Posted on Leave a comment

Fuji Frequency Converter FRENIC-Multi (FRN E1S) Series User Manual Guide

I. Introduction to the Operation Panel Functionality and Key Parameter Settings

1.1 Introduction to the Operation Panel Functionality

Fuji frequency converter E1S series operation panel function diagram

The Fuji Frequency Converter FRENIC-Multi (FRN E1S) series features an intuitive operation panel that allows users to easily monitor and control the operation of the frequency converter. The operation panel provides various functions such as setting operating frequencies, monitoring operating status, and configuring parameters.

Key Features of the Operation Panel:

  • LED Display: Displays various operating parameters such as output frequency, output current, and operating status.
  • UP/DOWN Keys: Used to adjust the set frequency.
  • RUN/STOP Keys: Used to start and stop the motor.
  • Mode Selection Keys: Allows switching between operation modes such as run mode, program mode, and alarm mode.

1.2 Setting the Electronic Thermal Relay Function

The electronic thermal relay function protects the motor from overheating by monitoring the output current of the frequency converter. To configure this function, the following parameters need to be set:

  • F10 (Thermal Relay Characteristic Selection): Selects the cooling system characteristic of the motor. Options include self-cooled motors with built-in fans and externally cooled motors.
  • F11 (Thermal Relay Action Value): Sets the current level at which the thermal relay will trip. This value should typically be set to around 100-110% of the motor’s rated current.
  • F12 (Thermal Time Constant): Sets the time it takes for the thermal relay to trip after the current exceeds the action value. This value depends on the motor’s thermal properties and the ambient operating conditions.

1.3 Configuring the Instantaneous Power Failure Restart Function

The instantaneous power failure restart function allows the frequency converter to automatically restart the motor after a temporary power outage. To enable and configure this function, the following parameters need to be set:

  • F14 (Instantaneous Power Failure Restart Selection): Enables or disables the instantaneous power failure restart function. Options include no restart (instant trip), no restart with reset on power restoration, restart at the frequency at the time of power failure (for general loads), and restart at the start frequency (for low-inertia loads).
  • H13 (Restart Waiting Time): Sets the time to wait after detecting a power failure before attempting to restart the motor. This helps to ensure that the residual voltage in the motor windings has decayed sufficiently to prevent inrush currents.
  • H14 (Frequency Ramp-Down Rate): Sets the rate at which the output frequency is reduced during restart to synchronize with the motor’s rotational speed and prevent excessive currents.
  • H16 (Instantaneous Power Failure Allowable Time): Sets the maximum time that can elapse after a power failure before the restart function is disabled.
Fuji frequency converter E1S standard wiring diagram

1.4 Selecting and Configuring the Terminal FM Function

The terminal FM provides an analog output signal that can be used to monitor various operating parameters of the frequency converter. To select and configure this function, the following steps are required:

  • F29 (Terminal FM Action Selection): Selects whether the terminal FM outputs a voltage signal (0-10V) or a pulse signal.
  • F30 (Output Gain): Adjusts the gain of the analog output signal. This allows scaling the output signal to match the input range of the monitoring equipment.
  • F31 (Function Selection): Selects the parameter to be monitored and output through the terminal FM. Options include output frequency, output current, output voltage, motor torque, load rate, and more.
  • F33 (Pulse Rate): When pulse output is selected, this parameter sets the pulse rate at 100% output.

By carefully configuring these parameters, users can fully utilize the advanced functionality of the Fuji FRENIC-Multi (FRN E1S) series frequency converter to optimize motor control and protect against potential faults.

Posted on Leave a comment

Panasonic Inverter VF200 Series User Manual Guide

Introduction

The Panasonic Inverter VF200 series is a powerful and flexible variable frequency drive (VFD) equipment widely used in the industrial automation field. This document aims to provide users with a detailed user guide to help them better understand and efficiently operate the VF200 series inverter.


Function diagram of Panasonic VF200 series inverter operation panel

1. Operation Panel Function Introduction, Parameter Upload, and Download

1.1 Operation Panel Function Introduction

The operation panel of the Panasonic Inverter VF200 series serves as the primary interface for user interaction. It features various functions and indicators to facilitate ease of use and monitoring.

  • Display Section: Displays output frequency, current, linear speed, set frequency, communication station number, abnormality content, various mode displays, and function setting data.
  • FWD/REV Indicators: Green indicators that show the forward/reverse operation status.
  • Panel Potentiometer: Used to set the operating frequency via the operation panel.
  • Alarm (ALM) Indicator: Red indicator that lights up in case of abnormalities or alarms.
  • RUN/STOP Buttons: Buttons to start/stop the inverter.
  • MODE Button: Toggles between various modes such as operation status display, frequency setting, rotation direction setting, control status monitoring, custom settings, function settings, and built-in memory settings.
  • SET Button: Used to switch modes, display data, and store settings.
  • ▲(UP) and ▼(DOWN) Buttons: Used to change data, output frequency, and set the rotation direction when operating via the panel.
VF200 picture

1.2 Uploading and Downloading Parameters

  • Uploading Parameters (CPY1): To upload the inverter’s functional parameters to the operation panel’s built-in memory, follow these steps:
    1. Stop the inverter.
    2. Press the MODE button four times to enter the function setting mode.
    3. Press the SET button.
    4. Use the ▲/▼ buttons to select “CPY1”.
    5. Press the SET button and set the value to “UPL”.
    6. Press the SET button again to start the upload process.
  • Downloading Parameters (CPY2): To download the parameters from the operation panel’s built-in memory to the inverter, follow these steps:
    1. Stop the inverter.
    2. Press the MODE button four times to enter the function setting mode.
    3. Press the SET button.
    4. Use the ▲/▼ buttons to select “CPY2”.
    5. Press the SET button and set the value to “dOL”.
    6. Press the SET button again to start the download process.

1.3 Setting and Eliminating Passwords

  • Setting a Password:
    1. Stop the inverter.
    2. Press the MODE button four times to enter the function setting mode.
    3. Use the ▲/▼ buttons to navigate to parameter P150.
    4. Press the SET button to display the current password.
    5. Use the ▲/▼ buttons to set a new password (range: 0000-9999).
    6. Press the SET button to save the password.
  • Eliminating a Password:
    1. Stop the inverter.
    2. Press the MODE button four times to enter the function setting mode.
    3. Use the ▲/▼ buttons to navigate to parameter P150.
    4. Press the SET button to display the current password.
    5. Set the password to “0000” using the ▲/▼ buttons.
    6. Press the SET button to eliminate the password.

1.4 Restoring Parameter Initialization

To restore the inverter’s parameters to their factory default settings, follow these steps:

  1. Stop the inverter.
  2. Press the MODE button four times to enter the function setting mode.
  3. Use the ▲/▼ buttons to navigate to parameter P151.
  4. Press the SET button to display the current setting.
  5. Set the value to “3” using the ▲/▼ buttons.
  6. Press the SET button to restore the parameters to their factory defaults.
Panasonic VF200 inverter control terminal wiring diagram

2. External Terminal Control for Forward/Reverse Rotation and PWM Frequency Control

2.1 Forward/Reverse Rotation Control via External Terminals

To achieve forward/reverse rotation control via external terminals, connect the relevant control signals to the designated terminals on the inverter.

  • Terminal Configuration:
    • SW1-SW5 (Control Circuit Terminals 4-8): These terminals can be configured to control forward/reverse rotation, start/stop, and other functions.
    • Configuration Steps:
      1. Stop the inverter.
      2. Enter the function setting mode by pressing the MODE button four times.
      3. Navigate to parameters P036-P040 using the ▲/▼ buttons.
      4. Set the desired function (e.g., forward/reverse, start/stop) to the corresponding terminal using the ▲/▼ buttons.
      5. Press the SET button to save the settings.

2.2 PWM (Pulse) Frequency Control

To control the inverter’s output frequency via PWM signals, follow these steps:

  • Terminal Configuration:
    • Terminal 7 (SW4) and Terminal 8: These terminals are used to receive PWM frequency control signals.
    • Configuration Steps:
      1. Stop the inverter.
      2. Enter the function setting mode by pressing the MODE button four times.
      3. Navigate to parameter P087 using the ▲/▼ buttons.
      4. Set the value to “1” to enable PWM frequency control.
      5. Press the SET button to save the setting.
      6. Connect the PWM signal source to terminals 7 and 8 according to the wiring diagram provided in the manual.
  • Additional Settings:
    • P088: Sets the number of PWM cycles to average for frequency calculation.
    • P089: Sets the PWM signal period.

By following this guide, users can effectively utilize the Panasonic Inverter VF200 series, leveraging its advanced features and flexible control options to meet various industrial automation needs.

Posted on Leave a comment

User Manual and Operation Guide for EACON EC5000 Series Frequency Converter

I. Introduction to Operation Panel Functions, Factory Reset, and Password Settings/Removal

The operation panel of the EACON EC5000 series frequency converter from Yikong integrates numerous functions, enabling users to easily configure and monitor the converter. The operation panel mainly comprises an LED display, a potentiometer, and various functional buttons. The LED display clearly shows the current operating status, set parameters, and alarm information, allowing users to monitor and adjust in real-time.

EC5000 physical image

Factory Reset:

  1. Preparation for Parameter Setting: Set the parameters in front of the frequency converter and switch the control mode to the factory reset state.
  2. Select Factory Reset: The display panel on the operation panel will show FXX. Use the up and down buttons to select 1 or 2 and press Enter. The screen will then display F00; press Enter again, and the screen will show F01.
  3. Confirm Reset: In the F01 state, press Enter. The screen will show F00, which is the final step of the factory reset.
  4. Complete Reset: After completing the above steps, press and hold the up and down buttons simultaneously to complete the factory reset.
  5. Reconfigure Parameters: After the factory reset, reconfigure the parameters according to actual requirements and save them.
EC5000 Terminal Block Function Diagram

Password Setting and Removal:

To ensure user and device security, the EACON EC5000 series provides a password setting function.

Password Setting:

  1. Access User Management Interface: On the home page, click the “User Management” menu and enter the initial account password “admin” to access.
  2. Modify Password: Click the “Modify Password” button, enter the original account password “admin”, then enter a new account password and confirm it, and click “Modify”.

Password Removal:

If the user forgets the password, they can reset the device to its factory settings using the reset button on the device. After the factory reset, the password will revert to “admin”. To prevent password theft, it is recommended to regularly change the password and set a relatively complex one.

II. Wiring and Parameter Setting for External Terminal Reversal and External Potentiometer Speed Regulation

EACON Inverter EC5000 Series Standard Wiring Diagram

External Terminal Reversal:

The EACON EC5000 series supports forward and reverse control via external terminals. Specific wiring and parameter settings are as follows:

  1. Wiring:
    • For reverse operation, connect S3, S2, S1, and SC. When the forward/reverse switch stop command (open) is activated, the frequency converter will stop operating.
    • For forward operation, connect the corresponding external switches and terminals as required.
  2. Parameter Setting:
    • No special settings are required; just ensure correct wiring of the external terminals.

External Potentiometer Speed Regulation:

Users can conveniently adjust the output frequency of the frequency converter using an external potentiometer, thereby achieving precise control of motor speed.

  1. Wiring:
    • Connect the output terminal of the external potentiometer to the analog input terminal of the frequency converter (such as the 0-10V or 4-20mA input terminal).
  2. Parameter Setting:
    • Enter the parameter setting interface of the frequency converter and select the corresponding analog input channel (such as FV or FI).
    • Set the corresponding parameters (such as B14 and B15) according to the type of external potentiometer (voltage or current).

III. Fault Code Analysis and Solutions

The EACON EC5000 series features comprehensive fault detection and diagnostic functions, displaying fault codes in real-time to help users quickly locate and resolve faults.

Common Fault Codes and Solutions:

  1. ERR: Indicates a control circuit fault. Possible causes include failure to establish transmission between the digital operator and the drive. Solutions include reinserting the digital operator and connectors, checking the wiring of the control circuit, or replacing the control plug-in board.
  2. Overvoltage, Overcurrent, Overload, etc.: These faults are usually related to the motor’s operating status or external load. Solutions include checking the motor’s operating status, load conditions, and ensuring the frequency converter’s output current and voltage are within specified ranges.
  3. Input/Output Phase Loss Fault: May be caused by poor power or motor wiring. Solutions include checking the power and motor wiring for firmness and reliability.
  4. Overheat Fault: May be caused by overheating of the frequency converter or motor. Solutions include checking if the cooling fan is operating normally, if the ambient temperature is too high, and if additional cooling measures are needed.

By following this guide, users can more effectively utilize the EACON EC5000 series frequency converter, achieving precise motor control and efficient operation. Prompt fault troubleshooting and resolution will improve equipment reliability and stability, extending its service life.