder signal lost or abnormal.
    • Solution:
      • Verify encoder wiring and power supply.
      • Check if the parameter EncoderPPR (45.03) is correctly configured.
  • F004: Field Overcurrent
    • Cause: Field circuit current exceeds the set value.
    • Solution:
      • Inspect the wiring of the field circuit.
      • Verify that the field parameters match the motor specifications.
  • F005: Fan Fault
    • Cause: The fan failed to start or stopped unexpectedly.
    • Solution:
      • Check the fan’s power supply and terminal connections.
      • Use FanTest (10.07) to test the fan’s functionality.

3.2 General Fault Troubleshooting Recommendations

  • Check the alarm messages on the control panel and note the fault codes.
  • Refer to the troubleshooting section of the user manual for detailed instructions.
  • Use the DriveWindow Light software to access detailed fault diagnostics and suggestions.

IV. Conclusion

This guide provides a detailed overview of the operation, parameter configuration, remote control, and fault troubleshooting of the ABB DCS550 DC drive. During use, consider the following key points:

  1. Ensure electrical wiring complies with the manual to avoid errors.
  2. Familiarize yourself with the control panel functions and adjust parameters to meet application needs.
  3. Regularly inspect the equipment’s operational status and promptly address alarm messages.

For complex issues, contact ABB technical support or refer to the relevant sections of the user manual for further diagnosis and resolution.

Posted on Leave a comment

User Guide for Delixi Inverter CDI-EM60/CDI-EM61 Series Manual

I. Introduction to Operation Panel Functions

The Delixi Inverter CDI-EM60/CDI-EM61 series is equipped with an intuitive and user-friendly operation panel, enabling users to easily set and adjust parameters.

CDI-EM60 and EM61 series frequency converter operation panel function diagram

Key Components of the Operation Panel

  1. Display Screen: Displays various operation parameters, status indicators, and error messages.
  2. Function Keys:
    • RUN: Starts the inverter.
    • STOP: Stops the inverter.
    • JOG: Enables jogging (inching) operation.
    • PROG: Enters programming mode for parameter adjustment.
    • ESC/RESET: Exits programming mode or resets errors.
    • ▲/▼: Adjusts parameter values.
    • ▶/◀: Navigates through menus.

Basic Operations

  1. Power On: Ensure the inverter is properly powered on.
  2. Navigation: Use the ▶/◀ keys to navigate through different menus and parameters.
  3. Value Adjustment: Use the ▲/▼ keys to adjust parameter values.
  4. Save & Exit: Press the ESC key to save changes and exit programming mode.

II. Using Simplified Internal Relay Programming Function

The Simplified Internal Relay Programming function allows users to perform basic logical operations using the inverter’s internal relays.

Steps to Configure

  1. Enter Programming Mode: Press the PROG key to enter programming mode.
  2. Navigate to Relay Control Parameters: Use the ▶/◀ keys to navigate to the relay control parameters (P3.2 group).
  3. Set Relay Logic:
    • P3.2.00: Set the control logic for each relay (M1-M5).
    • P3.2.01-P3.2.06: Configure the input conditions for each relay.
    • P3.2.07-P3.2.11: Define the output actions for each relay.
  4. Set Delay Times:
    • P3.2.12-P3.2.16: Set the on-delay times for each relay.
    • P3.2.17-P3.2.21: Set the off-delay times for each relay.
  5. Save Settings: Press the ESC key to save changes and exit programming mode.
CDI-EM60 and EM61 series VFD standard wiring diagram

III. Using Internal Timer Function

The Internal Timer function provides users with timing control capabilities.

Steps to Configure

  1. Enter Programming Mode: Press the PROG key to enter programming mode.
  2. Navigate to Timer Control Parameters: Use the ▶/◀ keys to navigate to the timer control parameters (P3.2.22-P3.2.25).
  3. Set Timer Control:
    • P3.2.23: Configure timer start/stop conditions.
    • P3.2.24/P3.2.25: Set the timer duration for Timer 1 and Timer 2.
  4. Set Timer Units:
    • P3.2.23: Select the time units (seconds, minutes, or hours).
  5. Save Settings: Press the ESC key to save changes and exit programming mode.

IV. Using Internal Calculation Module Function

The Internal Calculation Module function enables users to perform simple arithmetic operations and logical judgments.

Steps to Configure

  1. Enter Programming Mode: Press the PROG key to enter programming mode.
  2. Navigate to Calculation Module Parameters: Use the ▶/◀ keys to navigate to the calculation module parameters (P3.2.26-P3.2.39).
  3. Select Operation Type:
    • P3.2.26: Choose the type of operation (addition, subtraction, multiplication, division, comparison, etc.).
  4. Set Input Addresses:
    • P3.2.28/P3.2.29: Specify the input addresses (A and B) for the operation.
  5. Set Scaling Factors:
    • P3.2.30/P3.2.33: Define the scaling factors for the operation results.
  6. Configure Output:
    • Set the output address or action for the calculation result.
  7. Save Settings: Press the ESC key to save changes and exit programming mode.

V. Restoring Parameters to Factory Defaults

To restore the inverter parameters to their factory defaults, follow these steps:

  1. Enter Programming Mode: Press the PROG key to enter programming mode.
  2. Navigate to Parameter Initialization: Use the ▶/◀ keys to navigate to the parameter initialization parameter (P5.0.19).
  3. Select Initialization Option:
    • Set P5.0.19 to “09” to restore factory parameters, excluding motor parameters, calibration parameters, and password parameters.
    • Set P5.0.19 to “19” to restore factory parameters, excluding motor parameters and password parameters.
  4. Confirm Initialization: Press the RUN key to confirm the initialization process. The inverter will restart automatically.
  5. Exit Programming Mode: Press the ESC key to exit programming mode.

By following these guidelines, users can efficiently utilize the advanced features of the Delixi Inverter CDI-EM60/CDI-EM61 series, ensuring optimal performance and reliable operation.

Posted on Leave a comment

SEW Servo MDX60B/MDX61B Series User Guide and Fault F196.4 Meaning and Solutions

The SEW Servo Drives MDX60B/MDX61B series are widely used in automation control systems, known for their high performance and reliability, meeting the needs of various industrial applications. This guide will provide a detailed introduction to the usage, parameter settings, common faults, and troubleshooting methods of this series, with a focus on explaining the meaning of fault code F196.4 and its resolution.

On site maintenance of SEW servo

1. SEW Servo Operation Panel DBG60B Features

The SEW Servo Drives MDX60B/MDX61B series are equipped with the DBG60B operation panel, which provides an easy-to-use interface for monitoring and configuring the drive parameters.

Main Features:

  • Operating Status Display: The operation panel can display the current status of the servo drive, including alarms, operating parameters, and other critical information.
  • Parameter Settings: Users can set and adjust various parameters to customize the operation of the drive for specific applications.
Setting “Heat Sink Temperature” and “Operating Time”:
  1. On the DBG60B panel, press the “MENU” button to enter the parameter setting mode.
  2. Navigate to the “Parameters” menu and find the monitoring options for “Heat Sink Temperature” and “Operating Time.”
  3. Enable these parameters for display.
  4. After setting, press the “Confirm” button to save the settings. From then on, the operation panel will show the heat sink temperature and operating time, allowing users to monitor the drive’s operating conditions.
Restoring Factory Default Parameters:
  1. On the DBG60B panel, press the “MENU” button to enter the parameter setting mode.
  2. Select “Restore Factory Settings” from the menu.
  3. Confirm the restoration of factory settings, and the system will reset all parameters to their default values. This is useful for initializing the device or correcting configuration errors.
Setting Password and Locking Parameters:
  1. In the “Menu” options, select “Password Settings.”
  2. Enter the default password (usually “0000”), then set a new password.
  3. Enable “Lock Parameters” to prevent unauthorized modification of critical settings. This step is crucial for preventing accidental changes and ensuring the safety of the equipment.
SEW-MDX6061 Standard Wiring Diagram

2. Setting External Terminal Forward/Reverse and External Potentiometer (Analog) for Frequency Control

The SEW Servo MDX60B/MDX61B series supports controlling forward/reverse rotation and adjusting the speed via an external potentiometer or other analog input signals. This is useful for manual speed and direction control in various applications.

Wiring Requirements:
  • Forward/Reverse Control: Use digital input terminals (e.g., X10-X12) to connect external pushbuttons or switches for forward and reverse control.
    • For example, connect a switch between terminals X10 and X11 to implement forward/reverse control.
  • Analog Speed Control via Potentiometer: Use the analog input terminal (e.g., X13) to connect an external potentiometer (10kΩ) or other analog devices that provide a 0-10V or 4-20mA signal to control the speed.
    • Terminal X13 is used for the analog input to set the motor speed.
Parameter Settings:
  1. Setting External Forward/Reverse:
    • In the parameter menu, set the “Control Mode” to “External Control.” Map the input terminals X10-X12 to forward/reverse control functions.
    • Set the input signal correctly (e.g., X10 for forward, X11 for reverse).
  2. Setting Analog Potentiometer for Speed Control:
    • In the parameters, set the “Speed Control Mode” to “Analog Input Speed Control” and select the appropriate input terminal (e.g., X13).
    • Ensure the correct analog signal range (e.g., 0-10V or 4-20mA) is selected to ensure accurate speed control.
SEW MDX61B physical picture

3. Common Fault Codes in SEW Servo Drives and Solutions

The SEW Servo MDX60B/MDX61B series may show several common fault codes, including but not limited to:

  • F0001 – Overload Protection: This error indicates that the load on the servo motor exceeds its rated capacity, triggering the protection mechanism.
    • Solution: Check if the load is too heavy. Adjust the load or reduce the drive output power accordingly.
  • F0102 – Motor Overheating: If the motor temperature exceeds the set threshold, this fault is triggered.
    • Solution: Check the cooling system, ensure proper airflow, and remove any obstructions that may affect cooling.
  • F0203 – Encoder Signal Loss: When the encoder signal is lost or unstable, the drive cannot get accurate position feedback.
    • Solution: Inspect the encoder connection, ensuring that the signal wires are intact and not damaged.
F196.4 FAULT

4. Fault F196.4 Meaning and How to Repair It

F196.4 is a fault indicating an issue with the “Inverter Coupling Reference Voltage”, specifically a defective inverter coupling. This fault typically occurs when the reference voltage in the inverter’s coupling circuit is unstable or fails.

F196.4 Fault Analysis:
  • Fault Description: The F196.4 fault code generally indicates that the coupling module within the inverter cannot function properly, failing to generate or maintain the required reference voltage. This leads to abnormal signal transmission, affecting the inverter’s operation.
  • Possible Causes:
    1. Failure of the coupling module’s internal power supply, preventing the generation of reference voltage.
    2. Faulty circuit components (e.g., capacitors, resistors) within the coupling module.
    3. External power supply issues or unstable voltage leading to abnormal reference voltage.
Solution:
  1. Check the Coupling Module: Inspect the coupling module for any visible damage or loose connections.
  2. Measure the Voltage: Use a multimeter or oscilloscope to check the output voltage of the coupling module and ensure it is stable and within the specified range.
  3. Replace Defective Components: If the coupling module or related components are found to be defective, replace them with the correct parts.
  4. Verify Power Supply Stability: Ensure the power supply system is stable and the wiring connections are correct.

If the issue persists after these checks, it is recommended to contact SEW-EURODRIVE technical support for further diagnosis and assistance.


Conclusion

The SEW Servo MDX60B/MDX61B series drives, with their high efficiency and versatile functions, are widely used in industrial automation. The DBG60B operation panel provides an intuitive interface for setting parameters, monitoring status, and making adjustments as needed. Understanding common fault codes and their solutions is essential for maintaining system reliability. In particular, F196.4 indicates a serious issue with the inverter’s coupling reference voltage, which requires immediate attention and repair. By following the troubleshooting steps outlined in this guide, users can ensure the smooth operation and longevity of their servo drive systems.

Posted on Leave a comment

User Manual Guide for SUNYE CM530 Series Frequency Converter

The SUNYE CM530 series frequency converter is a high-performance flux vector control frequency converter widely used in various industrial control applications. This article aims to provide users with a detailed guide covering operation panel functions, terminal wiring and parameter settings, fault code analysis and troubleshooting methods, helping users better use and maintain the frequency converter.

CM530 Operation Panel Function Diagram
I. Introduction to Operation Panel Functions

The operation panel of the CM530 frequency converter integrates multiple functions, including parameter setting, status monitoring, and operation control. Here are the introductions to the main functions:

  1. Restoring Factory Settings:
    • In the stopped state of the frequency converter, enter the parameter setting interface through the operation panel.
    • Select function code F0-28 and set its value to “1”. Then press the confirmation key, and the frequency converter will restore factory settings.
  2. Setting and Resetting Passwords:
    • Setting Password: Select function code F7-49 and set its value to a non-zero value to enable parameter protection. After setting, entering the parameter setting menu again requires a password.
    • Resetting Password: Under password protection, set F7-49 to “0” to disable password protection.
  3. Setting Parameter Protection:
    • Parameter protection is realized through passwords. After setting the password, unauthorized users cannot modify the frequency converter parameters, ensuring the stability and security of device operation.
II. Terminal Forward/Reverse Control and External Potentiometer Speed Regulation

The CM530 frequency converter supports forward/reverse control via terminals and speed regulation using an external potentiometer. The specific wiring and parameter settings are as follows:

  1. Forward/Reverse Control Wiring:
    • Connect the forward control line to the DI1 terminal and the reverse control line to the DI2 terminal.
    • In the parameter setting interface, set F5-00 to “1” (forward operation) and F5-01 to “2” (reverse operation).
  2. External Potentiometer Speed Regulation Wiring:
    • Connect the center tap of the external potentiometer to the GND of the AI1 terminal, and the other ends to AI1 and +10V, respectively.
    • In the parameter setting interface, set F0-06 to “2” (AI1), selecting AI1 as the main frequency source.
  3. Parameter Settings:
    • Adjust parameters such as F0-14 (maximum operating frequency) according to actual needs to meet the speed regulation range requirements.
III. Fault Code Analysis and Troubleshooting Methods

The CM530 frequency converter features comprehensive fault protection functions. When a fault occurs, the corresponding fault code will be displayed on the operation panel. Here are some common fault codes, their meanings, and troubleshooting methods:

  1. Err01: Inverter Unit Protection
    • Meaning: The inverter has encountered a severe fault, such as overcurrent or overvoltage.
    • Solution: Check the motor and load for abnormalities, and inspect the input and output lines of the frequency converter for short circuits or grounding. If the issue cannot be resolved, contact after-sales service.
  2. Err02: Hardware Overcurrent Protection
    • Meaning: The output current of the frequency converter exceeds the rated value.
    • Solution: Check the motor and load for overload, inspect the motor cable for excessive length or poor insulation, and appropriately adjust the frequency converter parameters.
  3. Err03: Hardware Overvoltage Protection
    • Meaning: The DC bus voltage of the frequency converter is too high.
    • Solution: Check the input power supply voltage for being too high and inspect the braking resistor and braking unit for normal operation.
  4. Err13/Err14: Frequency Converter/Motor Overload
    • Meaning: The frequency converter or motor has been overloaded for an extended period.
    • Solution: Check the load for being too large, appropriately adjust the load or increase the motor capacity, and inspect the motor for being blocked or jammed.
IV. Conclusion
CM530 standard wiring diagram

The SUNYE CM530 series frequency converter user manual provides users with comprehensive operation guidance and troubleshooting methods. By proficiently mastering the functions of the operation panel, reasonably setting terminal wiring and parameters, and promptly analyzing and resolving fault codes, users can ensure the stable operation and efficient work of the frequency converter. Additionally, users should regularly perform maintenance and servicing of the frequency converter to extend its service life and improve operational efficiency.

During use, if encountering faults or questions that cannot be resolved, it is recommended to promptly contact the after-sales service team of SUNYE frequency converters for professional technical support and assistance. Through rational use and maintenance, the SUNYE CM530 series frequency converter will bring greater convenience and benefits to users’ industrial production.

Posted on Leave a comment

Operation Guide for Yuanshin Inverter YX300 Series User Manual

The Yuanshin Inverter YX300 series is a high-performance, low-noise inverter widely used in various industrial equipment. This document aims to provide users with an operation guide for this series of inverters, detailing how to control the inverter via its operation panel, how to set password and parameter access restrictions, how to initialize parameters, and how to achieve forward and reverse control via external terminals.

Actual operation picture of YX3000

1. Introduction to the Operation Panel and Basic Control

Operation Panel Function Introduction

The operation panel of the Yuanshin Inverter YX300 series features intuitive controls that allow users to easily monitor and manage the inverter’s operation. The following are the key functions and their corresponding operations:

  • Start/Stop the Inverter:
    • Start: Press the “RUN” button on the operation panel to start the inverter.
    • Stop: Press the “STOP/RESET” button to stop the inverter.
  • Set Frequency Using the Panel Potentiometer:
    • Rotate the potentiometer on the operation panel to adjust the output frequency of the inverter. This method is suitable for manual frequency adjustments during testing or initial setup.

Setting Password and Parameter Access Restrictions

  • Setting a Password:
    1. Press the “MENU” button to enter the parameter setting mode.
    2. Use the arrow keys to navigate to the password setting parameter (typically found in the PF group parameters).
    3. Enter the desired 4-digit password using the numeric keys.
    4. Press “ENTER” to confirm the password.
  • Accessing Restricted Parameters:
    • When attempting to access a restricted parameter, the inverter will prompt for the password. Enter the correct password to proceed.
  • Disabling the Password Function:
    • To disable the password function, simply set the password to “0000” and confirm.

Initializing Parameters

  • Parameter Initialization:
    1. Press the “MENU” button to enter the parameter setting mode.
    2. Navigate to the parameter initialization function (typically P3.01).
    3. Set the parameter to “1” to restore factory default settings.
    4. Press “ENTER” to confirm and initialize the parameters.
YX3000 standard wiring diagram for Yuanxin frequency converter

2. Forward and Reverse Control via External Terminals

Basic Wiring for External Control

To achieve forward and reverse control of the Yuanshin Inverter YX300 series via external terminals, you need to properly wire the control terminals. The following are the basic steps:

  1. Identify the Control Terminals:
    • FWD (Forward): Connect this terminal to a positive signal source to start the inverter in the forward direction.
    • REV (Reverse): Connect this terminal to a positive signal source to start the inverter in the reverse direction.
    • COM (Common): Common ground terminal for both FWD and REV.
  2. Wiring Configuration:
    • Connect the FWD terminal to a switch or relay contact that closes when you want the motor to run forward.
    • Connect the REV terminal to a switch or relay contact that closes when you want the motor to run reverse.
    • Ensure both FWD and REV terminals are connected to the COM terminal.
  3. Parameter Settings:
    • Set the operation command source to external terminals (P0.03 = 1).
    • Configure the frequency input method as desired (e.g., via potentiometer, analog signal, etc.).

Operation Example

  • Forward Operation:
    • Close the contact connected to the FWD terminal.
    • The inverter will start and run the motor in the forward direction.
  • Reverse Operation:
    • Close the contact connected to the REV terminal.
    • The inverter will start and run the motor in the reverse direction.
  • Stopping the Inverter:
    • Open both the FWD and REV contacts.
    • The inverter will stop the motor.

By following this operation guide, users can easily control the Yuanshin Inverter YX300 series via its operation panel and external terminals, setting passwords and parameter access restrictions as needed, and initializing parameters when required. This ensures efficient and secure operation of the inverter in various industrial applications.

Posted on Leave a comment

Siemens Inverter MM440 Series User Guide and Meaning of A503 Warning with Solutions

I. Introduction to MM440 Series Inverter Operating Panel Functions

1.1 Overview of Operating Panels

MM440 PICTURE

The Siemens MM440 series inverter is equipped with operating panels, including the Status Display Panel (SDP), Basic Operating Panel (BOP), and Advanced Operating Panel (AOP). These panels provide an intuitive interface for user interaction with the inverter, enabling monitoring, setting, and control of the inverter’s operation.

1.2 Setting Passwords and Parameter Levels

To prevent unauthorized changes, the MM440 inverter supports parameter locking and password protection. To set passwords and parameter levels, follow these steps:

  1. Enter Parameter Setting Mode: Use the BOP or AOP to press the “P” key to enter parameter setting mode.
  2. Select Password Parameter: Locate and set parameter P0012 (Unlocking of User-Defined Parameters) to your desired password.
  3. Lock Parameters: Set parameter P0011 (Locking of User-Defined Parameters) to 1 to enable password protection.

1.3 Restoring Factory Settings

To restore the inverter parameters to factory settings, follow these steps:

  1. Enter Parameter Setting Mode.
  2. Set P0010=30: Select the restore factory settings function.
  3. Set P0970=1: Confirm the execution of restoring factory settings.

1.4 Using BICO Functionality

The BICO (Binary Interconnect Connection) function allows users to program interconnections between internal signals and input/outputs of the inverter. To use the BICO function, follow these steps:

  1. Enter Parameter Setting Mode.
  2. Set Relevant BICO Parameters: For example, P0701 to P0708 are used to configure the functions of digital inputs, and P0731 to P0733 are used to configure the functions of digital outputs.
  3. Program Interconnection Logic: According to application requirements, use BICO control words and status words to program the desired interconnection logic.

II. Terminal Control and External Potentiometer Speed Regulation

2.1 Terminal Control

The MM440 inverter supports speed control via terminals. To achieve terminal control, follow these steps to set parameters and wiring:

  1. Set Command Source: Set parameter P0700 to 2 to select terminal control mode.
  2. Configure Digital Inputs: Configure parameters P0701 to P0708 as needed to specify the functions of each digital input (such as start, stop, direction control, etc.).
  3. Wiring: Connect external control signals (such as start and stop buttons) to the corresponding digital input terminals.

2.2 External Potentiometer Speed Regulation

An external potentiometer can be used to adjust the output frequency of the inverter, enabling speed regulation. The setup steps are as follows:

  1. Set Frequency Reference Source: Set parameter P1000 to 2 to select analog input as the frequency reference source.
  2. Configure Analog Input: Ensure that analog input AIN1 or AIN2 is correctly configured to receive a 0-10V or 0-20mA speed regulation signal.
  3. Wiring: Connect the output of the external potentiometer to the AIN1 or AIN2 terminal of the inverter, and ensure that the potentiometer is properly powered.
A503 WARNING CODE

III. Meaning of A503 Warning and Solutions

3.1 Meaning of A503 Warning

The A503 warning indicates that the inverter has detected undervoltage limitation, meaning that the DC link voltage is below the allowed minimum value. This can be caused by unstable supply voltage, input power failure, or internal inverter faults.

3.2 Solutions

  1. Check Supply Voltage: Ensure that the input supply voltage is within the allowed range and remains stable.
  2. Adjust Parameters:
    • Increase the ramp-down time (P1121) to reduce voltage drops during braking.
    • If the dynamic buffer function is enabled (P1240=2), adjust relevant parameters (such as P1243, P1245) to optimize performance.
  3. Check Inverter Internals: If the problem persists, it may be necessary to check the internal DC link and capacitors of the inverter for proper function.

3.3 Fault Codes and Meanings

The MM440 inverter has multiple fault codes that indicate different fault conditions. Here are some common fault codes and their meanings:

  • F0001: Overcurrent, usually caused by motor or cable short circuits, mismatched motor power, etc.
  • F0002: Overvoltage, possibly due to excessively high supply voltage or excessive regenerative energy generated during braking.
  • F0003: Undervoltage, indicating that the input supply voltage is below the allowed range.
  • F0004: Inverter overtemperature, usually caused by poor cooling or excessively high ambient temperature.
  • F0011: Motor overtemperature, possibly due to motor overload or poor cooling.

3.4 Fault Solutions

Methods for resolving inverter faults typically include checking the supply voltage, motor and cable connections, cooling system, and internal components of the inverter. Specific steps should be taken based on the indications of the fault code.

IV. Conclusion

This article provides a detailed introduction to the operating panel functions, terminal control and external potentiometer speed regulation setup methods, as well as the meaning and solutions of the A503 warning for the Siemens MM440 series inverter. Additionally, it outlines common fault codes, their meanings, and solutions. With the guidance of this article, users can better understand and utilize the MM440 series inverter to ensure stable equipment operation.

Posted on Leave a comment

Operation Guide for Senlan Inverter HOPE130 Series User Manual

I. Introduction to the Functions of the Inverter Operation Panel

The operation panel of the Senlan Inverter HOPE130 series offers a wide range of functions and an intuitive operating interface, making it convenient for users to set parameters, control operations, and monitor faults. Below are the primary functions of the operation panel:

Hope130 operation panel function diagram

1.1 Functions of the Operation Panel

  • Digital Display Area: Displays operational parameters such as frequency, current, and voltage.
  • Parameter Unit Display Area: Indicates the unit of the currently displayed parameter, such as Hz, A, V, etc.
  • Operational Status Indicator Area: Includes indicators like RUN (running) and FAULT (fault), used to show the current status of the inverter.
  • Keypad Area: Includes keys such as Menu/Exit, Program/Confirm, Increase, Decrease, Left Shift, Right Shift, Run, and Stop/Reset, used for parameter setting and operational control.

1.2 Restoring Factory Settings

To restore the factory settings of the inverter, follow these steps:

  1. Enter the parameter editing mode and press the Menu/Exit key to access the parameter group selection interface.
  2. Use the Increase or Decrease keys to select the F0 parameter group.
  3. Press the Program/Confirm key to enter the F0 parameter group editing interface.
  4. Use the Increase or Decrease keys to select the F0-11 parameter and set it to 11.
  5. Press the Program/Confirm key to save the setting, and the inverter will automatically restore to factory settings.

1.3 Setting and Removing Passwords

To set a password, follow these steps:

  1. Enter the parameter editing mode and select the F0 parameter group.
  2. Set the F0-13 parameter to the desired password value (0000~9999).
  3. Press the Program/Confirm key to save the setting.

To remove the password, simply reset the F0-13 parameter to 0000.

1.4 Parameter Locking

To prevent parameters from being accidentally modified, they can be locked. Follow these steps:

  1. Enter the parameter editing mode and select the F0 parameter group.
  2. Set the F0-12 parameter to 2 to enable full protection, locking all parameters.
Hope130 standard wiring diagram

II. Terminal Forward/Reverse Control and External Potentiometer Speed Regulation

2.1 Terminal Forward/Reverse Control

To achieve terminal forward/reverse control, the following parameters need to be set, and corresponding terminals need to be wired:

  • Parameter Settings:
    • F0-02: Operation Command Channel Selection, set to 2 (terminal control).
    • F4-06: FWD/REV Operation Mode, select the appropriate mode (e.g., Two-Wire Mode 1).
  • Wiring Terminals:
    • Connect the forward control signal to the X1 terminal and the reverse control signal to the X2 terminal.
    • Ensure the COM terminal is properly grounded.

2.2 External Potentiometer Speed Regulation

To achieve external potentiometer speed regulation, the following parameters need to be set, and corresponding terminals need to be wired:

  • Parameter Settings:
    • F0-01: Main Given Channel for Ordinary Operation, set to 4 (panel potentiometer).
    • If terminal control is desired, set to 5 (AI2) and connect the AI2 terminal to an external potentiometer.
  • Wiring Terminals:
    • If using the panel potentiometer, no additional wiring is required.
    • If using an external potentiometer, connect the two ends of the potentiometer to the AI2 and COM terminals.

III. Fault Code Analysis and Troubleshooting

The Senlan Inverter HOPE130 series provides a range of fault codes to help users quickly locate and resolve issues. Below are some common fault codes, their meanings, and solutions:

3.1 Er.ocb (Instantaneous Overcurrent at Startup)

  • Meaning: Inter-phase or ground short circuit within the motor or wiring, or damaged inverter module.
  • Solution: Check the motor and wiring, and seek professional service.

3.2 Er.ocA (Overcurrent During Acceleration)

  • Meaning: Too short acceleration time, inappropriate V/F curve, or restarting a rotating motor.
  • Solution: Extend the acceleration time, adjust the V/F curve, or set to speed tracking startup.

3.3 Er.ouA (Overvoltage During Acceleration)

  • Meaning: Abnormal input voltage or restarting a rotating motor.
  • Solution: Check the input power supply and set to speed tracking startup.

3.4 Er.dcL (Undervoltage During Operation)

  • Meaning: Abnormal input voltage or power loss during operation, heavy load impact, or damaged charging contactor.
  • Solution: Check the input power supply and wiring, inspect the load, and replace the charging contactor.

3.5 Er.oLL (Motor Overload)

  • Meaning: Inappropriate V/F curve, low input voltage, long-term low-speed heavy-load operation of a standard motor, or improper motor rating or overload protection settings.
  • Solution: Properly set the V/F curve and torque boost, check the input voltage, add an independent cooling fan or select an inverter-duty motor, and correctly set the motor parameters.

IV. Conclusion

The Senlan Inverter HOPE130 series user manual provides a detailed operation guide, covering the functions of the operation panel, restoring factory settings, setting and removing passwords, parameter locking, terminal forward/reverse control, external potentiometer speed regulation, and more. Additionally, the manual lists common fault codes, their meanings, and solutions to help users quickly locate and resolve issues. By carefully studying and mastering this operation guide, users can better utilize and maintain the Senlan Inverter HOPE130 series equipment.

Posted on Leave a comment

Operation Guide for Yaskawa V1000 Series Inverter User Manual

The Yaskawa V1000 series inverter, as a high-performance vector control inverter, is widely used in various industrial drive systems. This article will provide a detailed introduction to the operation panel functions, basic setting methods, common function applications, and fault code analysis of this inverter, helping users better understand and utilize this equipment.

Function diagram of V1000 operation panel

I. Introduction to Operation Panel Functions and Basic Settings

1. Introduction to Operation Panel Functions

The operation panel of the Yaskawa V1000 series inverter integrates rich display and control functions, mainly including the LED operator, LO/RE indicator light, RUN indicator light, etc. Users can perform parameter settings, mode switching, operation monitoring, and other operations through the operation panel.

2. How to Set and Clear Passwords

To protect the inverter parameters from being modified arbitrarily, users can set a password. The specific steps are as follows:

  • Setting a Password: In the parameter setting mode, find A1-04 (password setting), enter the desired password value, and then press the ENTER button to confirm. Next, enter the same password value in A1-05 (password) for confirmation.
  • Clearing a Password: To clear the set password, simply set the password values in both A1-04 and A1-05 to 0.

3. Parameter Initialization

When it is necessary to restore the inverter to its factory default settings, parameter initialization can be performed. The specific steps are as follows:

  • In the parameter setting mode, set A1-03 to 2220 (2-wire sequence control initialization) or 3330 (3-wire sequence control initialization), and then press the ENTER button to confirm. At this point, the inverter will be restored to its factory default settings.

4. Using the DWELL Function

The DWELL function can temporarily maintain the output frequency during motor startup or stoppage to prevent motor stall. The specific setting steps are as follows:

  • In the parameter setting mode, find b6-01 and b6-02, and set the DWELL frequency and time during startup respectively. For example, set b6-01 to 5Hz and b6-02 to 2s, so that the motor will maintain a 5Hz output for 2 seconds during startup.

5. Using the Speed Search Function

The speed search function can automatically search and set the appropriate output frequency when the motor stalls or restarts. The specific usage method is as follows:

  • In the parameter setting mode, set b3-05 to the speed search wait time (e.g., 1s). Then, trigger the speed search function through an external signal when needed, and the inverter will automatically search and set the appropriate output frequency.
V1000 labeled wiring diagram

II. Terminal Functions and Wiring Settings

1. Realizing Forward and Reverse Start/Stop Functions

To realize the forward and reverse start/stop functions of the motor, it is necessary to correctly wire and set relevant parameters. The specific steps are as follows:

  • Wiring: Connect the forward start signal to terminal S1, the reverse start signal to terminal S2, and the stop signal to terminal S3.
  • Parameter Settings: In the parameter setting mode, set b1-02 to 1 (LOCAL/REMOTE selection), and set H1-01 and H1-02 to the input terminals for forward and reverse commands (e.g., S1 and S2) respectively. At the same time, set H1-03 to the input terminal for the stop command (e.g., S3).

2. Realizing External Potentiometer Speed Regulation

The external potentiometer speed regulation function allows users to change the output frequency of the inverter by adjusting the resistance value of an external potentiometer. The specific implementation method is as follows:

  • Wiring: Connect the output signal of the external potentiometer to terminal A1 of the inverter (multi-function analog input terminal).
  • Parameter Settings: In the parameter setting mode, set b1-01 to 1 (control circuit terminal frequency command), and set H3-01 to 0 (0~10V input). At the same time, adjust the values of H3-04 (input gain) and H3-05 (input offset) according to actual needs.

III. Fault Code Analysis

The Yaskawa V1000 series inverter has a comprehensive fault diagnosis function. When a fault occurs in the inverter, the corresponding fault code will be displayed on the operation panel. The following are some common fault codes, their meanings, and solutions:

  • CPF02: A/D converter fault. Possible causes include control circuit damage, control circuit terminal short circuit, etc. Solutions include checking the control circuit connection and replacing the inverter.
  • CPF06: EEPROM data anomaly. Possible causes include control circuit damage, power being cut off during the initialization process, etc. Solutions include re-executing the initialization operation and replacing the inverter.
  • Uv1: Main circuit undervoltage. Possible causes include too low power supply voltage, power supply phase loss, etc. Solutions include checking the power supply voltage and power supply wiring.
  • oH1: Heatsink overheat. Possible causes include too high ambient temperature, excessive load, etc. Solutions include improving heat dissipation conditions and reducing the load.

When a fault occurs in the inverter, users should refer to the fault code displayed on the operation panel, combine the above analysis methods and solutions for troubleshooting and handling. If the problem cannot be solved, users should promptly contact professional technicians for repair.

IV. Conclusion

The Yaskawa V1000 series inverter, as a high-performance vector control inverter, boasts rich functions and flexible setting options. Through the introduction in this article, users can better understand and utilize this equipment to achieve precise motor control and efficient operation. At the same time, users should also regularly check and maintain the inverter to ensure its long-term stable operation.