1. Panel Startup, Speed Adjustment, Password Setting & Removal, and Parameter Initialization

Panel Startup and Speed Adjustment

The KCLY INVERTER KOC600 series supports startup and speed adjustment via the operation panel. To set up panel startup:

  1. Ensure the command source is set to the operation panel: Navigate to the parameter b0-02 and set it to 0 (Operation Panel Command Channel). This ensures that the startup and speed commands come from the panel.
  2. Adjust the frequency: Use the  and  keys on the panel to increase or decrease the set frequency (b0-12). The motor will run at the set frequency once the startup command is given.
Function diagram of KCLY INVERTER KOC600 series operation panel

Password Setting and Removal

To set a password for the KOC600 series inverter:

  1. Navigate to the password parameter: Go to parameter A0-00 and enter the desired password value (0-65535).
  2. Save and exit: Press the DATA/ENTER key to save the password setting.

To remove the password:

  1. Enter the current password: Go to parameter A0-00 and enter the current password.
  2. Clear the password: Set the value to 0 and press the DATA/ENTER key to save.

Parameter Initialization

To initialize the parameters to their factory defaults:

  1. Navigate to the initialization parameter: Go to parameter A0-09.
  2. Select the initialization option: Set A0-09 to 1 to restore factory settings excluding motor parameters, 2 to restore factory settings including motor parameters, or 3 for reserved purposes.
  3. Save and reset: Press the DATA/ENTER key to save and reset the parameters.
KCLY INVERTER KOC600 Series Wiring Diagram

2. External Terminal Startup and Pulse Frequency Speed Adjustment

Terminal Connection and Settings

To set up external terminal startup and pulse frequency speed adjustment, you need to connect and configure specific terminals:

  1. Connect the external startup terminal: Typically, you would connect an external switch or relay to the FWD (forward) and REV (reverse) terminals on the inverter. Ensure proper grounding and wiring according to the manual.
  2. Set the command source to terminal control: Navigate to parameter b0-02 and set it to 1 (Terminal Command Channel). This allows the inverter to receive startup and speed commands from the external terminals.
  3. Configure the pulse input terminal: If using pulse frequency for speed adjustment, connect the pulse generator to the DI6 (High-Speed Pulse Input) terminal.
  4. Set the frequency source to pulse input: Go to parameter b0-03 and set it to 5 (PULSE pulse setting). This configures the inverter to use the pulse input on DI6 as the frequency source.
  5. Adjust pulse-to-frequency parameters: Configure parameters b5-00 to b5-03 to define the relationship between the pulse input frequency and the inverter’s output frequency.

Example Configuration Steps

  1. Connect the external switch to FWD: Use a normally open switch connected between FWD and COM.
  2. Set the command source:
    • Navigate to b0-02 and set it to 1.
  3. Connect the pulse generator to DI6: Ensure the pulse generator outputs a compatible voltage and frequency range.
  4. Configure the pulse input:
    • Set b0-03 to 5 (PULSE pulse setting).
    • Adjust b5-00 to 0.00kHzb5-02 to the maximum expected pulse frequency (e.g., 50.00kHz), b5-01 to 0.0%, and b5-03 to 100.0%.
  5. Save the settings: Press the DATA/ENTER key to save all configurations.

By following these steps, you can set up the KCLY INVERTER KOC600 series for external terminal startup and pulse frequency speed adjustment. Always refer to the user manual for detailed wiring diagrams and additional configuration options.