Posted on Leave a comment

Application of S87C196MH (MC) microcontroller in inverter mainboard

1. Pinout of the 80-pin S87C196MH (MC) microcontroller in SMD package:

2. Introduction to the structure and functions of the S87C196MH (MC) microcontroller:

The controller is a 16-bit microcontroller produced by Intel. It is widely used in inverter products due to its powerful functions and high versatility.

The internal circuit includes arithmetic logic unit (RLU), registers, internal A/D converter, PWM generator, event processing array (EPA), three-phase to complement SPWM output generator, watchdog, clock and interrupt control circuits, etc. The internal structure schematic is as follows:

 The S87C196MH (MC) microcontroller uses CHMOS technology, has an operating temperature of -40 º C–85 º C, supports 16KB EPROM, and when the crystal oscillation frequency is 16MHz, it only takes 1.75 μs to complete 16-bit by 16-bit multiplication . It is suitable for the rapidity requirements of the control system. There are 7 I/O ports, and each port pin is multifunctional.

The register array has 512B, which is divided into low 256B and high 256B. The low 256B can be used as 256 accumulators during ALU operation, and the high 256B is used as register RAM. The high 256B can also be switched to 256B with accumulator function through unique window technology. The microcontroller has 13 10-bit/8-bit high-speed A/D converters inside, and the conversion time can be set between 1.39-40.2 μs . The A/D can also be used as a programmable comparator to generate an interrupt when the input crosses a threshold level.

The event processing array (EPA) mainly performs input and output functions. In input mode, the EPA monitors the changes in the input pin signal and records its time value when the event occurs. This process is called capture. In output mode, when the timer matches a stored time value, the output pin is set, cleared or triggered. Both capture and compare events can generate normal service processes or interrupts. There are 4 capture/compare modules and 4 compare modules.

EPA also contains two 16-bit bidirectional timer/counters T1 and T2. T1 can be timed according to an external clock source. In this working mode, EPA can directly process two pulse signals with a 90 ° phase difference output by the position sensor (such as a photoelectric encoder) to monitor the speed and direction of the motor.

External event processing server (PTS). The controller has two types of interrupt systems: programmable interrupt controller and PTS. The programmable interrupt can be set to PTS interrupt service mode. PTS has several micro-instruction coded hardware interrupt service processes, which can work in parallel with the CPU and can complete data block transfer, process multi-channel A/D conversion, control serial communication and other functions.

The S87C196MH (MC) microcontroller has a three-phase complementary SPWM waveform generator built in, which directly outputs six SPWM signals through the P6 port. The driving current can reach 20 mA and the driving frequency can reach 8MHz. Each SPWM signal can be independently programmed and the dead zone interlock time can be set.

3. Application of S87C196MH (MC) in INVT inverter motherboard:

(1) Power supply, clock, reset, etc. Pins that meet the basic working conditions of the microcontroller.

(2) Pins for processing digital and analog signals at the control terminals. The start, stop and speed control of the inverter, as well as the monitoring of the working status, are all carried out through the control terminals. The input and output signals of the control terminals directly enter the microcontroller pins.

The output of the analog signal of the inverter control terminal actually comes from the PWM0 (P6 I/O port) pin of the microcontroller. The actual output is a width-modulated pulse signal, which is converted into an analog voltage signal by the subsequent circuit.

(3)Switching control signal, control of charging contactor (relay control), control of cooling fan and reset control of drive circuit (release its fault lock state).

  (5)Processing of various detection and protection signals:

(6) Processing of other functional pins

Some pins are connected to ground, +5V, or +5V via a pull-up resistor according to their functions. Some pins are left unused.

    The specific functions of each pin of the S87C196MH (MC) microcontroller have been explained in detail above. In troubleshooting, the cause of the fault can also be determined and the fault location can be found based on the level status of the relevant pins.

For example, if the signal input of a certain terminal of the inverter is invalid, measure whether there is a 0-5V voltage change on the corresponding pin of the CPU , and then quickly determine whether it is a terminal input circuit fault or a CPU fault.

Posted on Leave a comment

A quick inspection method for PLC control circuits

A set of hydraulic processing equipment in a factory suddenly broke down. A solenoid valve could not be powered, causing the hydraulic system to not work properly. After receiving a notice from the user requesting on-site maintenance, an intern from a mechanical and electrical technical school and an undergraduate majoring in automation set out to do the work.

The hydraulic station is controlled by 8 solenoid valves, which are powered by 24V DC and automatically controlled by PLC according to the process flow. Two interns circled the hydraulic system and PLC electric control cabinet for several times, and measured the normal resistance of the solenoid valve (labeled 8YV) coil, which was about tens of Ω . They judged that the solenoid valve was good, and asked the operator to operate the electric control cabinet. The other seven solenoid valves could work normally. However, the two ends of the 8YV coil could not get voltage and could not be attracted. The two interns roughly checked the circuit. The output contact of the PLC drives the intermediate relay KA8, which controls the action of the solenoid valve. The circuit is as shown below:

The circuit was basically clear, but the two students were confused about whether the fault was a PLC problem, an intermediate relay problem, or a circuit problem. In other words, how to check the PLC peripheral circuit fault when the machine was stopped. They wanted to measure the fault during the operation of the equipment, but they did not understand the equipment control process and were afraid of damaging the equipment, so they did not dare to operate. They were not sure whether it was a PLC or a PLC peripheral circuit problem. They did not know how to check it when the machine was stopped. After tinkering for an hour or two, they did not find any results and felt that their self-confidence had suffered a not-so-small blow.

The factory owner was a little anxious. If the repair was not done, the customer order would not be completed. He quickly called two veteran electricians and asked them to repair the equipment in a short time. The veteran electrician, Master Zhang, came up and scolded the two students: If the solenoid valve does not work, there are only two wires, just follow them and find the problem. How can it not be repaired? ! He asked the two students, have you learned PLC, have you learned control circuits? Both of them answered that they had learned PLC and control circuits. The two felt that they had learned well at that time, and one of them was in the top three in the class, a top student. The student said that he understood what he learned at that time, from the control principle to the circuit, everything was OK. How come it is useless all of a sudden? It is exactly: feeling high-energy in learning, but very low-energy in practice; academic performance is not bad, but it is not good when it comes to reality.

Master Zhang said, “Let me fix it while you watch. How difficult is it?” Master Zhang found a wire and introduced the 24V voltage directly to the two control leads of 8YV. He saw that the 8YV solenoid valve still did not work, and the lead was indeed broken. Master Zhang said, “Replace the wires. Replace the two leads of the solenoid valve, and it will be fixed. It’s very simple!”

The control line from the electric control cabinet was introduced into the workshop hydraulic station through dozens of meters of buried iron pipes. Master Zhang said, I know, there is a joint in the control line, it must be a bad contact. To repair it quickly, re-route two control leads of the 8YV solenoid valve, and solve the problem in ten minutes! A student asked: Do I need to measure it again? Master Zhang said, there is no need to measure, didn’t I just try it? In addition, two wires were pulled from the control terminal of the electric control cabinet and directly connected to 8YA. The power-on test, just as Master Zhang said, within ten minutes, the fault was eliminated.

At this time, the two students’ interest in learning was aroused, and they asked the old electrician Master Li: If you were asked to repair this fault, what would you do? Master Li was gentle and explained slowly: Master Zhang’s repair method is based on experience, and his inspection method is also more accurate and direct. He is familiar with the circuit of this equipment and can often solve the problem in a few minutes. You can’t reach this level in a short time. I rely on multimeter measurement, and after several inspection methods and steps, I find out the fault and solve the problem. My method is slower, but more universal and can be used anywhere. In fact, my method is more professional and classic.

What method do you use? The two students are getting impatient.

Master Li said: According to this fault situation, I should first turn off the control power supply of the electric control cabinet and measure the resistance of the two-wire terminal of 8YA from the control terminal. It is tens of Ω , indicating that the lead wire and the solenoid valve coil are basically normal. In fact, this measurement also found that the control lead wire of 8YA was broken, and the fault can be repaired by replacing the lead wire.

Student asked: If the lead wire and coil are good, why doesn’t 8YV work?

Master Li said: Next, we should check the peripheral control circuit at the PLC output end.

Master Li said: Find the two output control terminals YO and COM0 of the PLC. In fact, there is a normally open contact of a relay inside the two terminals. To put it simply, the PLC control terminal is a small switch. When the switch is closed, relay KA8 is energized, connecting the power supply of the 8YV coil and the solenoid valve is activated, right?

We can first short-circuit the two terminals YO and COM0 to observe whether KA8 works. If KA8 works normally but 8YV does not work, and then short-circuit the normally open control contacts of KA8, 8YA works normally, it means that KA8 is broken and the normally open contacts are in poor contact. If the two terminals YO and COM0 are short-circuited, the solenoid valve 8YV works normally, which means that the PLC output peripheral circuit is good. If the terminals YO and COM0 are short-circuited and KA8 does not work, check the 24V control power supply and leads.

Of course, on the electrical control cabinet side, you can short-circuit the YO and COM0 terminals and measure the 8YV terminal to see if there is 24V voltage to determine whether the PLC peripheral control circuit is normal.

In this way, by short-circuiting the two switch points, even if the fault of the PLC peripheral control circuit is exposed, it is not necessary to check the fault during the operation of the equipment. You have to find a way to change the normal state of the circuit, make it move, and expose the fault.

What if the PLC peripheral control circuit is fine, but the 8YV still doesn’t work? Two students asked.

Master Li explained slowly as usual: This may be a problem with the PLC and PLC input signal.

How to check it? The student asked again.

Master Li said: We need to let the operator try it out.

During operation, please pay attention. If the indicator light of the YO terminal can light up, but KA8 does not attract, it means that the contact of the internal relay of the PLC is poor. The PLC should be repaired or replaced. As shown in the circuit above, when the output indicator light of the Y0 terminal is on, you can measure that the voltage between the two terminals of YO and COM0 is 0V, indicating that the internal switch is connected; when the light is off, the voltage is 24V, indicating that the internal switch is disconnected. If the output indicator light of the Y0 terminal is on, but the voltage is still 24V, the contact of the internal relay of the PLC must be damaged.

During the operation, the output indicator light of the Y0 terminal is always off. When the PLC program is running normally (such as other controls are normal in this example), it may be that the signal of the PLC input terminal is not input normally, or the state is wrong, and the conditions of YO output cannot be met. At this time, you can use a laptop to call up the PLC internal program, monitor the program running, find out the conditions that meet the Y0 output and various conditions, and then find out which input signal is abnormal, such as poor contact of the normally closed point of the external limit switch, etc., and the fault can be eliminated.

In the figure above, XO, T1, X3, X4, and T5 can all be called conditional contacts of YO. Let’s ignore T5 for now. For the control of YO, only when the XO (input condition) and T1 (after the delay time is up) contacts are connected, and the X3 and X4 contacts remain static, can YO meet the conditions for powering on. Find out which of these four contacts is not met, find the cause of the fault, and then repair it. If you check that the status of the X0, X3, and X4 contacts are all correct, and look at the PLC input terminal status indicator, X0 is on, and X3 and X4 are off, then three of the four conditions have been met, and only the T1 condition is not met. Further search for the control program segment for the T1 coil in the program, and then check the conditions for meeting the power-on condition of T1, step by step, and find the cause of the fault.

The external input signal of PLC, such as limit switch, may be installed in a place that is not easy for us to touch. Its closing and opening are not easy to operate. At this time, you can also take the method of short-circuiting YO and COM0 terminals, artificially short-circuiting the PLC input terminals, forming an input signal, satisfying the YO power-on condition, and finding out the fault. For example, short-circuit X0 and COM terminals to see if the input indicator light is on and whether the output is moving. If the input terminal status indicator light is not on, check the input terminal 24V power supply is normal, then the internal input circuit of PLC is broken.

During the maintenance process, do not forget to communicate with the operator and electrician in a timely manner. They are familiar with the operation process. You may have searched for a long time, but they may not be able to tell you the fault with just one word of reminder. For example, they mentioned that YO can only act after Y1 output delays for 10 seconds, which makes you understand that YO can only act after Y1 acts. As a result, the problem is found in the control circuit of Y1. This can greatly improve the maintenance efficiency.

When Master Li finished speaking, the two students were convinced and felt that this job was not that difficult. They were full of confidence. They learned things that they could not learn in school from this maintenance example and from the two old electricians. They felt that they had gained a lot. They felt that if the teachers who led the internship class could teach like Master Li, they would be very lucky.

Posted on Leave a comment

Alpha ALPHA2000 inverter circuit schematic and maintenance analysis

1.《Alpha ALPHA2000 18.5kW inverter》Switching power supply circuit diagram

The 530V power supply of the switching power supply is introduced from the CNPN terminal. The P terminal is added to the drain of the switching tube K2225 through the main winding of the switching transformer, and then to the N terminal through the emitter current sampling resistor, forming the input power supply path of the switching power supply. One path is added to the 6th pin of the oscillation board of the switching power supply (functional block diagram, including L3845P and other auxiliary components, see the second figure of the driving circuit for the specific circuit) through two 150kΩ2W resistors and the LED1 power startup circuit, providing excitation energy for the starting of the switching power supply. After the power supply starts oscillating, the self-powered winding of the switching transformer generates a DC power supply through rectification and filtering, which is input to pin 6 of the oscillation board as the power supply for the internal oscillation chip; pin 5 of the oscillation board is connected to the power supply N terminal, and pins 6 and 5 are the power supply pins of the oscillation board; the current sampling signal formed on the source current sampling resistor R39 of the switching tube is input to pin 3 of the oscillation board as a current control signal and a power supply stop protection signal. When an abnormal overcurrent occurs, the internal circuit forces the power supply to stop oscillating; the PWM controlled (variable pulse duty cycle) pulse is output from pin 4 of the oscillation board and connected to the gate of the switching tube to control the conduction and cutoff of the switching tube, so that the switching transformerinputs electrical energy and stores energy, and transmits the energy input by the power supply to the secondary load circuit in the form of electromagnetic transmission. The output voltage feedback signal of the switching power supply is input from pins 1 and 2 of the oscillation board, that is, the DC -15V voltage rectified and filtered by D48 and E28 outputs, which not only provides power for the CPU mainboard control circuit, but also serves as a feedback signal input to the oscillation board. Compared with the internal circuit reference voltage signal, an error voltage output is generated to control the PWM wave generator inside the oscillation board, so that the pulse duty cycle of the 4-pin input changes, adjusts the energy storage of the switching transformer winding, and maintains the output voltage unchanged.

The oscillation and voltage regulation of the switching power supply is to adjust the output voltage by changing the pulse width or period, which is called time proportion control. It is divided into two control modes: PWM (width modulation) and PFM (frequency modulation). The U3842, U3844, and U3845 series power supply chips are dedicated PWM controllers.

The switching transformer generates +11V power supply through rectification and filtering of the self-powered winding, and outputs 5V DC voltage through the 78L05C chip 8-pin voltage regulator to supply power to the input side of the U14-A7840 linear optocoupler. The U14 and LF513 two-stage amplifiers form the voltage detection circuit of the DC circuit. The DC voltage introduced from the P and N terminals is fed through a resistor divider network such as a 220kΩ 2W resistor and R54A to obtain a voltage value below 1V, which is then fed into the 2nd pin of A7840 through a 51Ω resistor . The voltage sampling signal output from the 7th and 8th pins of A7840 is fed into the input end of the differential amplifier (with an amplification factor of 1, which is actually a voltage follower for isolation and impedance transformation) composed of the subsequent LF353 through R55 and R56. The 1st pin of LF353 outputs a voltage signal that changes with the DC loop voltage, which is then compensated and adjusted by a semi-variable resistor and input into the subsequent circuit as a VPN (marked by the manufacturer on the circuit board, meaning the voltage sampling signal at the P and N terminals of the DC loop). When the input three-phase voltage is 380V and the DC circuit is about 530V, the VPN point voltage is about 3.8V .

by parallel rectification of D49 and D50 and 220μF50V current filtering is used as 1. Power supply for the cooling fan. The fan is put into operation when the inverter is powered on and there is no control; 2. Power supply for the control relay REL1 of the charging contactor coil. When the switch tube of the 1-pin of the wiring terminal CNN1 is turned on, REL1 is energized to control the charging contactor to be attracted; 3. Power supply for the module temperature detection circuit. The temperature sensor is a normally closed contact thermal relay, which is connected in series to the power supply branch on the input side of the photocoupler. When the module temperature rises abnormally, the temperature relay is activated, the normally closed point is disconnected, and the photocoupler outputs an OH overheat signal to the 14-pin of the CPU; 4. As the 24V power supply for the inverter control terminal. Other power supplies are omitted here.

The circuit on the lower side of the figure is a three-phase output voltage abnormality or three-phase output violent fluctuation or three-phase output phase loss detection circuit. This circuit form seems familiar to us. This circuit form of three-phase output voltage detection circuit has also been used in other inverters. At first glance, this is a typical instrument small signal amplifier, but it is not the case upon closer inspection. Due to the effect of the two input ends of the amplifier parallel diodes bidirectional clipping clamping, it means that the circuit no longer undertakes the task of amplifying small signals, but plays the role of shaping and synthesizing the input U and W two-phase signals into V-phase signals. Just like the principle of holography, if we look at it from the perspective of holographic theory, the U and W two-phase voltage signals must contain the information of the third phase V-phase voltage. Similarly, the synthesized V-phase signal contains the information of the U and V two-phase signals (in fact, the synthesized signal can be considered as the information of the three-phase voltage signal). I guess the subsequent circuit – the CPU’s internal hardware and software circuits is a circuit similar to a frequency meter, which counts the voltage wave heads input to the circuit. When it detects that a half-wave (or full-wave) of the three-phase output is missing, it determines that the output is missing a phase, and a fault alarm is given and the machine is shut down for protection.

2.《Alpha ALPHA2000 18.5kW inverter》 drive circuit, oscillation board circuit diagram

To check the fault of the driver IC or IGBT module, you must know the principle of the A316J (HCPL-316J) protection circuit and the corresponding output state (level value) of the key functional pins. Let’s first look at how the internal and peripheral fault protection circuits of the A316J work. The figure shows the two-way drive circuit, and the remaining space is filled in here with the circuit inside the oscillator board of the switching power supply circuit, which is also mentioned in passing.

Combined with the above figure (a typical circuit in the A316J related information, it is easy to see the connection between the fault protection circuit and the IGBT), let’s talk about the action flow of the protection circuit. Readers, please first understand the power supply circuit and pulse output circuit on the input and output sides. This part depends on you to read it yourself. The space is limited.

Pin 14 of A316J is the module OC fault (overcurrent fault) detection input terminal, which is connected to the C pole of IGBT through an external 100 Ω resistor and an embedded diode, and pin 16 is connected to the emitter of IGBT. Pins 14 and 16 of A316J and the external circuit constitute the IGBT tube voltage drop detection circuit. Under normal working conditions, during the transmission of the drive pulse, the IGBT tube is reliably turned on, and the external diode of pin 14 is forwardly turned on due to the conduction of the IGBT tube, and the voltage value of pin 14 is embedded in the low (zero) level value of the voltage of pin 16. The internal fault detection circuit does not work, and the pulse transmission channel is unblocked. The internal circuit of pin 11 normally outputs the inverter pulse signal, and the module OC alarm signal output pin 6 also outputs a high-level signal under normal conditions; when the load current is abnormal, the inverter pulse signal path is poor, or the IGBT itself fails, causing the IGBT tube voltage drop to be greater than 7V, the external diode of pin 14 is reversely cut off, and a high-level signal appears between pins 14 and 16. The internal fault detection circuit is activated. On the one hand, the transmission of the pulse channel is blocked through the internal circuit, and on the other hand, the fault protection circuit is activated, so that pin 6 outputs a low-level module OC fault signal and sends it to the previous CPU circuit. When the IGBT has an overcurrent, the drive voltage output by pin 11 drops, causing the IGBT to softly shut down to avoid sudden shutdown caused by overvoltage caused by lead inductance and damage to the IGBT. When the internal IC power supply detection circuit detects that the input power supply voltage is higher than the internal reference voltage value and there is no overcurrent signal input, the pulse transmission channel works normally. If an undervoltage signal is detected, regardless of whether the pulse channel is transmitting normally, the internal fault protection circuit will be activated to turn off the upper tube (transmitting the driving voltage) of the push-pull output stage inside the A316J, and at the same time turn on the lower tube (transmitting the cut-off voltage) to softly turn off the IGBT.

After the module OC fault protection circuit is activated, the 6th pin of A316J will be locked in the low-level fault signal output state until a low-level reset signal is input from the 5th pin. An external circuit must output a fault reset signal to release the circuit lock state. The 14th pin is connected to an external embedded diode, and its working parameters have special requirements, reverse withstand voltage ≥ 1000V, turn-on time = 75ns. If ordinary diodes are used instead, the detection and protection function will be lost due to the charge storage effect of the junction capacitor, causing damage to the IGBT.

The oscillator board of the switching power supply is connected to the power supply/driver board through six pins. The -15V DC voltage output by the secondary winding rectification is input to the voltage stabilization control circuit of the oscillator board through pins 1 and 2. The voltage stabilization circuit consists of U3 (8-pin SMD TL431) reference voltage source and U2 (181349D) photocoupler. The change of -15V output voltage causes the change of input current of the light-emitting diode inside U2. The output internal resistance of the phototransistor on the output side of U2 changes accordingly due to the different amount of light received. This change signal is input to pin 2 of U1 (3845). The internal circuit of U2 controls the duty cycle of the output pulse of pin 6 of U2, and outputs the driving pulse to the gate of the switch tube through pin 4 of the oscillator board, controlling the on/off time ratio of the switch tube, thereby maintaining the output voltage of the secondary winding of the switching transformer within a certain value. The working current signal of the switching circuit is introduced into pin 3 of U1 through the R7 and C7 loop, and the internal circuit implements current closed-loop control and overcurrent protection.

Posted on Leave a comment

the control terminal circuit of Inverter CPU motherboard

1. Digital control terminal circuit:

The operation control terminal of the frequency converter receives, outputs and processes two types of signals: digital and analog. Analog signals are generally used to input frequency instructions of 0-5V (10V) to determine the output speed of the frequency converter; output analog voltage signals corresponding to the output (given) frequency for external frequency meters to display the operating frequency, etc. The input signals of digital signals are used for the start/stop and fault reset of the frequency converter; the output switch signals are used for external relays and indicator lights to monitor the fault or operating status of the frequency converter, etc.

The following figure (Figure 1) is a digital control terminal circuit, 3 is a digital signal common terminal, 5, 6, 7, 8, 9 are digital signal input terminals. When any of the signal input terminals is connected to the common terminal 3, it can form an input path of the optocoupler, thereby transmitting the control signal to the CPU. The benefit of using optocouplers is that in addition to achieving electrical isolation, it also improves the anti-interference performance. The signals of the inverter control terminal, both input and output, are directly from the CPU pins. Pins 13 to 17 of the CPU are the switch control signal input pins. Pin 22 outputs the switch signal, and the signal content (operation, fault, etc.) can generally be set by parameters, also known as the programmable output terminal. The output signal provides a forward base bias current for the control switch tube TR3 through R36. The conduction of TR3 directly drives the RY1 relay, and the switch signal is output from the three terminals A, B, and C for the external indicator light or relay to indicate the working status of the inverter.

The output from the 76th pin of the CPU is a pulse signal representing the output speed, which drives the transistor TR2 through R27, and TR2 drives the optical coupler PC2. The pulse signal output by PC2 is filtered into a smooth DC voltage by R75 and C28, and is added to the subsequent two-stage voltage follower for current amplification, and then outputs a 0-10V (frequency output) analog signal from the control terminal 4. This circuit can actually be regarded as a simple analog/digital conversion circuit. Although the terminal output is an analog voltage, the CPU output is still a digital (pulse) signal.

For digital (switching) signals, at any time, the input and output potentials of the circuit are both in two states: 0 (ground potential of the power supply) and 1 (positive terminal potential of the power supply).

Figure 1: Panasonic VFO 220V 0.4kW inverter CPU motherboard circuit 2: digital control terminal circuit

The following figure ( Figure 2 ) is still part of the control terminal circuit. Because the four bidirectional analog switch circuits of IC4 (BU4066BCK) are used for unified input and output processing, the digital/analog circuits are drawn together for ease of reading. IC4 can transmit digital and analog signals. It contains four sets of bidirectional switches. Each set of switches has an independent on/off control terminal CTL. When the terminal is at a low level, the switch is in the off state, and the I/O and O/I are in a high impedance state; when the CTL terminal is at a high level, the switch is in the on state. The purpose of using a bidirectional analog switch is to make the transmission of the signal controlled by the CPU instruction, thereby realizing programmable input and output control. The circuit switches the input of two input signals and switches the output of two digital signals.

Figure 2 Panasonic VFO 220V 0.4kW inverter CPU motherboard circuit 3: digital/analog signal control terminal circuit

For the switching control of the two input analog signals, in order to facilitate the principle analysis, the analog signal path in the circuit of Figure 2 is redrawn as follows:

Panel frequency command circuit: VR1 is a potentiometer on the operation display panel, which can adjust the inverter output frequency from the operation panel. The adjustment voltage of VR1 is input to the 61st pin of the CPU through the R90 and C11 anti-interference circuits, and after internal A/D conversion, it is output from the 17th pin, through the IC4 bidirectional analog switch, and connected to the 11th pin of IC4, and then input to the 79th and 80th pins of the CPU;

Terminal frequency command circuit: The control terminal 2 inputs the variable voltage signal of the center arm of the external potentiometer, which is first converted by IC5 (93321N) into a U/F signal and then converted into a frequency signal proportional to the input voltage. It is then sent to another set of bidirectional analog switches inside IC4 through the PC1 (TLP759) photocoupler and output from pin 11.

The two frequency command signals are controlled by the level states of the CPU’s 39 and 40 pins, and further controlled by the user’s control intention. The control parameters can be set. When the 40 pin is high and the 39 pin is low, the CPU inputs the frequency command from the operation panel and determines the output frequency accordingly; otherwise, the control terminal is connected to an external potentiometer (or other analog voltage control signal, such as an instrument output signal, etc.) to adjust the output frequency.

Control terminals 10 and 11 are open collectors, and the switch signal output can realize programmable output. The user sets the output content through parameters, or the terminal is connected during operation, or the terminal is connected during failure. Under the control of the CPU’s 41-pin output instruction, when the analog switch 1 and 2 are connected, the photocoupler PC8 is driven by TR8 and turned on, and the terminals 10 and 11 are in a low-resistance state, outputting an operation signal; when the analog switch 3 and 4 are connected by the CPU’s 40-pin output instruction, the terminals 10 and 11 are also in a conducting state, but the output at this time is the inverter fault signal.

Similarly, the content of the output signal depends on the user’s intention – the CPU’s instructions. The two sets of analog switches play the role of a two-throw switch. Different output contents are switched according to the user’s intention.

Posted on Leave a comment

Function diagram of common IC pins in inverter circuits

illustrate:

From the perspective of application maintenance, it is enough to master the pin functions of some IC devices, so as to measure the voltage (level) status of some pins and judge whether the IC is in normal working condition. It is too late and unnecessary to care about what kind of circuit is inside the IC. For example, for the single-chip microcomputer circuit, it is enough to focus on detecting the voltage (level) status of the power supply, reset, crystal oscillator, control signal, and input signal terminals. For digital (including optocoupler) circuits, in general, knowing the pin functions of the device, it is possible to measure and judge the quality of the IC based on the logical relationship between the input and output terminals. As for the analog circuit, half of it is used to process switch signals in the inverter circuit, such as voltage comparators, etc., and it is as convenient to detect and judge as digital circuits. Some analog circuits that process analog signals can be measured based on the obvious changes in dynamic and static voltages, which is not too difficult.

Therefore, as long as you know two points, 1: What type of chip is the IC, digital or analog circuit? 2: The pin function, is the pin an input, output or power supply pin? Then you can implement the measurement. The commonly used IC pin function diagrams of inverters are concentrated in the appendix, so you don’t have to spend a lot of time to consult the relevant manuals.

1. CPU (microcontroller) chip and peripheral IC circuit pin function diagram:

(1)CPU chip-MB90F562B SMD package 64 pins, widely used:

(2) CPU chip – S87C196MH SMD package 80 pins, widely used:

(3) CPU chip – MN18992MDY-6 plastic package dual in-line plug, 64 pins, used for Panasonic’s early DV551 and DV561 models:

(4) CPU chip – HD6404733037F SMD package 80 pins, widely used:

(5) Memory pin function diagram:

(6) RS485 communication module pin function diagram:

(2)Commonly used operational amplifier pin function diagram:

LF353 dual op amp circuit LM393 dual op amp (open collector output) TL072 quad op amp circuit

Operational amplifiers are mostly used in current and voltage detection circuits to process analog signals and convert them into switch signals – alarm and shutdown protection signals. Open collector output types are mostly used in voltage comparator circuits. Operational amplifiers have good interchangeability. For example, LF347, LM324, and TL072 can all be directly replaced. When the pin arrangement is inconsistent, the terminal wiring can also be replaced.

Open collector output operational amplifiers must be replaced with amplifiers of the same type.

3. Commonly used digital IC circuit pin function diagram:

BU4066 Quad Bidirectional Analog Switch 74LS244 Octal Buffer/Line Driver/Line Receiver (Tri-State)

Digital integrated circuits are also divided into several types according to different materials and manufacturing processes. However, they are mainly TTL (transistor-transistor logic) integrated circuits and CMOS (complementary metal oxide semiconductor logic) integrated circuits. The 74 series TTL circuits and the 4000 series CMOS circuits are the most widely used and have the largest number of applications. TTL circuits consume slightly more power, but have higher operating frequencies and stronger output current capabilities, and the power supply voltage is 5V; CMOS circuit characteristics are the opposite. There is a wider power supply voltage range (3.0-18V ) . Under 5V power supply conditions, the same type of circuits can be interchanged. Under different power supply conditions, if the TTL circuit is damaged, you can consider replacing it with a CMOS circuit.

4. Commonly used driver ICs:

TLP250 and HCPL3120 can be directly replaced, and the output pins can be changed to replace PC923. PC923 and PC923 are often used in combination, while A4504 and MC33153 are also used in combination. The combination of the two completes the function of PC929.

5. Commonly used photocouplers:

Optocouplers are used in the control terminal circuit of the inverter, voltage sampling and isolation of the switching power supply, etc. As long as it is a four-wire terminal component, it can often be replaced by PC817. Linear optocouplers cannot be replaced by ordinary optocouplers, and it is best to replace them with original model devices.

6. Switching power supply oscillation chip:

The pin functions of UC3842 and UC3844 are the same, and both have 8-pin and 14-pin packages. UC3842 and UC3843 can be interchanged; UC3844 and UC4845 can be interchanged.

7. Commonly used power (inverter) modules:

The packaging form and size of the power module are consistent, and the rated current value of the replacement module should be equal to or greater than the original damaged module.

Intelligent power modules should be replaced strictly according to the original model.

Posted on Leave a comment

616G3-55kW Yaskawa inverter main circuit diagram and inverter maintenance ideas

1. Main circuit of “616G3-55kW Yaskawa inverter”

The structures of the main circuits of all inverters are similar or even identical. The main circuits of Yaskawa inverters and Taiwan Teco inverters are exactly the same. Later I observed that the control panels of the two machines are the same, and the control panel and parameter settings are also similar. It is found that the two machines are similar or even identical from hardware to software, which will bring a lot of convenience to installation, debugging and maintenance. As long as there is a technical data reference at hand, you can debug and repair the two devices.

When we open the shells of these two high-power inverters and check the main circuits, the six large rectangular box-shaped objects installed above the inverter modules (in parallel with the modules) will first arouse our interest – the model number MS1250D225P is connected in parallel with the upper arm IGBT tube of each phase, and the model number MS1250D225N is connected in parallel with the lower arm IGBT tube. To use a phrase from the Internet: What on earth is this? What is the purpose of installing it here?

Generally speaking, anything connected in parallel to the IGBT tube, whether it is a capacitor or a resistor-capacitor network, is set up to protect the IGBT tube. That is, when the tube is cut off, the energy formed by the reverse voltage is quickly consumed, providing a reverse current path to protect the IGBT tube from (in fact, it makes it bear less) the impact of reverse voltage. As we all know, whether it is a bipolar or field effect device, there is often a certain amount of surplus in the forward voltage, but the ability to withstand reverse voltage is extremely fragile. Therefore, the things connected in parallel to the IGBT tube can be said to complete this task of consuming reverse voltage.

It should be noted that the internal circuits of MS1250D225P and MS1250D225N were not opened for verification. After the module was damaged, these two devices were often intact, so it was not convenient to disassemble them after they were damaged. The internal circuit in the above figure was drawn based on measurement and speculation, and is only a reference for readers. I have searched a lot of information and searched on the Internet, but I have not found any information about this component. It is obviously easy to mislead to analyze the principle based on the speculation of the circuit. Therefore, the analysis of its principle is temporarily omitted.

However, after connecting such components in parallel to the module, it will bring us new experience in maintenance. See below.

According to the conventional maintenance method, after replacing the damaged module, before conducting the power-on test, we must cut off the P point in the above figure, connect two 25W (or 40W) bulbs in series, and then power on. In this way, if the inverter module circuit or drive circuit is abnormal, causing the two IGBT tubes of the upper and lower arms to short-circuit the DC power supply, the expensive IGBT module will not be damaged due to the current limiting effect of the bulb. Other brands of inverters connect small-capacity capacitors of the picofarad level in parallel at both ends of the tube. After powering on or starting the inverter, as long as the U, V, and W output terminals are unloaded, the bulb will not light up. But the performance of Yaskawa inverters in maintenance is different. Connect a bulb in series at point P, power on, and the bulb does not light up. It is correct, I breathed a sigh of relief; press the operation panel to start the inverter, and the bulb becomes bright! It is broken, the output module has a short circuit! This is my first judgment. Check the module and drive circuit during power outage, and there is no abnormality. Looking back at the circuit structure, after removing the MS1250D225P and MS1250D225N, the light bulb did not light up after starting the inverter. The three-phase voltage of the no-load output was normal. These two components and the external 10 Ω 80W resistor provided a current path of about 100 mA, making the 25W bulb bright. Sacrificing tens of watts of power consumption in exchange for higher safety of the IGBT tube is the characteristic of the module protection circuit of the Yaskawa inverter.

After the inverter is started without load, due to the relationship between components such as MS1250D225P and MS1250D225N, the inverter circuit itself forms a certain circuit path, which is not caused by the inverter module failure. This machine is a special case. The existence of a circuit path does not necessarily mean that the module is damaged. Observe which components provide the current path? When fresh experience solidifies into a fixed mindset, misjudgment of faults is inevitable.

The control power of the whole machine is obtained from a multi-tap transformer at the bottom of the figure. The short-circuit wires of sockets 3CN and 4CN are different, and the level of input voltage can be adjusted to ensure the accuracy of the secondary winding AC220V voltage. The cooling fan uses an AC220V power supply, which is filtered and used as the input of the switching power supply. When repairing the driver board alone, the terminals 2 and 3 of the fan; 3 and 4 of the contactor terminals; 14CN, 15CN, and 16CN must be short-circuited, and fault signals such as undervoltage (FU/LU), overheating (OH), and fan failure (FAN) must be manually eliminated, so that the CPU can output six pulse signals, which is convenient for checking the drive circuit.

2. Drive/protection circuit of “616G3-55kW Yaskawa inverter”

“616G3-55kW Yaskawa Inverter” drive circuit/protection circuit diagram

The types of drive circuits are similar. The most common ones we see are drive detection circuit (protection circuit) is also integrated. Although you can find circuit information about A3316J, etc., and you can see the internal unit block circuit diagram and the introduction of the circuit principle, you always feel a little confused about the specific composition of its protection circuit – the protection circuit inside the IC is indeed invisible and intangible. It happens that this circuit is a detection and protection circuits composed of ICs such as PC929 and A316J, in which the module fault circuit composed of discrete components, which makes it easier to understand the detection and protection action process. Slightly redrawing the pulse and protection circuit in the above figure, you can see how the IGBT tube voltage drop detection circuit implements the protection action on the module:

Circuit principle: The PWM pulse signal from the CPU pin is isolated and amplified by the U2 optocoupler and then sent to the module protection circuit. Under normal conditions, this pulse signal is amplified by the push-pull power amplifier circuit of Q2 and Q3 to directly drive the IGBT module. It is generally believed that the IGBT module is a voltage-type drive module, which is biased. The input gate-emitter junction capacitance of the IGBT tube just needs a transient large inrush current! This is why Q2 and Q3 are used for power amplification. The introduction resistor of the drive signal is also a 5 Ω 8W power resistor. In this sense, in essence, the IGBT module is still a current-type drive device. This is the author’s opinion, is it correct? When the current output capacity of the drive circuit is insufficient, the three-phase output current will be intermittent, the motor will vibrate, and a rumbling sound will be emitted. The principle of the pulse processing circuit can be found in other figures. The focus here is on how the protection circuit works.

When the inverter does not receive the start signal, the output pins 7 and 8 of U2 are cut-off negative voltages. If the 0V power line is used as the reference point, the voltage of pins 7 and 8 is about -9.5V (ignoring the saturation voltage drop of the internal tube). This negative voltage is introduced to the base of Q2 and Q3 through R13 and R3. Q2 is cut off due to reverse bias, Q3 is turned on due to positive bias, and the gate bias of the IGBT module is negative and is in the cut-off state. Resistors R1 and R2 divide +15V and negative -9.5V to obtain a 3V level. D9 is a voltage regulator with a breakdown voltage value of 9V. The voltage division value of R1 and R2 is not enough to cause it to break down, so Q3 has no bias current and is in the cut-off state. There is no input current to the photocoupler U1, so no fault signals such as GF (grounding) and OC (overload, short circuit) are returned to the CPU. When the CPU sends a drive pulse, the 7th and 8th pins of U2 become positive pulse voltages with a peak value of 15V, and the positive pole of D1 rises to +15V at this time. At this time,two situations occur: In one case, the module is good, and the IGBT tube is quickly turned on under the drive of the positive excitation pulse. It can be considered that the P and E points are short-circuited instantly. The negative terminal potential of D1 is instantly pulled to 0V, and the negative terminal potential of D2 is also pulled to below 1V. Because it does not reach the breakdown value of D2, Q3 still has no base bias current and is cut off; In another case, the module has caused the operating current to be too large due to abnormal load, or the IGBT tube is not turned on well due to the poor driving circuit itself such as Q3. The negative terminal of D1 is high potential and is cut off, and +15V causes D2 to break down through R1, Q3 is biased and turned on, and the positive pulse voltage of the base of Q2 is pulled to zero level, and the IGBT module loses the pulse and is cut off. At the same time, the conduction of Q3 generates the input current of U1, and U1 sends the module fault signal to the CPU. It can be seen that the protection circuit of this circuit first cuts off the driving pulse of the IGBT tube and sends out the module fault signal at the same time. The protection is timely and fast.

3. Drive/FU circuit of 616G3-55kW Yaskawa inverter

“616G3-55kW Yaskawa Inverter” Drive/FU Circuit Diagram

The protection circuit of the drive circuit implements protection actions and sends OC signals according to the tube voltage drop of the IGBT tube during the sending of the excitation pulse. According to the information, the on-state voltage drop of the IGBT module is about 3V under normal (rated current) conditions. When the tube voltage drop reaches 7V or more, it means that the current flowing through the IGBT module has exceeded 180% to 200% of Ie. At this time, the protection action is of course the faster the better. The purpose of setting up this protection circuit is to make up for the slow protection action of the subsequent current detection circuit such as the current transformer. The current detection circuit inevitably uses a large capacity filter capacitor, which makes the circuit have a certain time constant and slow response. The tube voltage drop detection circuit of the IGBT can be called a fast protection action circuit because of its rapid response, just like a fast action unit, which is used to deal with emergency events. The treatment of slight overcurrent and current limiting regulation is still implemented by the current detection circuit of the current transformer circuit.

The drive circuit is also equipped with a fuse detection circuit. In general, a fast-blow fuse is connected in series at the P end of the DC circuit to implement module protection. However, this machine circuit has a fuse connected in series at each phase output module. The inverters produced by each manufacturer generally have the following trends: early products are inevitably crude, old and heavy, and their user control functions are not perfect, but there is a large margin in their production and selection of materials; they are conservative in protection performance, but they do not hesitate to add components that seem redundant now to ensure the reliability of the protection circuit. The early products of Yaskawa inverters were no exception. With the advancement of product technology and the fierce market competition, the functions of inverters have been improved, while the costs have been reduced, and there is even a suspicion of cutting corners. The operating reliability of inverters has also been compromised, and domestic inverters should take this as a warning.

The detection circuit of the three-way fuse blown is to compare the 0V line of the lower three-arm drive power supply with the N line of the main DC circuit to determine whether the fuse is normal. Under normal conditions, the 0V line and the N line of the drive power supply are connected through the fuse and are of equal potential. That is, the E pole of the lower three-arm IGBT tube is connected to the N line of the main DC circuit. Therefore, the base bias of the transistors Q4, Q19, and Q28 is zero. All three tubes are cut off. When the fuse of any phase output module is disconnected, the N line and the 0V line of the phase drive power supply produce a huge potential difference, and the transistor is turned on by positive bias. The three optical couplers Q5, Q20, and Q29 are connected into an OR gate circuit. The input signal of any optical coupler will be transmitted to the same output point, and the fuse signal of the fast insurance will be transmitted to the CPU, so that the CPU reports the FU (fuse) broken signal and refuses to accept the start signal.

There is also an interesting problem of the order of fault signal alarm of Yaskawa inverter. For example, when the power is on, a warning of the fault code is given for overheating, undervoltage, overcurrent, fan failure, fuse failure, etc., and the startup operation is refused; during the startup, the module fault detected by the module protection circuit is warned with the GF (ground fault) code. When the module fault is detected during operation, the OC (operating overcurrent, load short circuit, etc.) fault code signal is reported. The same signal output by the IGBT tube voltage drop detection circuit is output at different times (one is during the startup process, and the other is during the operation process), but the inverter reports two different fault codes (GF: ground fault; OC: overload or short circuit fault). Similarly, in the current and voltage detection circuits, the same means are sometimes used. The overcurrent or overvoltage signal reported by the same protection circuit may report different fault codes or take different treatment measures due to the different working states of the inverter (starting or running). All this depends on the ideas of the software designer. The control ideas of each manufacturer’s inverter must be similar. Pay attention to the relevant characteristics of the inverter fault alarm to facilitate efficient diagnosis of the fault.

When analyzing the protection circuit, you need to look at the main circuit and the drive (protection) circuit in two or three parts. Many drawings are broken down into individual unit circuits. Readers must strengthen their ability to read drawings in a comprehensive and coherent manner. This is a piece of advice I give you.

Posted on Leave a comment

Debugging ideas and methods of Siemens G120 VFD PM240

As an important part of Siemens automation solutions, Siemens G120 series inverters are designed for high-performance applications. This series of inverters not only supports a wide range of motor types (including asynchronous motors, synchronous motors and servo motors), but also has excellent dynamic response capabilities and a rich set of functions, which can meet various needs from simple speed control to complex positioning control.

In the field of industrial automation, Siemens G120 series inverters are widely used in various motor control applications due to their high performance, high reliability and easy integration. This article combines multiple professional materials to provide engineers with a detailed Siemens G120 series inverter commissioning guide to help everyone better master the commissioning skills of this key equipment.

A、 BOP-2 operation panel description

The BOP-2 basic control interface is cleverly placed at the top of the control module. It plays a key role in inverter commissioning, operating status monitoring, and specific parameter configuration. This operation panel is unique and adopts a dual-line display design: the upper line focuses on displaying the specific values of the parameters, which is intuitive and clear; the lower line corresponds to the clear name of the parameters, which is convenient for users to quickly identify and operate. It is particularly worth mentioning that BOP-2 allows users to easily copy the various parameters of the inverter to the operation interface, and when necessary, easily download these parameters in batches to the inverters of the same series, greatly improving work efficiency and data management flexibility.

  • As shown in Figure 1, the BOP2 operation interface of the G120 inverter is detailed, and its main components include:

1. Motor Monitoring: This area focuses on real-time status monitoring of the motor, ensuring that users can instantly obtain key indicators of motor operation.

2. Control Operations: This section provides direct control of the inverter and the connected motor, allowing users to flexibly adjust the operating status.

3. Fault Diagnosis Area (Diagnostic Analysis): Specially used to identify and display possible system errors or abnormal conditions, so as to quickly locate the problem and handle it.

4. Parameter Settings: This area allows users to adjust and optimize the inverter parameters according to actual needs to achieve the best working performance and efficiency.

5. Setup Configuration: Focuses on the configuration management of the inverter itself, including network settings, security parameters, etc., to ensure stable operation of the equipment and compliance with safety standards.

6. Extra Features: Provides a series of additional practical functions or advanced settings to meet specific applications or user preferences.

(B)The hardware layout of the operation panel is equipped with multiple intuitive and easy-to-use buttons, as shown in Figure 2, including:

1. Escape key (ESC): used to exit the current operation or return to the previous menu.

2. Confirm button (OK): Execute the current selection or confirm the modified settings.

3. Mode switch key (HAND/AUTO): allows the user to easily switch between manual control mode and automatic operation mode.

4. Direction control keys (↑/↓): Used to move the cursor up and down in the menu and select the desired option.

5. Green start button: represents the command to start the motor safely, ensuring that the motor is started under safe conditions.

6. Red stop button: used to immediately stop the motor in an emergency to ensure the safety of personnel and equipment.

This design not only improves the convenience of operation, but also enhances the user’s ability to control the operating status of the inverter.

B、Quick debug mode operation

When starting up the inverter for the first time, the first step is to reset its parameters to factory settings. By navigating to the “setup” menu and confirming the “reset” operation, a selection box will pop up, showing the two options of “no” and “yes”. After explicitly selecting “yes” and confirming, the inverter will automatically initialize and return to the default configuration state. This step is to eliminate all existing motor-related configurations, ensure a pure test environment, avoid any potential unnecessary parameters from interfering with the normal operation of the inverter and motor on the test bench, and lay a stable foundation for subsequent debugging.

After completing the reset, there is no need to perform a power-off restart operation. Jump directly to the “parameter” interface, where you will see two options: “standard” and “expert”. Select to enter the “standard” level, first set P10=1, and then accurately configure various related parameters based on the motor nameplate information and refer to Table 1.

Then, set the P1900 parameter to 1 to start the dynamic self-learning process of the motor. Then, adjust P10 back to 0. Press the “esc” key to return to the main interface, and then tap the “HANDAUTO” key. The hand icon representing the manual mode will appear on the screen. At this time, use the ↑ key to manually set the target speed of the motor. The recommended setting value is about 50 rpm. Then, press the green motor start button, and the motor will enter the self-learning state. During this period, the screen will display the “MOTID” logo, and the motor and inverter may make some noises, which are all normal reactions.

When the motor identification and self-learning process is successfully completed, the error message X that may have existed will automatically disappear, indicating that the motor’s rapid commissioning phase has been successfully completed. At this point, the user can flexibly set the motor speed through the BOP-2 operation panel to achieve manual control of the rotation without having to power off again.

It is worth noting that in order to ensure that all settings are saved, it is necessary to re-enter the “standard” mode after completing the settings and set the P971 parameter to 1. This step is crucial because it ensures that the configured parameters can be retained even after the inverter is powered off and restarted, avoiding the frequent flashing of the inverter green light RDY (indicating that the parameters are not set correctly, affecting the operation of the motor), while also ensuring that the motor can continue to accept manual control. In addition, during the motor self-learning period, please maintain a proper distance to prevent accidents.

C、Quick debugging mode graphic specific operation process

The key to achieving quick start-up and stable operation of the motor lies in the accurate configuration of a series of core parameters, including the performance setting of the motor, the selection of the inverter command receiving source, and the clarification of the speed control source. This series of operations together builds an efficient and convenient motor commissioning process. With the help of BOP-2 (Basic Operation Panel) for quick commissioning, the specific steps can be summarized as follows:

During the quick commissioning process, if parameter P1900 is configured to a non-zero value, after the commissioning is completed, the inverter will immediately trigger the A07991 alarm message, clearly indicating that the motor data identification process has been activated and is in standby state, waiting for further start instructions. This step is an important part of ensuring the matching degree between the motor and the inverter and optimizing performance. Users should refer to Section 5.2 “Static Identification” in the inverter manual to understand the details and precautions of this process in detail so as to smoothly perform subsequent operations.

D、Specific method flow for setting parameters

Through the BOP-2 interface, users can easily adjust various parameters. The specific operations are located in the “PARAMS” (parameter setting) or “SETUP” (configuration) menu. Simply modify the required parameter value.

1. Select parameter number:

2.To modify a parameter value:

E、BOP-2 Manual Mode

F、Upload parameters from VFD to BOP-2 panel

G、Download parameters from BOP-2 panel to VFD

H、Main parameter settings

I、Communication parameter settings

After the motor acceleration debugging process is successfully completed, the next step is the key step of the communication configuration link. Entering the “parameter” interface, two major paths are presented in front of you: one is “standard” (standard mode), which is suitable for basic and broad needs; the other is “expert” (expert mode), which unlocks deeper customization and extended parameter options. When you step into the “expert” hall, you need to accurately adjust the parameters closely related to communication and other advanced settings one by one according to the carefully prepared Table 3 (parameter configuration guide). It is worth noting that there is no need to touch the P10 parameter (that is, the start switch P10=1 for motor quick debugging) at this time, because it has been properly set in the previous debugging stage, laying a solid foundation for the subsequent communication configuration.

After completing the setting of all parameters, the next necessary maintenance step is to power off the inverter and then restart the device. When restarting the inverter, in order to ensure that the system is stable and smoothly transitions to the new configuration state, the recommended restart interval should not be shorter than one minute. This waiting time gives the system enough buffering and reset opportunities.

During the period when the inverter is powered off, you can make full use of the time to carefully check the configuration of the inverter on the OPC (operation control panel or host control system), including but not limited to the serial port number, baud rate setting and device address confirmation. These steps are crucial to ensure seamless connection of the communication link.

After the inverter restarts and runs stably, you will find that the communication between the inverter and OPC has been successfully established, and the data transmission between the two will become smooth and unimpeded, laying a solid foundation for the subsequent automated control process.

Posted on Leave a comment

Maintenance Method of Basic Circuit of VFD CPU Board

1. What is CPU?

CPU, also known as central processing unit, is generally composed of arithmetic unit, controller, internal memory, input/output device, interface circuit and bus. However, with the advancement and update of technology, its functions and structure are constantly expanding – the original CPU peripheral circuit is also integrated into the device. When its hardware equipment is expanded to a certain scale, so that it can independently complete a more complex control function, this device is called a microprocessor. In the microprocessor family, in order to be suitable for a certain application field, the hardware structure is different from the general microprocessor (such as 80C51) – there is a certain uniqueness. For example, the microprocessor often used in the inverter referred to in this article has a six-way PWM wave output function and can realize specific control functions. It is also called a microcontroller, alias: single-chip microcomputer. Because people in the industry generally refer to the circuit board of the inverter single-chip microcomputer as the CPU motherboard, from the perspective of convention and concise definition, this book also calls the microcontroller (single-chip microcomputer) CPU.

The microcontroller used for inverter control, also known as “high-performance microcontroller”, should be a dedicated control chip developed specifically. It should have at least six PWM wave forming and output circuits and ports to output the six inverter pulses required by the drive circuit; it should have an A/D conversion circuit, and some should also have a D/A conversion circuit to adapt to the processing of analog input and output quantities; it should have high-speed pulse signal input and output ports and serial port sending and receiving pins to process various digital signals and communication instructions; it should contain program memory and data memory to store programs, original data and rewritable data; of course, it should also have port drivers, various buffers and other circuits, which will not be repeated here.

What goes in and out of each CPU pin is nothing more than some “signal flows”. Some only go in but not out, and go but not return, such as the switch signal input by the control terminal; some only go out but not in, and go but not return, such as the relay signal output by the CPU on the control terminal; some go in and out, such as the signal transmitted between the CPU and the memory, and the operation display panel. This type of signal is bidirectional. All signals can be divided into two categories based on their nature: digital and analog. Voltage detection signals and speed control command signals are often analog, while the start and stop signals of the inverter and keyboard input signals are digital (switch quantity). Some analog signals are processed by the CPU external circuit, such as A/D conversion, before being sent to the CPU. Some directly enter the CPU pins and are processed by the internal A/D circuit. The different CPU hardware function circuits used will inevitably lead to different external circuits.

The integration of microcontrollers is high enough. It is impossible to integrate all the circuit elements required for operation without limit. It needs the active cooperation of external circuits to work. There are three working conditions that are necessary for microcontrollers, the so-called three elements of CPU operation: +5V power supply, working clock, and reset signal. The generation of working clock is generated by the oscillation circuit composed of the internal circuit of the microcontroller and the crystal oscillator element connected to the pin; the reset signal is generated by the external reset circuit when the power is on. A low-level (or high-level) pulse is sent to the reset pin of the microcontroller, and the internal circuit controls the program reset and enters the standby state. The program memory and data memory (referred to as memory) inside the microcontroller have limited capacity and use. External memory-electrically erasable memory is often required to complete some data storage tasks (especially user program storage tasks), which should constitute the four elements of the normal operation of the microcontroller. In order to accept the user’s instructions or inform the user of the working status of the inverter, the microcontroller needs a human-machine interface-operation display panel, communicate with the user, and normal communication with the operation display panel becomes the five elements of the microcontroller’s operation. In addition, the quality of the external circuits of each pin of the microcontroller will affect the operation of the microcontroller. Since then, seven or eight or even dozens of elements of the microcontroller’s operation have appeared. In fact, in my opinion, from the perspective of the microcontroller (or microprocessor, CPU) itself, three elements are necessary for the work. Without them, the microcontroller cannot meet the most basic working conditions. If the microcontroller does not work due to other reasons, it is the external circuit, not the microcontroller itself that is not working, right?

The external circuit and external framework of the microcontroller have been built, but a “body” alone cannot work. It also needs a “soul” to command the operation of the body – the software control program. The program capacity of the inverter is large, generally up to thousands of lines. The control function of the microcontroller is concentrated on two points. One is the control of the output PWM wave. In this regard, there is a clear difference between high-quality and low-quality inverters. Some PWM waves are very optimized, while others are a bit bad – the output torque is small, the operating noise is large, and the carrier interference is also large; the other is the state detection and protection of the inverter module. This task is completed in conjunction with the external circuit, and it is also the focus of the inverter circuit.

Microcontroller – single-chip computer technology has become an important technical branch of automation control technology. I hope that friends can master more relevant knowledge themselves. I will not go into details here.

The failure rate of the CPU motherboard is relatively low, accounting for about 20% of the total failure rate. Failures mostly occur in the fault detection circuit and the control terminal circuit. The inspection and maintenance of the fault detection circuit has become an important inspection content of the CPU motherboard. When the fault detection circuit (subsequent circuits for voltage and current detection, temperature detection circuit) itself is damaged, it is a bit like “falsely reporting military intelligence” and deliberately making trouble. The main circuit is obviously good, but it reports an “output short circuit” fault or an output phase failure fault. The fan is obviously good, but it reports an overheating fault, etc., which prevents the inverter from being put into normal operation. The fault of the control terminal is mostly caused by the user mistakenly connecting to a high voltage, which burns the terminal power supply 24V, the terminal input circuit is open-circuited and damaged, and the input side circuit of the photocoupler is damaged.

The damage rate of the CPU chip itself is less than 2%. Due to the technical blockade involved, the internal program is not easy to crack. General maintenance personnel do not have the relevant conditions to repair the chip. They can only purchase original manufacturer parts or replace the CPU motherboard, the so-called “board-level repair”. However, for partial damage to the CPU chip, workarounds can be used to try to repair it.

2. Principle analysis and maintenance of the basic circuit of CPU:

Figure 1. One of the CPU mainboard circuits of INVT inverter G9/P9: Basic circuit of CPU

The inverter CPU motherboard circuit, which is the basic circuit for CPU operation, is composed of power supply, crystal oscillator circuit, reset circuit, external memory circuit and operation panel display circuit. The reset circuit is composed of special three-terminal reset components IMP809M and R188. It provides a low-level pulse to the 48th pin of the CPU at the moment of power-on, just like shouting the slogan “Everyone take your place”, realizing system reset and starting the program to run. The 3rd, 4th, 6th and 8th pins are connected to the U2 (93C66) memory. The user control program has been stored inside when leaving the factory. During the debugging and use process, the user needs to modify certain parameters at any time to meet the control requirements. The modified parameter values are stored by U2. The four pins connecting the CPU and the memory are all connected to +5V by pull-up resistors.

The general model of the inverter, the operation display panel, has been used as an independent device to communicate with the CPU. It accepts user instructions and transmits relevant monitoring data. The operation display panel contains CPU, decoding driver, LED display and other circuits, and can perform two-way data transmission with the CPU. Between the operation display panel and the CPU, the RS442/RS485 transceiver realizes communication transfer. The user operation signal is input from the A and B differential input terminals and sent to the CPU from the R receiver output terminal; the data signal output by the CPU enters from the D transmitter input terminal and enters the operation display panel from the Y and Z driver output terminals.

In order to adapt to the new control requirements, the control terminal of the inverter is also equipped with an RS485 communication port. In the figure, U6 (15176B) is an RS485 transceiver. D is the driver input terminal, connected to the CPU’s TXD1 serial port sending pin; R is the receiver output terminal, connected to the CPU’s RXD1 serial port receiving pin; A and B are the receiver input and driver output terminals; DE and DR are the driver and receiver enable signal terminals. The working status of the driver and receiver is controlled by the level signals of these two pins.

CPU basic circuit inspection and maintenance:

The failure rate of the CPU (single-chip microcomputer) itself is extremely low. Except for abnormal situations such as damage caused by lightning strikes introduced by the inverter, electrical failures are rare. The CPU is damaged because it contains running programs. For the sake of technical confidentiality, the manufacturer has taken some confidentiality measures to the greatest extent possible. It is difficult to decrypt the program and re-copy the chip. General maintenance personnel do not have such technical means. Does this also involve the issue of intellectual property rights? Therefore, after damage, it is necessary to purchase a chip with the program copied from the manufacturer, or replace it from a circuit board of the same model, or simply replace it with a CPU motherboard.

The inspection of the CPU basic circuit mainly includes the inspection of its three working elements and other working conditions, and fault repair.

The failure of the CPU basic circuit (three-element circuit) is typically characterized by: after power-on and when the power supply is normal, the operation panel has no display, or displays a fixed character, the inverter has no initialization process, and all operations on the operation display panel fail, similar to the phenomenon that a computer cannot be turned on and “freezes”.

The nature of the fault: A. At least one of the three elements of CPU work is missing, the CPU cannot complete the initialization operation, and the program is “stuck”; B. The CPU detects the existence of a dangerous fault signal during the self-test process and is in a fault lock state. All operations are rejected. This is a “CPU motherboard pseudo-fault” phenomenon. After checking and eliminating the cause of the fault, the CPU “strike” phenomenon will disappear immediately; C. The CPU chip is damaged due to lightning strike or abnormal power supply.

Note: If the program is “stuck”, be sure to eliminate the “CPU mainboard pseudo-fault” first, and then inspect the three elements of the CPU and other circuits. Focus on inspecting the OC fault alarm circuit, see the relevant content of Chapters 4 and 5 for details.

To determine whether the CPU is working or the three-element circuits are normal, you can first make a rough judgment:

(1).When the inverter is powered on, listen carefully to see if there is a “click” sound from the charging relay or contactor. If there is, it means that the three-element circuits are normal and the CPU is working normally. The inverter is in a fault lock state;

(2)Observe the operation display panel. Generally, there is a “power-on character” that flashes and finally stabilizes to a certain character. This process indicates that the CPU has also entered the working state.

(3)If you know the power-on self-test process of the inverter and the potential status of each pin, you can detect the voltage changes and level status of the relevant pins to determine whether the CPU is in operation. Use the key signal input of the operation display panel and the voltage changes of the key points of the detection circuit to determine whether the CPU is in working state. If you press the reset button on the panel, the inverter status signal output relay may make a “click” opening and breaking sound, and at the same time, the reset signal input pin of the drive circuit has a corresponding level change. This means that the CPU can accept the reset signal input and can output the fault reset signal to the drive circuit. This means that the CPU is working normally.

(4)If it is determined that the CPU is not operating normally, the basic working circuit of the CPU can be checked.

Fault inspection of the three-element circuit:

A、 Check the +5V power supply circuit. Check the CPU’s VDD, VSS, Vcc, GND and other power pins to confirm that the power supply is normal. The +5V power supply circuit is often connected to a filter capacitor with a large capacity of thousands of microfarads. When its capacity drops seriously, the CPU program will run disorderly and easily enter a program “dead loop”;

B、Check the reset circuit. The reset circuit provides a pulse voltage for the reset pin of the CPU during the power-on period. The duration of the pulse voltage is μs . Therefore, if a low pulse is required for reset, the static voltage of the CPU reset pin should be +5V. If a high level pulse is required for reset, the static voltage of the CPU reset pin should be 0V low level. Detection methods for the reset circuit:

a. According to the CPU reset pin’s requirement for high or low pulse voltage, measure whether its static potential is normal. If the static voltage is abnormal, check the CPU external reset circuit. You can disconnect the CPU pin to determine whether the abnormal reset pin voltage is a reset circuit failure or the CPU reset pin’s internal circuit is damaged.

b. If the static voltage is normal, you can use the artificial forced reset method to determine whether the CPU can work normally. The method is: if the static voltage of the CPU reset pin is +5V, use a metal wire to quickly short the reset pin and the power supply ground to artificially form a low-level signal input; if the static voltage of the reset pin is 0V, use a wire to quickly short the reset pin and the power supply +5V to artificially form a high-level signal input.

c. After forced reset, if the CPU can work normally, as shown by changes in the content of the operation display panel and the ability to modify parameters, it indicates that the external reset circuit is faulty and the damaged components must be replaced. For dedicated three-wire reset components, if there are no original components to replace, the RC component circuit can be connected for emergency repair;

d. If forced reset is invalid, the crystal oscillator circuit should be further checked.

3. Check the crystal oscillator circuit. The crystal oscillator circuit has few external components, usually only two capacitors and a crystal oscillator. Common circuit faults include the following:

a. Because the crystal oscillator contains quartz crystal, it is easy to break and fail after severe vibration;

b. If the crystal oscillator or capacitor leaks electricity, the signal transmission loss will increase, causing the oscillation to stop;

c. The internal oscillation circuit of the CPU is damaged and the CPU needs to be replaced.

Measurement method: a. The oscillation pulse is a rectangular square wave, and its pin voltage is about the middle value of 0V and +5V. The voltage values of the two pins are slightly different, about 0.3V. Among them, the X2 pin is 2V, and the X1 pin is 2.3V. Please use the voltage range of the digital multimeter when measuring. If you use a pointer meter, due to the low internal resistance, it may cause oscillation to stop, making the measurement result inaccurate; b. If the crystal oscillator leaks slightly or the performance deteriorates, when the crystal oscillator pin is lightly ironed with an electric soldering iron, the CPU motherboard resumes normal operation. It may be that the crystal oscillator is inefficient and the crystal oscillator should be replaced; c. If the crystal oscillator is suspected to be bad, it is best to replace it with a good crystal oscillator for testing. When removing the crystal oscillator for inspection, you can shake the crystal oscillator and carefully observe whether there is a slight clattering sound inside it. If there is, it means that the crystal oscillator is damaged by vibration. Measure the resistance value of the two pins, which should be infinite. If there is a resistance value, it means leakage. If there is a capacitance meter to measure the two pins, a good crystal oscillator has a PF-level capacitance, and its capacitance value decreases with the increase of the nominal frequency. e. There is another rare situation of defective crystal oscillator. Due to structural deformation or mechanical aging, the circuit oscillation frequency is lower than the nominal frequency value, and the frequency of CPU clock pulse is reduced. First, the system operation slows down. Second, due to the change of time reference value, the CPU sampling of input current and voltage signals will have errors, and the display values of running current and output frequency will also have corresponding deviations. In severe cases, the CPU may stop by mistake. The occurrence of this fault is manifested as a difficult fault.

Check the fault of CPU external memory. The inverter can be operated and the parameters can be modified, but after power failure, the modified parameter value cannot be stored, indicating that the machine has an external memory fault. Check the power supply of CPU external memory and the status of the connection line with CPU. Because the “pulse stream signal” is transmitted between CPU and external memory, it is difficult to judge whether it works well or not by the voltage of its pins. You can remove a good memory from the same model circuit board and replace it for testing. Note: If a new blank memory chip is used, the machine will not work. The user control parameters are already stored in the memory when it leaves the factory. If conditions permit, the original storage content can be copied to the new chip. Or purchase the memory chip from the manufacturer and replace it.

Inspection and maintenance of the operation display panel. 1. The buttons and speed regulating potentiometers on the operation display panel are wearing parts. Due to dust and humidity at the work site, they may cause poor contact, unstable output frequency or failure to write parameters. They can be replaced and repaired. 2. The LED display strokes are incomplete. Vibration causes internal drive circuit pins to be poorly soldered, copper foil strips to break, etc., which can be repaired by welding. 3. The power supply is normal, but there is no display, or a fixed character is displayed. You can replace the operation panel with the same model for testing. If the operation display panel is faulty, you can purchase a complete replacement from the manufacturer. 4. If replacing the operation display panel is invalid, check the data communication module between the CPU and the operation display panel – RS442/RS485 transceiver and other circuits.

[ Failure Example 1 ] :

    A 7.5kW INVT inverter could not hear the sound of the charging relay closing when powered on, and all control operations failed. The voltage of the CPU reset control pin 48 was measured to be 2.3V, which should be 5V under normal circumstances. It was determined that the three-wire reset element IMP809M was defective. After replacement, the fault was eliminated.

[ Failure Example 2 ] :

A Fuji 5000G9S 11kW inverter had a fixed character displayed on the operation panel and could not be operated. The “program stuck” phenomenon occurred and was determined to be a CPU mainboard failure. The static voltage of the CPU reset control pin was measured after powering on and was normal. The manual forced reset method was ineffective. The fault disappeared when the crystal oscillator soldering pin was heated with a soldering iron. After replacing a high-quality crystal oscillator component and two ceramic capacitors, the fault was eliminated.

[ Failure Example 3 ] :

A Fuji 5000G9S 47kW inverter, the operation panel displays a fixed character, cannot be operated, and the “program stuck” phenomenon occurs, which is judged to be a CPU mainboard failure. After starting the machine for inspection, power on, and measuring the CPU power supply, it is normal, but the CPU chip is hot and has an abnormal temperature rise. It is judged that the CPU chip itself has a short circuit fault. A CPU chip of the same model is removed from an old circuit and replaced to eliminate the fault.

[ Failure Example 4 ] :

An INVT INVT-G9-004T4 low-power machine was found to have a damaged inverter module. The CPU mainboard and power driver board were powered on first, and the inverter module was purchased after the driver board failure was repaired. After powering on, the operation display panel showed H:00, and all the buttons on the panel failed to operate. It was determined to be a failure of the CPU basic circuit. The three working elements of the CPU were checked first, and no abnormalities were found; the other peripheral circuits of the CPU were checked, and no abnormalities were found. For a while, I was at a loss and did not know where to start, and the maintenance work came to a deadlock.

Later, when checking the current detection circuit, the voltage of the 8th and 14th pins of the current signal input amplifier U12D was 0V, which was normal; the 14th pin of U13D was negative 8V, which was an overcurrent signal output error. But logically, the CPU should report OL or OC, SC faults, and the program should not stop running, right? Try to cut off the fault signal so that it cannot be input into the CPU, power on, and the operation panel can actually be operated!

The protection sequence of INVT G9/P9 inverter is roughly as follows: when the power inverter output part is detected to be faulty at power-on, even if the start/stop signal is not received, the SC–output short circuit fault code will still be displayed, and all operations will be rejected; when the overcurrent signal from the current detection circuit is detected at power-on, H.00 will be displayed, and all operations will still be rejected at this time; when the power-on detection has a thermal alarm signal, most other operations can be performed, but the start operation is rejected, perhaps the CPU thinks that the output module is still in a high temperature rise state, and it will wait for it to return to normal temperature before allowing it to start running. For module short circuit faults and overcurrent faults, in order to ensure safe operation, all operations are simply rejected! However, this protective measure is often mistaken for the program entering an infinite loop, or a CPU peripheral circuit failure, such as abnormal reset circuits and crystal oscillator circuits.

After repairing the current detection circuit and checking that there was no abnormality in the drive circuit, the fault was eliminated after replacing the power module.

Posted on Leave a comment

Analysis of 3 types of VFD motherboard wiring terminal signal source drawings

If you frequently repair a certain brand or several brands of inverters, you should have the terminal diagram of the connection cable between the CPU motherboard and the power/driver board. With it, the maintenance efficiency will be greatly improved. I spent a lot of effort to survey and map the terminal diagrams of the CPU motherboards of three inverters. I dare not keep it secret, so I share it here with you.

The above figure shows the function/destination (50 lines) of the TECO 7300PA inverter mainboard wiring terminal 7CN. The inverter of this model has excellent versatility in CPU mainboards, ranging from 22kW to 300kW, and can be interchanged. You only need to adjust the parameter “inverter capacity”. That is to say, this brand of inverter, due to different power levels, except for the power supply/driver board, actually uses the same CPU mainboard, so this terminal diagram can be used for “all sizes” during maintenance.

Figure 1.Function/direction diagram of TECO 7300PA inverter mainboard wiring terminal 7CN

Using the terminal diagram:

1. Check the input and output control signals. Most of them are switch signals, and the high and low level values are very obvious. For example, the detection signal terminals 2 and 4 of the charging contactor and temperature sensor have a terminal voltage of 24V when normal and 0V when abnormal. The static and dynamic (start/stop) voltage values of the six-way pulse signal terminals are obvious; although the output current detection signal is an analog quantity, it should be 0V when static and unloaded. Generally, it is about 2V when fully loaded.

2. You can “play tricks” on the terminals. For example, if the module overheats, you can try to short-circuit terminal 4 and pin 28. If the fault disappears, it means that the external temperature relay (sensor) at terminal 2 is faulty. If the fault still exists, it means that the fault is in the subsequent temperature signal processing circuit.

If you connect a potentiometer between terminals 10 and 29 and connect its center arm to the output current detection terminal (terminal 7 or 9), you can simulate a load test to check whether the subsequent current detection circuit is normal.

If an analog signal only deviates from the normal value (and still works), and falsely reports an “overvoltage” fault under normal power supply, you can use parallel and series resistance methods at terminals 23 to make its voltage value fall back to the normal detection value for emergency repair.

[ Failure Example 1 ] :

    A 300kW7300PA inverter has an output frequency display on the operation display panel, but there is no three-phase voltage output on the U, V, and W terminals. After disconnecting the power supply of the inverter circuit, the six pulse signals of the 11, 13, 15, 17, 19, and 21 pins of the 7CN terminal were measured and all were normal. It was determined that the fault was in the pulse pre-stage signal circuit of the power supply/driver board. From these six terminals, it was quickly found that U12 (MC14069) was defective. After replacement, the fault was eliminated.

[ Failure Example 2 ] :

    A 300kW7300PA inverter reported a “DC circuit undervoltage” fault after power-on and could not start running. The DC circuit voltage detection signal of terminal 23 of the wiring terminal 7CN was normal. After power-on, the measurement of terminal 2 was always low level, indicating that the auxiliary contact of the charging contactor was not closed. The CPU detected that the charging contactor was not closed, so it reported an undervoltage fault.

Try to short-circuit terminal 2 and terminal 28, and it runs normally.

Check from terminal 2 to the power supply/driver board and find out that the normally open contact of relay KA1 is connected in series in the 2-terminal circuit. The contact of KA1 is in poor contact. Replace KA1 and the fault is eliminated.

[ Failure Example 3 ] :

A 7300PA37kW inverter reported an OC fault as soon as it was powered on. The power supply of the current detection circuit was detected from the terminals. The -15V of terminals 40, 41, and 42 was 0V. Due to the abnormal power supply, the output of the current detection circuit was offset and an OC fault was reported. The -15V rectifier diode of the switching power supply was checked and found to be open. The fault was eliminated after replacement.

In the above three faults, with the guidance of the 7CN terminal diagram, the faults were found quickly and accurately in a very short time and the faults were eliminated efficiently.

Figure 2.Alpha ALPHA2000 medium and small power inverter CNM motherboard wiring terminal function/direction diagram

The above picture is the Alpha inverter CPU motherboard CNM wiring terminal diagram, a total of 24 lines. Although the CPU motherboard of this model cannot be replaced – the overload protection and other parameters are fixed and the relevant parameter values cannot be modified; the CPU motherboard circuits are also different. I have seen two motherboard circuits, but the CNM terminals are the same. Therefore, the CNM terminal function/destination diagram is still very valuable as a “guide” for maintenance.

[ Failure Example 1 ] :

An Alpha 2000 15kW inverter tripped an undervoltage fault as soon as it was started, and no charging contactor closure sound was heard when it was powered on. The CNM terminal 1 was tested and was always at a high level of 24V, indicating that the charging relay control circuit was faulty. From terminal 1 to the CPU mainboard, it was determined that the circuit inside the CPU control pin was damaged.

Emergency repair: Short-circuit terminal 1 and terminal 7. After the switching power supply starts to oscillate, force the charging relay to be energized and closed to eliminate the fault.

[ Failure Example 2 ] :

An Alpha 2000 18.5kW inverter, with a load rate of less than 50%, but the on-site power supply fluctuates greatly, sometimes as low as 320V. The inverter tripped an undervoltage fault, and the dealer and the user required measures to make the inverter run. Cut the cable of CNM terminal 8, connect a 4.7kΩ semi-variable resistor between terminals 25 and 7 , connect the center arm to terminal 8, and adjust it to a fixed voltage of 3V.

The inverter no longer trips the undervoltage fault and operates normally. (This emergency measure must be used with caution in specific applications!)

Figure 3.Function/direction diagram of CN1 terminal on INVT G9/P9 medium power inverter motherboard

There is a trick to speed up the inspection, which is to make a diagram of the motherboard wiring terminals. Clearly mark the terminal serial number and the source and destination of the terminal signal. It would be even better if the dynamic and static voltage values of each terminal could be marked. Fortunately, there are many switching signals, which are easier to detect and judge. Analog signals also have obvious differences in dynamic and static, which are easier to detect.

The figure above is the function/destination diagram of the CN1 terminal. For terminals 4, 7, 8, and 9, the terminals are set by the manufacturer. Except for replacing the CPU motherboard, you can check the short-circuited state of the terminals. For maintenance, it is useless, so don’t worry about it. 24V, +15, -15V, +15V, and +5V power supplies are the 5 power supplies commonly used by the CPU motherboard. Some inverters have two 24V power supplies, one for the control relay coil and the other for the control sub-power supply. The power supply introduction in the terminal occupies most of the terminals, six inverter pulses, and some have one DC braking pulse, which occupies part of the terminals. The others are various input/output, switch quantity/analog quantity signal terminals. What we need to pay attention to and frequently test is this third type of terminal. When checking a certain circuit, you can also artificially change the voltage state of this type of terminal to see if the corresponding circuit reacts. By observing or measuring the normal or abnormal reaction of the corresponding circuit, you can clearly judge whether the circuit is good or bad.

[ Failure Example 1 ] :

An INVT G9/P9 5.5kW inverter has an unbalanced output three-phase voltage. After disconnecting the inverter power supply, the start signal is input and the six pulse signal terminals 19, 21, 23, 25, 27 and 29 of CN1 are detected. It is found that the voltage at pin 21 is fixed and there is no change in dynamic or static state. It is judged that the fault is in the pulse pre-stage circuit or the PWM pulse output pin of the CPU.

Check the inverter pulse pre-stage circuit U4 (LS07), the six-way inverter pulse at the input end is normal, and there is no signal voltage output at the output pin 8. Replace U4 and the fault is eliminated.

[ Failure Example 2 ] :

An INVT G9/P9 5.5kW inverter reported an undervoltage fault during operation. The CN1 terminal 39 pin was detected to be low level, indicating that the CPU has output a charging relay closing signal. The charging relay was checked and found to have been replaced. The coil solder joints were poorly soldered. After re-welding, the fault was eliminated.