Posted on Leave a comment

EASYDRIVE Inverter M200 User Manual Operation Guide

I. Operation Panel Functions and Basic Settings

1. Operation Panel Function Introduction
M200 frequency converter displays normally

The EASYDRIVE M200 inverter’s operation panel features a straightforward design, incorporating keys such as RUN, M-FUNC (multifunctional), STOP/RESET, PRG (program switch), ENTER, ▲/▼ (data modification), and ▼▼ (data bit switch). The LED display can show set frequency, output voltage, output current, and other parameters.

2. Restoring Factory Defaults

To restore the EASYDRIVE M200 inverter to its factory settings, you can follow these steps via the operation panel:

  • Enter the parameter setting interface (PRG key).
  • Locate the F0-01 parameter (Parameter Initialization).
  • Set F0-01 to 1 and press ENTER to confirm.
  • The inverter will automatically restart and revert to factory settings.
3. Password Setting and Removal

To protect the inverter settings, a user password can be set. The specific operations are as follows:

  • Enter the parameter setting interface.
  • Locate the F0-00 parameter (User Password).
  • Set a non-zero digit as the password and press ENTER to confirm.
  • To remove the password, set F0-00 to 0000.
4. Torque Boost, Cutoff Frequency, and Slip Frequency Compensation Settings
  • Torque Boost Setting:
    • Enter the F1 parameter group and find F1-13 (Torque Boost).
    • Set the torque boost percentage (0.0% to 30.0%) according to the load condition.
  • Cutoff Frequency Setting:
    • Locate F1-14 (Torque Boost Cutoff Frequency).
    • Set the cutoff frequency percentage (0.0% to 50.0%).
  • Slip Frequency Compensation Setting:
    • Enter the F1 parameter group and find F1-15 (V/F Slip Frequency Compensation).
    • Set the slip frequency compensation percentage (0.0% to 200.0%).
E-15

II. Three-Wire Operation Control and External Potentiometer Settings

1. Three-Wire Operation Control

Three-wire operation control allows for forward, reverse, and stop control of the inverter through three terminals. The setup steps are as follows:

  • Enter the F6 parameter group and find F6-09 (FWD/REV Terminal Control Mode).
  • Set F6-09 to 2 or 3 to select the three-wire control mode.
  • When wiring, connect the forward control terminal (e.g., DI1), reverse control terminal (e.g., DI2), and stop control terminal (e.g., DI3) to the corresponding function terminals, respectively.
2. External Potentiometer for Forward/Reverse and Speed Adjustment

An external potentiometer can be used for frequency setting on the inverter, enabling forward/reverse control and speed adjustment. The specific settings are as follows:

  • Forward/Reverse Setting:
    • Enter the F1 parameter group and set F1-02 (Main Frequency Source A Selection) to AI1 or AI2.
    • When wiring, connect the center tap of the external potentiometer to the common terminal of the inverter (e.g., GND), and the other ends to AI1 or AI2 terminals, respectively.
    • Adjust the potentiometer resistance to achieve forward or reverse rotation.
  • Speed Adjustment Setting:
    • Enter the F5 parameter group to set the input range of AI1 or AI2 (F5-00 to F5-03 or F5-05 to F5-08).
    • Wiring is the same as above; adjusting the potentiometer resistance will change the output frequency.

III. Fault Diagnosis and Handling

1. E-015 Fault (External Device Fault)

When the inverter displays the E-015 fault code, it indicates that the external device fault input terminal is closed. The solution is as follows:

  • Check if the external device is functioning normally.
  • Disconnect the external device fault input terminal and clear the fault.
2. Other Common Faults and Solutions
  • E-01 Overcurrent During Acceleration:
    • Possible Causes: Too short acceleration time, excessive load inertia.
    • Solution: Extend the acceleration time, reduce the load inertia.
  • E-02 Overcurrent During Deceleration:
    • Possible Causes: Too short deceleration time, large inertial load.
    • Solution: Extend the deceleration time, reduce the load inertia.
  • E-07 Bus Undervoltage:
    • Possible Cause: Abnormal input voltage.
    • Solution: Check if the power supply voltage is normal.
  • E-16 RS485 Communication Fault:
    • Possible Causes: Improper baud rate setting, serial port communication error.
    • Solution: Set the baud rate appropriately, check the communication cable and ensure the upper computer is working normally.

IV. Conclusion

The EASYDRIVE Inverter M200 User Manual provides a comprehensive operation guide, covering operation panel function introduction, basic settings, terminal control, external potentiometer settings, fault diagnosis, and handling. By reasonably setting parameters and correctly wiring, users can easily achieve various functions of the inverter, ensuring stable equipment operation. Meanwhile, understanding common faults and solutions helps users quickly locate and troubleshoot issues, improving equipment efficiency and reliability.

Posted on Leave a comment

Analysis and Solutions for FAULT FB11 and FAULT FB14 in ABB’s ACS880 Series Frequency Converters

Introduction

In the field of industrial automation, ABB’s ACS880 series frequency converters are highly regarded for their high performance, reliability, and wide range of applications. However, like any equipment, they may encounter faults during operation. This article delves into the meanings, causes, and solutions of FAULT FB11 and FAULT FB14 in the ACS880 series through a specific maintenance case.

check connection

Specific Maintenance Case

A customer’s ABB ACS880 series frequency converter initially displayed the fault message “Drive is faulted, Please reset the fault first.” After pressing the reset button, the display changed to “Check Connection” fault. Upon inspection, it was found that the ZCU-12 mainboard had burned out. After replacing it with a new ZCU-12 mainboard, the operation panel showed the fault “Panel and Drive not Compatible.” After initializing the parameters, the “Fault FB11” appeared, indicating that the memory card was missing and the mainboard could not detect the ZMU-02 memory card.

Drive is faulted fault

Fault Analysis

  1. FAULT FB11FAULT FB11 signifies a software loading failure of the memory unit, typically caused by a missing or unrecognized memory card. In the ACS880 series, the memory card (such as ZMU-02) stores the converter’s parameters, programs, and data. If the memory card is missing, damaged, or the data is inconsistent, the converter cannot load the necessary operating programs and data properly, triggering the FAULT FB11 fault.
  2. FAULT FB14FAULT FB14 indicates the inability to load data from the memory card. This usually occurs when the memory card is damaged, the data is lost, or there is data inconsistency. Similar to FAULT FB11, FAULT FB14 is triggered by the converter’s failure to correctly read the data from the memory card.
panel and drive  not compatible fault

Solutions

  1. Check the Memory CardFirst, check if the ZMU-02 memory card is installed correctly and ensure its physical connection is good. A loose or poorly connected memory card may cause the converter to fail to recognize it.
  2. Re-initialize the Memory CardIf the memory card connection is normal but the problem persists, try using ABB’s specialized tools to re-initialize the memory card. This can usually restore the memory card to its factory settings and clear any data inconsistencies that may cause faults.
  3. Replace the Memory CardIf re-initializing the memory card does not solve the problem, it may be necessary to replace it with a new one. Various types of memory cards are available on the market, such as standard program N2000, textile program N5500, custom programming N8010, lifting program 7518, curling program N5000, lifting program N5050, etc. Choose the appropriate memory card for replacement based on the specific application and needs of the converter.
  4. Check the Mainboard and Connection CablesAfter replacing the memory card, also check if the mainboard and connection cables are normal. Ensure all connections are secure and reliable to avoid faults caused by poor connections.
  5. Contact Professional TechniciansIf the above methods cannot solve the problem, it is recommended to contact ABB’s professional technicians or authorized service centers for further inspection and repair.
fault FB11

Role of the Memory Card

In the ACS880 series frequency converters, the memory card plays a crucial role. It not only stores the converter’s parameters, programs, and data but also allows users to modify and update these data when needed. Furthermore, the memory card provides data backup and recovery functions, ensuring that the converter can quickly recover to its normal state in case of unexpected faults. Therefore, maintaining the good condition of the memory card and the integrity of the data is essential for the proper operation of the converter.

zmu-02

Conclusion

ZCU-12

Through this discussion, we have gained a deep understanding of the meanings, causes, and solutions of FAULT FB11 and FAULT FB14 in ABB’s ACS880 series frequency converters. In practical applications, when encountering such faults, one should first check the status and connection of the memory card and take corresponding solutions based on the specific situation. Regular maintenance and inspection of the converter and its related components are also important measures to prevent faults. We hope this article provides valuable reference and assistance for users in using and maintaining ACS880 series frequency converters.

Posted on Leave a comment

Does ABB’s ACS880 drive require ZMU-02 to be used?

The ABB ACS880 drive does not necessarily require the ZMU-02 storage card to operate. The ZMU-02 card is primarily used to provide additional storage space for saving specific configuration parameters, and it is often used in applications that require storing large amounts of programs or advanced functions (e.g., multi-drive networking, complex control strategies, etc.).

ZMU-02

Role of the ZMU-02 Storage Card:

  1. Storing Parameters and Programs: The ZMU-02 card can be used to store the drive’s parameter settings, control programs, or fault logs. In applications where frequent adjustments or multiple preset configurations are needed, the ZMU-02 card becomes useful.
  2. Program Upgrades and Backup: The ZMU-02 card can also serve as a tool for program upgrades or backing up data. If the drive needs firmware updates or parameter changes, the storage card can make the process more convenient.
ACS880 NZ2000

Is the ZMU-02 Card Required?

  1. Standard Models: For most standard applications or regular ACS880 drives, the ZMU-02 card is not required for basic operation. The drive itself can operate normally with manual parameter adjustments and control, without the need for additional storage.
  2. Specialized Models or Specific Requirements: If the ACS880 model is part of a more specialized application or requires more advanced functionality (e.g., storing large amounts of configuration data, multiple programs, or updates), the ZMU-02 card might be necessary. This is especially true in multi-drive setups or when managing configurations across multiple devices.
  3. Different Model Requirements: Some specific ACS880 models may indeed require the ZMU-02 card for operation, particularly in complex applications. It is best to consult the specific model’s documentation or application manual to determine whether the storage card is required.

Conclusion:

The ZMU-02 storage card is not mandatory for all ACS880 drives. Standard models typically do not require it, but in certain specialized or advanced applications, the card may be necessary. It’s advisable to check the specific model and application manual to confirm whether the storage card is needed.

Posted on Leave a comment

Schneider ATV310 Series Inverter User Manual Guide

I. Introduction to Operating Panel Functions and Password Settings

The Schneider ATV310 series of inverters come equipped with an intuitive operating panel that facilitates various settings and operations. The operating panel includes a display screen, multiple buttons, and indicator lights. The display screen shows current parameters and status, while the buttons are used for navigation and parameter setting.

ATV310 is not working when powered on

Password Setting and Unlocking

To ensure device security, the ATV310 inverter supports password locking. Users can restrict access to the inverter by setting a password.

  • Setting a Password: Enter the “Configuration Mode” (ConF), select the “999 HMI Password” parameter, enter the desired password (ranging from 2 to 9999) using the navigation keys, and press the confirm button to save.
  • Unlocking the Inverter: If the inverter is locked, enter the “Configuration Mode”, select the “999 HMI Password” parameter, enter the password, and press the confirm button to unlock. If the password is forgotten, contact Schneider Electric technical support.
ATV310 actual terminal wiring diagram

Accessing Full Menu Functions and Storing/Restoring Parameters

The ATV310 inverter offers a comprehensive range of parameter settings. Users can access the full menu via the “Configuration Mode” (ConF).

  • Accessing the Full Menu: In the “Configuration Mode”, use the navigation keys to select the “FULL” submenu to access the complete list of parameters.
  • Storing Parameters: After completing parameter settings, select “101 Store Customer Parameter Settings” and press the confirm button to save the current configuration.
  • Restoring Factory Defaults: To reset the inverter to its factory default settings, select “102 Factory/Restore Customer Parameter Settings” and then press the confirm button and select “64”.
ATV310 displays normally

II. Setting the External Terminal Operating Mode

The ATV310 inverter supports the external terminal control mode, allowing users to achieve forward, reverse, high-speed, and low-speed functions through the LI1, LI2, LI3, and LI4 logic input terminals.

Wiring and Parameter Settings

  1. Wiring:
    • Connect the LI1, LI2, LI3, and LI4 terminals to the corresponding outputs of the external controller.
    • Ensure all wiring is secure and compliant with safety regulations.
  2. Parameter Settings:
    • Enter the “Configuration Mode” (ConF) and select the “Control Menu” (400-).
    • Set the “Control Type” (201) to “3-Wire Control” (01).
    • Set the “Logic Input Type” (203) to “Positive Logic” (00) to ensure high-level activation.
    • Set the “Given Channel 1” (401) to “Remote Display” (01) to receive speed commands via the external controller.
    • Set the “Command Channel 1” (407) to “Terminal” (01) to receive control commands through the LI1-LI4 terminals.
    • In the “Input/Output Menu” (200-), assign functions to LI1, LI2, LI3, and LI4:
      • LI1: Forward (L1H)
      • LI2: Reverse (L2H)
      • LI3: High Speed (L3H)
      • LI4: Low Speed (L4H)
    • In the “Speed Limit Menu” (512-), set the specific frequency values for high speed (512.2) and low speed (512.0).

High and Low Speed Frequency Given

The high and low speed frequencies can be given via the analog or digital outputs of the external controller. If using an analog output, connect the AI1 terminal to the analog output of the external controller and set the AI1 type and range in the “Input/Output Menu” (200-). If using a digital output, directly control high and low speeds through the LI3 and LI4 terminals.

III. Fault Code Analysis and Troubleshooting

The ATV310 inverter features advanced fault diagnosis. When a fault occurs, the corresponding fault code will be displayed on the screen. Users can take appropriate measures based on the code.

Common Fault Codes and Solutions

  • F001 Precharge Fault: Possible causes include faulty charging relays or damaged charging resistors. The solution is to check connections, confirm the stability of the main power supply, and contact Schneider Electric technical support if necessary.
  • F010 Overcurrent Fault: May be caused by incorrect parameter settings, excessive load, or mechanical lockup. The solution is to check parameter settings, adjust motor/drive/load dimensions, inspect mechanical device status, and connect motor reactors.
  • F011 Inverter Overheat Fault: May be caused by excessive load, poor ventilation, or high ambient temperature. The solution is to check motor load, inverter ventilation, and ambient temperature, and wait for the inverter to cool down before restarting.
  • F013 Motor Overload Fault: Triggered by excessive motor current. The solution is to check motor thermal protection settings and motor load, and adjust parameters if necessary.
  • F014/F015 Output Phase Loss Fault: May be caused by poor motor connections or faulty output contactors. The solution is to check motor connections and output contactor status.

IV. Conclusion

The Schneider ATV310 series inverter user manual provides detailed operating instructions and parameter setting explanations, helping users quickly get started and fully utilize the inverter’s functions. Through this guide, users can understand the operating panel functions, password setting and unlocking methods, steps for setting the external terminal operating mode, and solutions for common fault codes, thereby more effectively using and maintaining the ATV310 inverter. In practical applications, users should set parameters reasonably according to specific needs and environmental conditions, and regularly check the device status to ensure long-term stable operation of the inverter.

Posted on Leave a comment

Fuji Frequency Converter FRENIC-Multi (FRN E1S) Series User Manual Guide

I. Introduction to the Operation Panel Functionality and Key Parameter Settings

1.1 Introduction to the Operation Panel Functionality

Fuji frequency converter E1S series operation panel function diagram

The Fuji Frequency Converter FRENIC-Multi (FRN E1S) series features an intuitive operation panel that allows users to easily monitor and control the operation of the frequency converter. The operation panel provides various functions such as setting operating frequencies, monitoring operating status, and configuring parameters.

Key Features of the Operation Panel:

  • LED Display: Displays various operating parameters such as output frequency, output current, and operating status.
  • UP/DOWN Keys: Used to adjust the set frequency.
  • RUN/STOP Keys: Used to start and stop the motor.
  • Mode Selection Keys: Allows switching between operation modes such as run mode, program mode, and alarm mode.

1.2 Setting the Electronic Thermal Relay Function

The electronic thermal relay function protects the motor from overheating by monitoring the output current of the frequency converter. To configure this function, the following parameters need to be set:

  • F10 (Thermal Relay Characteristic Selection): Selects the cooling system characteristic of the motor. Options include self-cooled motors with built-in fans and externally cooled motors.
  • F11 (Thermal Relay Action Value): Sets the current level at which the thermal relay will trip. This value should typically be set to around 100-110% of the motor’s rated current.
  • F12 (Thermal Time Constant): Sets the time it takes for the thermal relay to trip after the current exceeds the action value. This value depends on the motor’s thermal properties and the ambient operating conditions.

1.3 Configuring the Instantaneous Power Failure Restart Function

The instantaneous power failure restart function allows the frequency converter to automatically restart the motor after a temporary power outage. To enable and configure this function, the following parameters need to be set:

  • F14 (Instantaneous Power Failure Restart Selection): Enables or disables the instantaneous power failure restart function. Options include no restart (instant trip), no restart with reset on power restoration, restart at the frequency at the time of power failure (for general loads), and restart at the start frequency (for low-inertia loads).
  • H13 (Restart Waiting Time): Sets the time to wait after detecting a power failure before attempting to restart the motor. This helps to ensure that the residual voltage in the motor windings has decayed sufficiently to prevent inrush currents.
  • H14 (Frequency Ramp-Down Rate): Sets the rate at which the output frequency is reduced during restart to synchronize with the motor’s rotational speed and prevent excessive currents.
  • H16 (Instantaneous Power Failure Allowable Time): Sets the maximum time that can elapse after a power failure before the restart function is disabled.
Fuji frequency converter E1S standard wiring diagram

1.4 Selecting and Configuring the Terminal FM Function

The terminal FM provides an analog output signal that can be used to monitor various operating parameters of the frequency converter. To select and configure this function, the following steps are required:

  • F29 (Terminal FM Action Selection): Selects whether the terminal FM outputs a voltage signal (0-10V) or a pulse signal.
  • F30 (Output Gain): Adjusts the gain of the analog output signal. This allows scaling the output signal to match the input range of the monitoring equipment.
  • F31 (Function Selection): Selects the parameter to be monitored and output through the terminal FM. Options include output frequency, output current, output voltage, motor torque, load rate, and more.
  • F33 (Pulse Rate): When pulse output is selected, this parameter sets the pulse rate at 100% output.

By carefully configuring these parameters, users can fully utilize the advanced functionality of the Fuji FRENIC-Multi (FRN E1S) series frequency converter to optimize motor control and protect against potential faults.

Posted on Leave a comment

Panasonic Inverter VF200 Series User Manual Guide

Introduction

The Panasonic Inverter VF200 series is a powerful and flexible variable frequency drive (VFD) equipment widely used in the industrial automation field. This document aims to provide users with a detailed user guide to help them better understand and efficiently operate the VF200 series inverter.


Function diagram of Panasonic VF200 series inverter operation panel

1. Operation Panel Function Introduction, Parameter Upload, and Download

1.1 Operation Panel Function Introduction

The operation panel of the Panasonic Inverter VF200 series serves as the primary interface for user interaction. It features various functions and indicators to facilitate ease of use and monitoring.

  • Display Section: Displays output frequency, current, linear speed, set frequency, communication station number, abnormality content, various mode displays, and function setting data.
  • FWD/REV Indicators: Green indicators that show the forward/reverse operation status.
  • Panel Potentiometer: Used to set the operating frequency via the operation panel.
  • Alarm (ALM) Indicator: Red indicator that lights up in case of abnormalities or alarms.
  • RUN/STOP Buttons: Buttons to start/stop the inverter.
  • MODE Button: Toggles between various modes such as operation status display, frequency setting, rotation direction setting, control status monitoring, custom settings, function settings, and built-in memory settings.
  • SET Button: Used to switch modes, display data, and store settings.
  • ▲(UP) and ▼(DOWN) Buttons: Used to change data, output frequency, and set the rotation direction when operating via the panel.
VF200 picture

1.2 Uploading and Downloading Parameters

  • Uploading Parameters (CPY1): To upload the inverter’s functional parameters to the operation panel’s built-in memory, follow these steps:
    1. Stop the inverter.
    2. Press the MODE button four times to enter the function setting mode.
    3. Press the SET button.
    4. Use the ▲/▼ buttons to select “CPY1”.
    5. Press the SET button and set the value to “UPL”.
    6. Press the SET button again to start the upload process.
  • Downloading Parameters (CPY2): To download the parameters from the operation panel’s built-in memory to the inverter, follow these steps:
    1. Stop the inverter.
    2. Press the MODE button four times to enter the function setting mode.
    3. Press the SET button.
    4. Use the ▲/▼ buttons to select “CPY2”.
    5. Press the SET button and set the value to “dOL”.
    6. Press the SET button again to start the download process.

1.3 Setting and Eliminating Passwords

  • Setting a Password:
    1. Stop the inverter.
    2. Press the MODE button four times to enter the function setting mode.
    3. Use the ▲/▼ buttons to navigate to parameter P150.
    4. Press the SET button to display the current password.
    5. Use the ▲/▼ buttons to set a new password (range: 0000-9999).
    6. Press the SET button to save the password.
  • Eliminating a Password:
    1. Stop the inverter.
    2. Press the MODE button four times to enter the function setting mode.
    3. Use the ▲/▼ buttons to navigate to parameter P150.
    4. Press the SET button to display the current password.
    5. Set the password to “0000” using the ▲/▼ buttons.
    6. Press the SET button to eliminate the password.

1.4 Restoring Parameter Initialization

To restore the inverter’s parameters to their factory default settings, follow these steps:

  1. Stop the inverter.
  2. Press the MODE button four times to enter the function setting mode.
  3. Use the ▲/▼ buttons to navigate to parameter P151.
  4. Press the SET button to display the current setting.
  5. Set the value to “3” using the ▲/▼ buttons.
  6. Press the SET button to restore the parameters to their factory defaults.
Panasonic VF200 inverter control terminal wiring diagram

2. External Terminal Control for Forward/Reverse Rotation and PWM Frequency Control

2.1 Forward/Reverse Rotation Control via External Terminals

To achieve forward/reverse rotation control via external terminals, connect the relevant control signals to the designated terminals on the inverter.

  • Terminal Configuration:
    • SW1-SW5 (Control Circuit Terminals 4-8): These terminals can be configured to control forward/reverse rotation, start/stop, and other functions.
    • Configuration Steps:
      1. Stop the inverter.
      2. Enter the function setting mode by pressing the MODE button four times.
      3. Navigate to parameters P036-P040 using the ▲/▼ buttons.
      4. Set the desired function (e.g., forward/reverse, start/stop) to the corresponding terminal using the ▲/▼ buttons.
      5. Press the SET button to save the settings.

2.2 PWM (Pulse) Frequency Control

To control the inverter’s output frequency via PWM signals, follow these steps:

  • Terminal Configuration:
    • Terminal 7 (SW4) and Terminal 8: These terminals are used to receive PWM frequency control signals.
    • Configuration Steps:
      1. Stop the inverter.
      2. Enter the function setting mode by pressing the MODE button four times.
      3. Navigate to parameter P087 using the ▲/▼ buttons.
      4. Set the value to “1” to enable PWM frequency control.
      5. Press the SET button to save the setting.
      6. Connect the PWM signal source to terminals 7 and 8 according to the wiring diagram provided in the manual.
  • Additional Settings:
    • P088: Sets the number of PWM cycles to average for frequency calculation.
    • P089: Sets the PWM signal period.

By following this guide, users can effectively utilize the Panasonic Inverter VF200 series, leveraging its advanced features and flexible control options to meet various industrial automation needs.

Posted on Leave a comment

User Manual and Operation Guide for EACON EC5000 Series Frequency Converter

I. Introduction to Operation Panel Functions, Factory Reset, and Password Settings/Removal

The operation panel of the EACON EC5000 series frequency converter from Yikong integrates numerous functions, enabling users to easily configure and monitor the converter. The operation panel mainly comprises an LED display, a potentiometer, and various functional buttons. The LED display clearly shows the current operating status, set parameters, and alarm information, allowing users to monitor and adjust in real-time.

EC5000 physical image

Factory Reset:

  1. Preparation for Parameter Setting: Set the parameters in front of the frequency converter and switch the control mode to the factory reset state.
  2. Select Factory Reset: The display panel on the operation panel will show FXX. Use the up and down buttons to select 1 or 2 and press Enter. The screen will then display F00; press Enter again, and the screen will show F01.
  3. Confirm Reset: In the F01 state, press Enter. The screen will show F00, which is the final step of the factory reset.
  4. Complete Reset: After completing the above steps, press and hold the up and down buttons simultaneously to complete the factory reset.
  5. Reconfigure Parameters: After the factory reset, reconfigure the parameters according to actual requirements and save them.
EC5000 Terminal Block Function Diagram

Password Setting and Removal:

To ensure user and device security, the EACON EC5000 series provides a password setting function.

Password Setting:

  1. Access User Management Interface: On the home page, click the “User Management” menu and enter the initial account password “admin” to access.
  2. Modify Password: Click the “Modify Password” button, enter the original account password “admin”, then enter a new account password and confirm it, and click “Modify”.

Password Removal:

If the user forgets the password, they can reset the device to its factory settings using the reset button on the device. After the factory reset, the password will revert to “admin”. To prevent password theft, it is recommended to regularly change the password and set a relatively complex one.

II. Wiring and Parameter Setting for External Terminal Reversal and External Potentiometer Speed Regulation

EACON Inverter EC5000 Series Standard Wiring Diagram

External Terminal Reversal:

The EACON EC5000 series supports forward and reverse control via external terminals. Specific wiring and parameter settings are as follows:

  1. Wiring:
    • For reverse operation, connect S3, S2, S1, and SC. When the forward/reverse switch stop command (open) is activated, the frequency converter will stop operating.
    • For forward operation, connect the corresponding external switches and terminals as required.
  2. Parameter Setting:
    • No special settings are required; just ensure correct wiring of the external terminals.

External Potentiometer Speed Regulation:

Users can conveniently adjust the output frequency of the frequency converter using an external potentiometer, thereby achieving precise control of motor speed.

  1. Wiring:
    • Connect the output terminal of the external potentiometer to the analog input terminal of the frequency converter (such as the 0-10V or 4-20mA input terminal).
  2. Parameter Setting:
    • Enter the parameter setting interface of the frequency converter and select the corresponding analog input channel (such as FV or FI).
    • Set the corresponding parameters (such as B14 and B15) according to the type of external potentiometer (voltage or current).

III. Fault Code Analysis and Solutions

The EACON EC5000 series features comprehensive fault detection and diagnostic functions, displaying fault codes in real-time to help users quickly locate and resolve faults.

Common Fault Codes and Solutions:

  1. ERR: Indicates a control circuit fault. Possible causes include failure to establish transmission between the digital operator and the drive. Solutions include reinserting the digital operator and connectors, checking the wiring of the control circuit, or replacing the control plug-in board.
  2. Overvoltage, Overcurrent, Overload, etc.: These faults are usually related to the motor’s operating status or external load. Solutions include checking the motor’s operating status, load conditions, and ensuring the frequency converter’s output current and voltage are within specified ranges.
  3. Input/Output Phase Loss Fault: May be caused by poor power or motor wiring. Solutions include checking the power and motor wiring for firmness and reliability.
  4. Overheat Fault: May be caused by overheating of the frequency converter or motor. Solutions include checking if the cooling fan is operating normally, if the ambient temperature is too high, and if additional cooling measures are needed.

By following this guide, users can more effectively utilize the EACON EC5000 series frequency converter, achieving precise motor control and efficient operation. Prompt fault troubleshooting and resolution will improve equipment reliability and stability, extending its service life.

Posted on Leave a comment

User Guide for Marasen M740 Variable Frequency Drive


The Marasen M740 variable frequency drive is a high-performance industrial device widely used for pump control and constant pressure water supply applications. This guide, based on the manual, provides detailed explanations of the operation panel functions, key parameter settings, protective functions, and multi-pump networking operations to help users master the device.

M740 physical picture

1. Operation Panel Functions and Parameter Settings

1. Operation Panel Features

The M740 drive panel includes:

  • LED Display: Shows real-time operating status, current, voltage, and fault codes.
  • Key Functions:
    • Start/Stop Button: Controls the operation of the device.
    • Shift (▲) and Decrease (▼) Buttons: Used for parameter adjustments.
    • Confirm Button: Confirms settings or switches display content.

2. Key Parameters and Codes

The following table provides explanations and configuration methods for key parameter codes:

Pressure Holding Detection Interval (P1.02)

  • Function: Sets the time interval for pressure detection to prevent pressure fluctuations from triggering alarms.
  • Range: 5-120 seconds (recommended: 30 seconds).
  • Default Value: 30 seconds.

Sleep Frequency (P3.01)

  • Function: When the drive output frequency is below the set value for a period, the device enters sleep mode.
  • Range: 0-50 Hz (recommended: 10 Hz).
  • Default Value: 10 Hz.

Water Shortage Detection Mode (P4.01)

  • Function: Sets the logic for detecting water shortage.
  • Options:
    • 0: Disable water shortage detection.
    • 1: Pressure mode.
    • 2: Current mode.
  • Default Value: 1 (Pressure Mode).

Water Shortage Detection Pressure (P4.02)

  • Function: Sets the pressure threshold for water shortage detection in pressure mode.
  • Range: 0-1.0 MPa (adjust based on site needs).
  • Default Value: 0.2 MPa.

Water Shortage Detection Frequency (P4.03)

  • Function: Output frequency during water shortage detection.
  • Range: 0-50 Hz.
  • Default Value: 30 Hz.

Water Shortage Detection Delay (P4.04)

  • Function: Sets the delay time to avoid false alarms.
  • Range: 1-60 seconds.
  • Default Value: 5 seconds.

Water Shortage Detection Current (P4.05)

  • Function: Sets the current threshold for water shortage detection in current mode.
  • Range: 0-50 A.
  • Default Value: 5 A.

M740 Real Panel Diagram

2. Protective Features and Settings

1. Anti-Freeze Function (P5.01)

  • Function: Prevents pipes from freezing during winter to ensure safe operation in low temperatures.
  • Settings:
    • Configure the anti-freeze start temperature (recommended: 5°C).
    • Ensure the external temperature sensor is properly installed.

2. High/Low-Pressure Alarms (P6.01, P6.02)

  • High-Pressure Alarm (P6.01):
    • Function: Prevents damage caused by overpressure.
    • Range: 0-1.0 MPa (recommended: 0.9 MPa).
    • Default Value: 0.9 MPa.
  • Low-Pressure Alarm (P6.02):
    • Function: Alerts the system when water pressure is insufficient.
    • Range: 0-1.0 MPa (recommended: 0.1 MPa).
    • Default Value: 0.1 MPa.

3. Feedback Signal Disconnection Protection (P7.01)

  • Function: Detects signal integrity to prevent malfunction due to sensor or wiring issues.
  • Settings:
    • Enable feedback disconnection protection and configure the alarm logic.

4. Sleep Mode (P3.02)

  • Function: Puts the system into sleep mode under no-load or low-load conditions to save energy.
  • Settings:
    • Sleep Delay: Set the time to enter sleep mode (recommended: 10 minutes).
    • Wake-Up Mode: Triggered by pressure or flow signals.

M740 standard wiring diagram

3. Multi-Pump Networking and Parameter Configuration

The M740 supports a multi-pump networking mode, enabling intelligent switching and cooperative operation.

Usage

  1. Communication Configuration: Connect pumps via the RS485 bus and ensure proper communication.
  2. Master-Slave Pump Switching:
    • Set priority levels for master and slave pumps.
    • Automatically switch based on cumulative runtime.

Key Parameter Configuration

  • Networking Mode (P8.01):
    • Set to “1” (Multi-pump Networking Mode).
  • Switching Time (P8.02):
    • Set to 4-8 hours (adjust as needed).
  • Load Balancing (P8.03):
    • Enable load balancing to extend device lifespan.

4. Fault Codes and Troubleshooting

Below are common fault codes, their meanings, and suggested solutions:

Fault CodeMeaningSolution
E01Motor OverloadCheck load conditions and reduce power.
E02Input Voltage Too LowVerify that the power supply voltage is stable.
E03Output Short CircuitInspect cables for short circuits or grounding issues.
E04Heat Sink OverheatingClean the fan and remove dust from the heat sink.
E05Feedback Signal LostInspect sensors and communication wiring.

For other fault codes not listed, refer to the manual’s appendix section.


With this guide, you can quickly start using the M740 drive and gain expertise in its operations. For further assistance, please consult the complete user manual or contact technical support.

Posted on Leave a comment

User Guide and E-04 Fault Meaning and Solution for NSA2000 Series Inverters from Nengshi

I. Introduction to the Operation Panel of the Nengshi NSA2000 Series Inverters

Basic wiring diagram of NS2000 frequency converter

The operation panel of the Nengshi NSA2000 series inverters features intuitive and powerful control functions, capable of meeting the demands of various industrial applications. The main function keys on the operation panel include:

  • RUN: The inverter run key, used to start the inverter.
  • REV/JOG: The reverse/jog key, which can be set to reverse or jog functions according to parameters.
  • STOP/RST: The stop/reset key, used to stop the inverter or reset it in case of a fault.
  • PRG: The mode switch key, used to switch the working mode of the operation panel.
  • ENTER: The confirmation key, used to confirm the current status or store parameters.
  • ▲/▼: The data modification keys, used to modify function codes or parameter values.
  • SHIFT: The data bit switch key, used to select the bit to be modified when modifying data.

How to Restore Factory Settings (Initialize Parameters)

  1. With the inverter in the stopped state, press the PRG key to enter the parameter query mode.
  2. Press the PRG key again to enter the parameter modification mode.
  3. Use the ▲/▼ keys to select the function parameter F3.01.
  4. Press the ENTER key to enter the parameter modification state.
  5. Set the parameter value to 1 and press the ENTER key to confirm, restoring the inverter to factory settings.

How to Set Passwords and Parameter Write Protection Functions, and How to Eliminate Passwords

  1. Setting a Password: Modify the function parameter F3.03 to set a 4-digit numeric password within the range of 0000-9999.
  2. Parameter Write Protection: Function parameter F3.02 is used to set parameter write protection, allowing choices between allowing modification of all parameters, only allowing modification of frequency settings, or prohibiting modification of all parameters.
  3. Eliminating a Password: Reset the value of function parameter F3.03 to 0 to eliminate password protection.

Function and Setting Method of Jump Frequencies

Jump frequencies are used to avoid the mechanical resonance points of load devices, preventing equipment damage or performance degradation due to resonance. The setting method is as follows:

  1. Use the ▲/▼ keys to select function parameters F2.36F2.37F2.38F2.39F2.40, and F2.41, which are used to set the three jump frequencies and their corresponding jump ranges.
  2. Press the ENTER key to enter the parameter modification state, use the ▲/▼ keys to set the desired jump frequencies and ranges.
  3. After setting, press the ENTER key to confirm.

II. Realization of Terminal Forward/Reverse Control and External Potentiometer Frequency Control Functions

Terminal Forward/Reverse Control

Terminal forward/reverse control is achieved by controlling the on/off states of the FWD and REV terminals. The parameters that need to be set include:

  • F0.04: Operation command channel selection, set to 1 to control via terminals.
  • F4.06: FWD/REV terminal control mode, select the appropriate control mode according to actual needs (such as two-wire or three-wire mode).

In terms of wiring, connect the external control switches to the FWD and REV terminals respectively, and ensure that the common terminal COM is correctly connected.

External Potentiometer Frequency Control

The external potentiometer frequency control function allows users to change the output frequency of the inverter by adjusting the resistance value of an external potentiometer. The parameters that need to be set include:

  • F0.01: Frequency setting channel selection, set to 0 to use the potentiometer on the operation panel.
  • If using an external potentiometer, set F0.01 to 4 (VCI analog setting) or 5 (CCI analog setting), and configure the input range of VCI or CCI (F5.00-F5.03) according to actual conditions.

In terms of wiring, connect the three terminals of the external potentiometer to the VCI (or CCI), GND, and +10V (or 0V) terminals of the inverter.

E-04 FAULT

III. Meaning and Handling of E-04 Fault

Meaning of E-04 Fault

The E-04 fault indicates overvoltage during the acceleration process of the inverter. This is usually caused by abnormal grid voltage, restarting a rotating motor, or excessively short deceleration time.

Handling Method

  1. Check the Input Power Supply: Ensure that the grid voltage is stable and meets the operating requirements of the inverter.
  2. Avoid Restarting a Rotating Motor: If it is necessary to start a rotating motor, set it to DC brake start.
  3. Extend the Deceleration Time: Appropriately extend the deceleration time of the inverter based on actual conditions to reduce overvoltage.

Fault Repair

If the above methods cannot resolve the E-04 fault, further inspection and repair of the inverter may be required. It is recommended to contact professional after-sales service personnel or a technical support team for troubleshooting and repairs. During the repair process, ensure that the power supply to the inverter is cut off and operate in accordance with relevant safety regulations.

Conclusion

The Nengshi NSA2000 series inverters feature a rich set of operation panel functions. Through reasonable parameter settings and wiring configurations, various control functions can be realized. When handling E-04 faults, first check the input power supply and the operating status of the inverter, and take corresponding measures based on actual conditions. If further repairs are needed, it is recommended to contact a professional technical support team. Through proper use and maintenance, the Nengshi NSA2000 series inverters will provide users with stable and reliable variable frequency speed regulation solutions.

Posted on Leave a comment

User Manual Guide for Sanken SAMCO-vm05 Series Inverter

Basic Settings and Function Adjustments for the Inverter

1. Torque Compensation Function and Startup Mode Configuration

The Sanken SAMCO-vm05 series of inverters offers flexible torque compensation and startup mode settings to meet various operational requirements.

Torque Compensation Function

The torque compensation function allows fine-tuning of the inverter’s output to compensate for variations in motor load and maintain stable operation. To set the torque compensation:

  • Navigate to the function code menu (Cd004).
  • Enter the desired compensation percentage (0-20%). A higher percentage increases the output voltage at low frequencies, enhancing torque output.
Startup Mode Configuration

The startup mode determines how the inverter initiates the motor. To configure the startup mode:

  • Navigate to the function code menu (Cd009).
  • Select the appropriate startup mode:
    • Cd009 = 1: Start from the set startup frequency.
    • Cd009 = 2: Start with speed tracking (for smooth transitions from motor coasting to active control).
    • Cd009 = 3: Apply DC brake before starting from the set startup frequency (useful for loads that may be rotating unexpectedly).
2. Configuring Frequency Parameters

Proper configuration of frequency parameters is crucial for smooth and efficient motor operation.

Startup Frequency (Cd010)

This sets the initial frequency at which the motor begins to accelerate. To set:

  • Navigate to the function code menu (Cd010).
  • Enter the desired startup frequency (0.05-20 Hz).
Run Start Frequency (Cd011)

This sets the minimum frequency required to maintain motor operation. To set:

  • Navigate to the function code menu (Cd011).
  • Enter the desired run start frequency (0-20 Hz). Ensure it is lower than the startup frequency to prevent unintended motor stops.
Lower Limit Frequency (Cd008)

This sets the minimum allowable output frequency. To set:

  • Navigate to the function code menu (Cd008).
  • Enter the desired lower limit frequency (0.05-200 Hz).
Upper Limit Frequency (Cd007)

This sets the maximum allowable output frequency. To set:

  • Navigate to the function code menu (Cd007).
  • Enter the desired upper limit frequency (30-600 Hz, depending on the model).
3. Activating DC Brake and Configuring Related Parameters

The DC brake function helps quickly stop the motor by applying a DC current to the motor windings.

Activating DC Brake

To activate the DC brake:

  • Ensure the DC brake function is enabled in the function code menu (typically defaulted to enabled).
  • Configure the DC brake start frequency (Cd014), brake time (Cd015), and brake strength (Cd016) as required.
Configuring DC Brake Parameters
  • DC Brake Start Frequency (Cd014): Sets the motor speed at which the DC brake engages (0.2-20 Hz).
  • DC Brake Time (Cd015): Sets the duration of the DC brake application (0.1-10 seconds).
  • DC Brake Level (Cd016): Sets the strength of the DC brake (1-10 levels).

By carefully configuring these parameters, you can optimize the performance and reliability of your Sanken SAMCO-vm05 series inverter, ensuring smooth and efficient motor control tailored to your specific application needs.