Posted on Leave a comment

Implementing 485 Communication between Schneider ATV12 Series Inverter and PLC

In modern industrial automation systems, the inverter plays a crucial role in controlling motor operations. Communication between the inverter and the Programmable Logic Controller (PLC) is essential for precise control and monitoring. The Schneider ATV12 series inverter utilizes the RS-485 communication protocol to exchange data with the PLC, enabling accurate motor control. This article provides a detailed guide on implementing 485 communication between the Schneider ATV12 series inverter and PLC, including specific wiring, communication features, and implementation methods.

ATV12 physical working status

I. Overview of Schneider ATV12 Series Inverter

The Schneider ATV12 series inverter is a high-performance variable frequency drive widely used in various industrial settings. It offers a broad power range, high control precision, and significant energy savings. By communicating with the PLC, the inverter can achieve more flexible and efficient control, meeting the demands of complex industrial environments.

ATV12 communication wiring

II. Features of RS-485 Communication Protocol

RS-485 is a half-duplex communication protocol commonly used in industrial automation. Its key features include:

  1. Long-Distance Transmission: RS-485 supports long-distance data transmission, up to 1200 meters, making it suitable for large industrial sites.
  2. Multi-Drop Communication: It supports multiple devices on the same bus, ideal for complex industrial control networks.
  3. Strong Anti-Interference Capability: Using differential signaling, RS-485 offers strong anti-interference capabilities, suitable for environments with significant electromagnetic interference.
PLC communication wiring

III. Specific Wiring between Schneider ATV12 Inverter and PLC

To implement 485 communication between the Schneider ATV12 inverter and PLC, follow these steps:

  1. Preparation:
  • Ensure that the power to both the inverter and PLC is turned off for safety.
  • Prepare the RS-485 communication cable, typically a shielded twisted pair.
  1. Inverter-Side Wiring:
  • Locate the communication port on the Schneider ATV12 inverter labeled “RDA+” and “RDA-”.
  • Connect the two signal wires of the RS-485 cable to the “RDA+” and “RDA-” terminals.
  • Ground the cable shield to enhance anti-interference capability.
  1. PLC-Side Wiring:
  • On the PLC’s 485 communication module, find the corresponding “A” and “B” terminals.
  • Connect the RS-485 cable from the inverter to the “A” and “B” terminals on the PLC.
  • Ground the cable shield.
  1. Termination Resistor Matching:
  • Add a 120-ohm termination resistor at each end of the bus to eliminate signal reflections and ensure communication quality.

IV. Communication Features of Schneider ATV12 Inverter

The Schneider ATV12 series inverter has the following communication features:

  1. Multi-Protocol Support: Supports multiple communication protocols such as Modbus RTU, accommodating various industrial control requirements.
  2. High Reliability: Built-in EMC filters reduce electromagnetic interference, enhancing communication reliability.
  3. Flexible Configuration: Communication parameters such as baud rate and address can be flexibly configured to meet different communication needs.

V. Implementation Method

  1. Parameter Configuration:
  • Enter the inverter’s configuration mode and set communication parameters, including baud rate, data bits, parity, and stop bits.
  • Ensure that the communication parameters match those of the PLC to enable correct data transmission.
  1. Communication Testing:
  • After powering on, use the PLC’s communication software or programming tools to test the connection with the inverter.
  • Verify that data transmission is correct and that the inverter responds accurately to the PLC’s control commands.
  1. Function Verification:
  • In actual operation, verify the communication functionality between the inverter and PLC to ensure the motor operates as expected.
  • Adjust communication parameters and control strategies as needed to optimize system performance.
Touchscreen working status

VI. Conclusion

The Schneider ATV12 series inverter achieves efficient and reliable data exchange with the PLC through the RS-485 communication protocol, providing strong support for industrial automation control systems. Proper wiring and parameter configuration enable stable communication between the inverter and PLC, enhancing control precision and reliability. In practical applications, attention to communication line layout and shielding is crucial to ensure communication quality and minimize interference. Through thoughtful design and testing, the Schneider ATV12 inverter can leverage its high-efficiency control advantages in complex industrial environments.

Posted on Leave a comment

Causes and Solutions for the E0006 Fault in HPMONT HD09 Series Inverters

1. Fault Overview

The E0006 fault in the HPMONT HD09 series inverter corresponds to a “DC bus constant-speed overvoltage fault.” This means that the DC bus voltage in the inverter exceeds the safety limit during constant-speed operation. Such faults can cause equipment shutdowns, affecting production and normal operation.

HP09 physical picture
oplus_32

2. Fault Mechanism Analysis

  1. Causes of DC Bus Overvoltage: The DC bus voltage in the inverter is converted from AC through a rectifier. If the input voltage is too high or too low, it can cause instability in the bus voltage. During load operation, especially during rapid stops, large load inertia, or abnormal braking systems, the DC bus voltage may rise sharply, triggering overvoltage protection.
  2. Constant-Speed Overvoltage Scenario: The inverter operates at a constant speed, maintaining a stable motor frequency. If the input power supply voltage is too high, or if the acceleration/deceleration times are improperly set, overvoltage can occur. Furthermore, if the braking system is improperly configured or not correctly installed, excessive voltage can be generated during deceleration.
  3. Potential Circuit Reasons:
    • High input voltage: Especially in areas where the grid voltage fluctuates significantly, the inverter may detect overvoltage.
    • Abnormal braking system: If the braking unit or brake resistor is incorrectly configured, or if it is not equipped in systems with heavy loads, excessive voltage can be generated during deceleration.
    • System overload: If the load is too heavy or has significant inertia, the inverter may not be able to decelerate effectively, leading to overvoltage faults.

3. On-Site Fault Handling Methods

  1. Check Input Voltage:
    • Use a multimeter to check whether the input voltage to the inverter is within the normal range. If the input voltage exceeds the specified range (e.g., too high), consider using a voltage regulator or check the stability of the power grid.
  2. Check Acceleration/Deceleration Time Settings:
    • Refer to the inverter’s user manual and check the acceleration and deceleration times (parameters such as F03.01, F03.02, etc.). Too short a deceleration time can cause a sharp fluctuation in the bus voltage. It is recommended to extend the deceleration time to avoid overvoltage.
  3. Check Braking System:
    • For loads requiring deceleration, inspect the braking unit and brake resistor configuration to ensure they are appropriately sized for the load. If necessary, add a braking unit or adjust the brake resistor’s power and resistance.
  4. Inspect and Check the Circuit:
    • Inspect the internal circuitry of the inverter for loose connections, poor contact, or damage, especially in the power and braking resistor wiring terminals.

4. Specific Circuit Repair Methods

  1. Input Voltage Issues:
    • If the input voltage is too high, consider adding measures to stabilize the grid power, such as using overvoltage protection devices. For areas with significant voltage fluctuations, it is recommended to use appropriate power protection equipment, such as overvoltage protectors.
  2. Braking System Faults:
    • If the braking system is causing overvoltage, first verify whether the braking resistor is correctly specified. If the braking resistor is inadequate or damaged, select a properly rated resistor according to the load requirements. Check that the braking unit is properly connected, and ensure the braking circuit is securely wired.
  3. Capacitor Issues:
    • If the capacitor is aging or damaged, it could cause the DC bus voltage to be unstable. In this case, replace the damaged capacitors and verify whether the capacitor’s capacity matches the requirements.
  4. Reconfigure Deceleration Time:
    • For loads with high inertia or large power, it is necessary to increase the deceleration time. This can be achieved by adjusting parameters such as F03.02 to prevent overvoltage faults. Ensure that the deceleration process is smooth and does not lead to a sharp voltage change.
E6000
oplus_32

5. Conclusion

The E0006 fault is typically caused by high input voltage, braking system issues, or improper acceleration/deceleration time settings. When addressing this fault, it is essential to check key parameters such as input voltage, acceleration/deceleration times, and the braking system. Specific circuit repair actions, such as replacing capacitors, adjusting the braking system configuration, and extending deceleration times, can restore normal operation of the inverter.

Posted on Leave a comment

User Guide for the Anrui E6 Series Frequency Inverter


1. Introduction to the Inverter’s Control Panel Functions

The Anrui E6 series frequency inverter is designed with an intuitive control panel, making it easy for users to set and monitor various parameters. The control panel mainly consists of the display screen, function selection keys, and adjustment knob. Each component serves the following functions:

  • Display Screen: Displays the current operating status, frequency, alarm information, and parameter settings.
  • Function Keys: These keys allow the user to navigate through different functional menus, view and modify parameters.
  • Adjustment Knob: Used to adjust the output frequency, enabling users to control it in real-time.
E6 physical image

2. How to Copy Parameters to Another Inverter

The E6 series inverter provides a convenient parameter copy function, allowing users to quickly copy the settings of the current inverter to another one. The steps are as follows:

  1. Access the control panel and select the Parameter Copy function.
  2. In the menu, choose the source inverter (current inverter) and target inverter (the inverter where settings need to be copied).
  3. Confirm the operation and complete the data transfer. The target inverter will replicate all the settings from the source inverter.

This allows users to easily configure multiple inverters with identical settings, ensuring consistency across the system.

3. How to Initialize Parameters

In some cases, users may need to restore the inverter to its default settings. The parameter initialization function can reset all custom settings and restore the inverter to its initial configuration. Here’s how to perform the initialization:

  1. Access the inverter’s settings menu and select Parameter Initialization.
  2. Choose either “Restore Factory Settings” or “Clear Fault History.”
    • Restore Factory Settings: Resets all parameters to the default values.
    • Clear Fault History: Removes any fault records from the inverter’s history.
  3. Execute the initialization to return the inverter to its default state.

The initialization function allows for a quick reset of the inverter when needed, ensuring that it operates in its original configuration.

4. How to Set and Remove Passwords

The Anrui E6 series frequency inverter offers password protection to prevent unauthorized changes to settings and parameters. Here are the steps for setting and removing passwords:

  1. Set a Password: Go to the settings menu, select Password Setting, enter the desired password, and confirm. The inverter will then be protected by a password.
  2. Remove the Password: To remove the password protection, go to the “Password Management” section, select “Clear Password,” and enter the administrator password to confirm deletion.

If a password is set, the inverter will require it when exiting the editing mode. This security feature helps prevent unauthorized modifications to the parameters, improving safety.

5. How to Set Parameter Access Restrictions

To further protect the inverter, the E6 series supports parameter access restrictions. Through this feature, users can limit access to certain parameters, preventing unauthorized users from modifying them. This can be configured in the “Access Permissions” section of the settings menu.

6. External Terminal Control and Potentiometer Speed Control

The Anrui E6 series frequency inverter supports external terminal control for forward/reverse operation and potentiometer speed control. Here’s how to configure these features:

  • External Terminal Forward/Reverse Control: Users can connect forward/reverse control signals to the X1 and X2 terminals and set the relevant parameters to control the motor’s rotation direction.
  • External Potentiometer Speed Control: Users can connect an external potentiometer to the X3 terminal to control the speed by adjusting the potentiometer’s position. Set the relevant parameters in the inverter to control the frequency range based on the potentiometer’s position.

After these settings, the external terminal signals will directly influence the operation of the inverter.

7. Inverter Fault Codes and How to Handle Them

The E6 series inverter provides various fault codes to help diagnose issues quickly. Some common fault codes include:

  • OV1/OV2: Over-voltage fault, typically caused by high input voltage.
  • OC1/OC2: Overload protection fault, possibly due to excessive load or high current.
  • UV1/UV2: Under-voltage fault, check if the power supply is stable.

Each fault code comes with detailed troubleshooting advice, which can be followed to resolve the issues.

E6 standard wiring diagram

8. Conclusion

By properly utilizing the functions of the Anrui E6 series frequency inverter, users can achieve more efficient and secure control of the equipment. Whether it’s for parameter configuration, fault troubleshooting, or integration with external control systems, the E6 series offers a wide range of options to meet the needs of various applications.

This is the main operational and setup guide for the Anrui E6 series frequency inverter. By following the correct procedures and settings, users can fully utilize the performance of the inverter and ensure long-term stable operation. If any issues arise during use, it is recommended to refer to the manual or contact technical support.


Posted on Leave a comment

User Guide for SZOR ZC1000 Series AC Drive Manual


The SZOR ZC1000 Series AC Drive is a high-performance variable frequency control device widely used in various industrial automation control systems. This article provides a detailed introduction to the operation panel functions, parameter settings, and troubleshooting for the ZC1000 Series, helping users better understand and utilize this equipment.

ZC1000 physical picture

I. Introduction to Operation Panel Functions

1.1 Overview of Operation Panel Functions

The operation panel of the ZC1000 Series AC Drive is the primary interface for user interaction with the device. Through the operation panel, users can control the drive’s operating status, read status data, and adjust parameters. The operation panel mainly includes the following parts:

  • Status Indicator Lights: Indicate the drive’s running status, fault status, etc.
  • Unit Indicator Lights: Display the current unit, such as frequency (Hz), current (A), voltage (V), etc.
  • Code Display Area: Displays various monitoring data and alarm codes.
  • Analog Potentiometer: Used to set the frequency when the frequency source is set to the analog potentiometer.
  • Keypad Button Area: Includes program keys, entry keys, up/down keys, right shift keys, run keys, stop/reset keys, etc., used for operating the drive and modifying parameters.

1.2 Parameter Copying

To copy parameters from one drive to another, follow these steps:

  1. Upload Parameters to Keypad EEPROM: On the source drive, set F08.29 to 1 to upload control panel parameters to the keypad EEPROM.
  2. Download Parameters to Target Drive: On the target drive, set F08.29 to 2 or 3 to download parameters from the keypad EEPROM to the control panel, and choose whether to download motor parameters.

1.3 Parameter Initialization

Parameter initialization restores the drive’s parameters to factory settings. Follow these steps:

  1. Enter Parameter Setting Interface: Press the “PRG” key to enter the parameter setting interface.
  2. Select Parameter Initialization Option: Locate parameter F00.18 and set it to 1 to restore default values.
  3. Confirm and Save: Press the “ENT” key to confirm and save the parameters.

1.4 Setting and Removing Passwords

To protect the drive’s parameters from unauthorized access, you can set a password:

  1. Set Password: In the parameter setting interface, locate parameter F07.00 and set it to a non-zero value to set the password.
  2. Remove Password: Set parameter F07.00 to 0 to remove the password.

1.5 Parameter Access Restrictions

To further protect the drive’s parameters, you can set parameter access restrictions:

  1. Set Parameter Access Restrictions: In the parameter setting interface, locate parameter F08.21 and set it to 0x0000 to restrict parameter access.
  2. Remove Parameter Access Restrictions: Set parameter F08.21 to another value to remove access restrictions.

II. External Terminal Forward/Reverse Control and External Potentiometer Speed Control

2.1 External Terminal Forward/Reverse Control

External terminal forward/reverse control allows the use of external switches or buttons to control the drive’s forward/reverse operation. The wiring and parameter settings are as follows:

  1. Wiring: Connect the external switch or button to the drive’s DI1 terminal (forward) and DI2 terminal (reverse).
  2. Parameter Settings: In the parameter setting interface, locate parameter F05.01 and set it to 1 (forward) or 2 (reverse).

2.2 External Potentiometer Speed Control

External potentiometer speed control allows the use of an external potentiometer to set the drive’s frequency. The wiring and parameter settings are as follows:

  1. Wiring: Connect the external potentiometer to the drive’s Al1 terminal.
  2. Parameter Settings: In the parameter setting interface, locate parameter F00.06 and set it to 2 (analog Al1 setting).
ZC1000 standard wiring diagram

III. Fault Codes and Troubleshooting

The ZC1000 Series AC Drive may encounter various faults during operation. Fault codes help quickly identify the cause and address the issue. Below are some common fault codes and their meanings, along with troubleshooting steps:

3.1 Common Fault Codes

  1. E.out 1/2/3: IGBT U/V/W phase protection fault, possibly due to fast acceleration, internal IGBT damage, or poor driving wire connections. Solutions include increasing acceleration time, replacing the power unit, and checking driving wires.
  2. E.oc 1/2/3: Acceleration overcurrent fault, possibly due to fast acceleration/deceleration, low grid voltage, or insufficient drive power. Solutions include increasing acceleration time, checking input power, and selecting a larger drive.
  3. E.ou 1/2/3: Acceleration or constant overvoltage fault, possibly due to abnormal input voltage or large energy feedback. Solutions include checking input power and increasing energy consumption components.
  4. E.LU: Bus undervoltage fault, possibly due to low supply voltage. Solution: Check the input power supply.
  5. E.SPI: Input phase loss fault, possibly due to input phase loss or fluctuation. Solution: Check the input power supply.

3.2 Troubleshooting Steps

  1. Confirm Fault Code: Use the code display area on the operation panel to confirm the fault code.
  2. Identify Fault Cause: Refer to the fault code to identify possible causes.
  3. Take Action: Based on the fault cause, take appropriate actions such as checking power supply, replacing components, or adjusting parameters.
  4. Restart the Drive: After addressing the fault, restart the drive to ensure the issue is resolved.

Conclusion

The SZOR ZC1000 Series AC Drive is a powerful and user-friendly variable frequency control device. This guide provides insights into the operation panel functions, parameter settings, and troubleshooting for the ZC1000 Series. By understanding these aspects, users can effectively utilize the ZC1000 Series AC Drive, enhancing work efficiency and prolonging the device’s lifespan.

Posted on Leave a comment

User Manual Guide for Bosch Rexroth VFC3610/VFC5610 Series Frequency Converters

The Bosch Rexroth VFC3610/VFC5610 series frequency converters are high-performance devices widely used in industrial automation, mechanical processing, pump and fan control, and other fields. This article provides a detailed guide on using the user manual for these frequency converters, including operating panel functions, parameter settings, and troubleshooting.

VFC3610VFC5610 physical picture

I. Operating Panel Function Introduction

1.1 Operating Panel Functions

The operating panel of the Bosch Rexroth VFC3610/VFC5610 series offers a range of functions for parameter settings, monitoring, and diagnostics. The main components include an LED display, navigation knob, function button, stop button, and run button.

  • LED Display: Shows the operating status, parameter values, and fault codes.
  • Navigation Knob: Used to select parameter groups/parameters and set parameter values.
  • Function Button (Func): Enters the parameter group screen and returns to the previous screen.
  • Stop Button (Stop): Stops the frequency converter.
  • Run Button (Run): Starts the frequency converter.

1.2 Parameter Copying

Users can copy parameter settings from one frequency converter to another using the parameter copy function:

  1. Back up parameters to the operating panel: Set parameter [b0.11] = ‘1: Backup parameters to the operating panel’.
  2. Install the operating panel on the target frequency converter.
  3. Set parameter [b0.11] = ‘2: Copy parameters from the operating panel’ to complete the parameter copying process.

1.3 Password Setting and Removal

To protect parameter settings, users can set a password. The steps for setting and removing the password are as follows:

  • Set Password: Set parameter [b0.20] to the desired user password (range: 0…65,535).
  • Remove Password: Set parameter [b0.20] to 0.

1.4 Parameter Access Restriction

To prevent unauthorized access to parameter settings, the frequency converter offers access restriction features. Users can set parameter [b0.00] to limit access rights:

  • 0: Basic parameters
  • 1: Standard parameters
  • 2: Advanced parameters
  • 3: Startup parameters
  • 4: Modified parameters

1.5 Parameter Initialization

In some cases, users may need to initialize the frequency converter parameters to their default settings. The steps are as follows:

  1. Set parameter [b0.10] = ‘1: Restore default settings’.
  2. The frequency converter will automatically revert to the factory default settings.
VFC3610_VFC5610 Standard Wiring Diagram

II. External Terminal Control and Speed Adjustment

2.1 External Terminal Forward and Reverse Control

Users can control the forward and reverse operations of the frequency converter through external terminals. The steps are as follows:

  1. Set parameter [E0.17] = ‘0: Forward / Reverse’.
  2. Connect the terminals:
  • X1: Multifunctional digital input for forward control.
  • X2: Multifunctional digital input for reverse control.

2.2 External Potentiometer Speed Adjustment

Users can adjust the speed of the frequency converter using an external potentiometer. The steps are as follows:

  1. Set parameter [E0.00] = ‘2: Al1 Analog Input’.
  2. Connect the terminals:
  • Al1: Analog voltage input for frequency setting.
  • GND: Common ground for analog input.

III. Fault Codes and Handling

3.1 Fault Codes

The Bosch Rexroth VFC3610/VFC5610 series provides detailed fault codes to help users quickly identify and resolve issues. Some common fault codes and their meanings are as follows:

  • 0: No fault
  • 1: OC-1, Overcurrent during constant speed
  • 2: OC-2, Overcurrent during acceleration
  • 3: OC-3, Overcurrent during deceleration
  • 4: OE-1, Overvoltage during constant speed
  • 5: OE-2, Overvoltage during acceleration
  • 6: OE-3, Overvoltage during deceleration
  • 7: OE-4, Overvoltage during stop
  • 8: UE-1, Undervoltage during operation
  • 9: SC, Current surge or short circuit
  • 10: IPH.L, Input phase loss
  • 11: OPH.L, Output phase loss
  • 12: ESS-, Soft start fault
  • 20: OL-1, Overload
  • 21: OH, Overheating
  • 23: FF, Fan failure
  • 24: Pdr, No-load protection
  • 25: Col:, Command value loss

3.2 Fault Handling

When a fault occurs, users should take appropriate actions based on the fault code’s meaning. For example:

  • Overcurrent Faults (1, 2, 3): Check if the motor and load are functioning correctly. Ensure proper cable connections and adjust parameter settings if necessary.
  • Overvoltage Faults (4, 5, 6, 7): Check if the power supply voltage is stable. Ensure proper cable connections and adjust parameter settings if necessary.
  • Undervoltage Fault (8): Check if the power supply voltage is normal. Ensure proper cable connections.
  • Short Circuit Fault (9): Check cable and terminal connections for short circuits.
  • Phase Loss Faults (10, 11): Check cable and terminal connections for phase loss.
  • Overload Fault (20): Check if the motor and load are functioning correctly. Ensure proper cable connections and adjust parameter settings if necessary.
  • Overheating Fault (21): Check the cooling conditions of the frequency converter. Ensure the fan is working properly and clean the heat sink if necessary.
  • Fan Failure (23): Check if the fan is working properly. Replace the fan if necessary.
  • No-load Protection (24): Check if the motor is running correctly and ensure the load is normal.
  • Command Value Loss (25): Check communication cables and terminals for proper connections. Ensure communication is functioning correctly.

Conclusion

The Bosch Rexroth VFC3610/VFC5610 series frequency converters are powerful and user-friendly devices suitable for various industrial control applications. This guide provides a comprehensive overview of the operating panel functions, parameter settings, and fault handling for these frequency converters. By following this guide, users can effectively operate and maintain these devices, enhancing productivity and reliability.

Posted on Leave a comment

Analysis and Handling of ER.258 Fault in Inovance IS620P Servo System

In industrial automation, servo systems play a crucial role in precise control and efficient driving tasks. However, in practical applications, servo systems may encounter various faults that affect the stability and efficiency of production lines. One of the common error codes in the Inovance IS620P servo system is ER.258, which can disrupt the normal operation of the system. This article will provide an in-depth analysis of the ER.258 fault, explore its causes, and suggest reasonable handling methods.

ER,258

1. Analysis of ER.258 Fault

1.1 Basic Meaning of ER.258 Fault

The ER.258 fault is typically associated with the speed, torque, and position control in the servo system during the return-to-zero process. According to the design of the Inovance IS620P servo, the return-to-zero process begins after the motor contacts the limit switch. When the motor hits the limit switch, if the motor’s speed and torque meet certain threshold values, the system considers that the motor has reached the limit position and triggers the return-to-zero operation. However, in some cases, if the motor’s speed and torque are out of the normal range, or the system fails to accurately determine if the motor has stopped, the ER.258 fault is triggered.

1.2 Conditions for the Fault to Occur

Specifically, the ER.258 fault is triggered in the following situations:

  • Overcurrent or Overload: When the motor contacts the limit switch, if the current suddenly increases, or if the resistance at the limit position is too high, causing the motor’s torque to exceed the allowed range, an overcurrent or overload protection alarm will be triggered.
  • Exceeding Position Limit: When the motor reaches the mechanical limit, if it continues to try to move or cannot stop properly, the system considers that the motor has exceeded the predefined position and triggers the alarm.
  • Motor Has Not Fully Stopped: When the H05-56 parameter is set too sensitively (such as setting it to 0), the system might wrongly interpret that the motor has stopped while it has not completely stopped, leading to the ER.258 fault.

1.3 Influence of H05-56 Parameter on the Fault

The H05-56 parameter plays an important role during the return-to-zero process. It sets the minimum speed threshold, and when the motor’s speed falls below this value, the system assumes that the motor has stopped and initiates the return-to-zero process. If H05-56 is set to 0, the system becomes overly sensitive in determining if the motor has stopped, which might lead to the motor not fully stopping, but the system falsely interpreting it as a stop and triggering the ER.258 fault.

1.4 Impact of Parameter Setting on the Fault

When the H05-56 parameter is set to 1, the system requires the motor’s speed to drop below 1 rpm before it determines that the motor has stopped and initiates the return-to-zero process. This provides more time and space for the motor to decelerate and avoids triggering the fault caused by speed instability or excessive torque. According to data, changes in the H05-56 parameter directly affect the system’s tolerance, ensuring that the motor and drive system will not cause overcurrent or excessive torque after contacting the limit switch, thus preventing the ER.258 fault.

ISP620P

2. Causes of ER.258 Fault

2.1 Behavior of the Motor After Contacting the Limit Switch

During the return-to-zero process, the servo motor first contacts the mechanical limit switch. At this point, the motor’s torque and speed will be significantly affected. Once the motor contacts the limit switch, the system evaluates the motor’s speed and torque. If the torque exceeds a certain set value, the system assumes that the motor has reached the mechanical limit and stops further movement. If not, the motor may continue to attempt movement, leading to abnormal current or torque, triggering the ER.258 fault.

2.2 Incorrect Determination of Motor Stop Status

When the H05-56 parameter is set to 0, the system may mistakenly determine that the motor has stopped even if it has not completely stopped. This could happen because the motor might still have slight inertia or be moving slightly, causing the system to incorrectly interpret this as a stop condition and initiate the return-to-zero process prematurely, leading to the fault.

2.3 Excessive Current and Torque

After the motor contacts the limit switch, it may experience significant resistance or load, generating excessive torque. If the current exceeds the maximum allowable capacity of the drive, the system will trigger an overcurrent alarm, causing the ER.258 fault to occur.

2.4 Uneven Load or Slow Deceleration

If the motor’s load is uneven or the deceleration process is slow, the motor may continue to attempt movement after contacting the limit switch, generating excessive current or torque, triggering the ER.258 fault. Proper adjustment of the H05-56 parameter can help prevent this situation.

3. Handling Methods for ER.258 Fault

3.1 Adjusting the H05-56 Parameter

As mentioned earlier, the H05-56 parameter has a significant impact on the system during the return-to-zero process. Setting H05-56 to 1 can effectively prevent the ER.258 fault. This setting requires the motor’s speed to drop below 1 rpm before it is considered stopped, thus providing more time for the motor to decelerate and avoiding triggering the fault due to instability.

3.2 Checking Load and Torque

During the return-to-zero process, the motor’s load and torque can cause excessive current, triggering the ER.258 fault. Check whether the motor’s load and torque are too high and ensure that the motor can stop stably after contacting the limit switch. This will help avoid overcurrent or overload protection from being triggered.

3.3 Calibrating the Limit Switch

Check and calibrate the position of the mechanical limit switch to ensure that the motor stops at the correct position. Early or late contact with the limit switch could prevent the motor from stopping properly, leading to excessive torque and current, and triggering the ER.258 fault.

3.4 Adjusting the Motor’s Deceleration Settings

If the motor’s deceleration process is too slow, it may cause excessive torque or current, triggering the fault. Adjust the motor’s deceleration time and method to ensure that the motor decelerates smoothly after contacting the limit switch, avoiding excessive current and torque.

3.5 Regular Maintenance and Inspection

Regularly inspect the operation status of the servo system, including the motor, drive, limit switches, and other components. Clean the mechanical parts from dirt and check the motor’s operating condition to ensure that the system operates within normal ranges and prevent faults due to wear or malfunction.

4. Conclusion

The ER.258 fault is a common alarm in the Inovance IS620P servo system during the return-to-zero process. It is usually related to motor speed, torque, position control, and the functioning of the limit switch. By adjusting the H05-56 parameter, checking the load and torque, calibrating the limit switch, optimizing the motor deceleration settings, and performing regular maintenance, the occurrence of the ER.258 fault can be effectively prevented. Proper system settings and regular maintenance ensure the stable operation of the servo system, improving the reliability and efficiency of the equipment.

Posted on Leave a comment

User Manual Guide for Yushu Inverter YS510 Series

I. Introduction to the Inverter Operator Panel Functions

The Yushu Inverter YS510 series operator panel integrates a wealth of functions, enabling users to conveniently set parameters, monitor operating status, and diagnose faults. The operator panel primarily includes a digital display, function indicator lights, programming keys, data confirmation keys, shift keys, run keys, stop/reset keys, etc.

  • Digital Display: Used to display key information such as the current operating frequency, set frequency, and fault codes.
  • Function Indicator Lights: Such as RUN/TUNE (operating status indicator), FWD/REV (forward/reverse indicator), LOCAL/REMOT (control mode indicator), etc., to indicate the current operating status of the inverter.
  • Programming Key: Used to enter or exit the parameter setting menu.
  • Data Confirmation Key: Used to confirm the current parameter settings or enter the next menu level.
  • Shift Key: Used to select different digits or functions during parameter setting.
  • Run Key: Used to start the inverter.
  • Stop/Reset Key: Used to stop the inverter or reset fault alarms.
YS510 physical picture

II. Restoring Factory Default Settings

In certain situations, users may need to restore the inverter’s parameters to their factory settings. This can be achieved through the following steps:

  1. Enter the Parameter Setting Menu: Press the programming key to enter the parameter setting menu.
  2. Select Function Code F0.17: Use the shift key to select function code F0.17 (function parameter restore).
  3. Set the Parameter Value to 1: Enter the setting interface for function code F0.17 using the data confirmation key, set the parameter value to 1, and then confirm with the data confirmation key.
  4. Restore Factory Defaults: The inverter will automatically restore all parameters to their factory settings and display the “End” message, indicating that the restoration is complete.

III. Setting and Removing Passwords

To protect parameters from unauthorized modification, the Yushu Inverter YS510 series provides password protection. Users can set and remove passwords through the following steps:

Setting a Password

  1. Enter the Parameter Setting Menu: Press the programming key to enter the parameter setting menu.
  2. Select Function Code F7.00: Use the shift key to select function code F7.00 (user password).
  3. Enter the Password Value: Enter the desired password value (0~65535) in the setting interface for function code F7.00 using the data confirmation key, and then confirm.

Removing a Password

  1. Enter the Parameter Setting Menu: Press the programming key to enter the parameter setting menu.
  2. Select Function Code F7.00: Use the shift key to select function code F7.00 (user password).
  3. Set the Password Value to 0: Enter the setting interface for function code F7.00 using the data confirmation key, set the password value to 0, and then confirm. The password protection function will be disabled.

IV. Setting Parameter Access Restrictions

In addition to password protection, the Yushu Inverter YS510 series also provides parameter access restriction functions, allowing users to restrict access to specific function codes. This can be achieved through the following steps:

  1. Enter the Parameter Setting Menu: Press the programming key to enter the parameter setting menu.
  2. Select the Function Code Requiring Access Restriction: Use the shift key to select the function code requiring access restriction.
  3. Set Access Restriction: Enter the setting interface for the function code using the data confirmation key and set the access restriction to “not changeable” as needed (specific setting methods please refer to the inverter manual).

V. Copying Parameters to Another Inverter for Use

In certain situations, users may need to copy the parameters of one inverter to another for use. This can be achieved through the following steps:

  1. Use the Communication Interface: Ensure that both inverters support the Modbus communication protocol and connect them using a communication cable.
  2. Read Source Inverter Parameters: Use the upper computer software or programmer to read all parameters of the source inverter.
  3. Write to Target Inverter: Write the read parameters to the target inverter. Please note that before writing the parameters, ensure that the model and hardware configuration of the target inverter are the same as or compatible with the source inverter.

VI. External Terminal Forward/Reverse Control and External Potentiometer Speed Regulation

The Yushu Inverter YS510 series supports forward/reverse control and external potentiometer speed regulation through external terminals. The following are the specific wiring and parameter setting methods:

External Terminal Forward/Reverse Control

  1. Wiring:
    • Connect the external forward control signal to the FWD terminal of the inverter.
    • Connect the external reverse control signal to the REV terminal of the inverter.
    • Ensure that the common terminal COM is correctly wired.
  2. Parameter Setting:
    • Enter the parameter setting menu, select function code F5.06 (FWD terminal function selection), and set it to “forward operation” (usually 1).
    • Select function code F5.07 (REV terminal function selection), and set it to “reverse operation” (usually 2).
    • Ensure that function code F0.02 (run command channel) is set to “terminal command channel” (usually 1).

External Potentiometer Speed Regulation

  1. Wiring:
    • Connect the output terminal of the external potentiometer to the analog input terminal VCI (or CCI, depending on the output type of the potentiometer) of the inverter.
    • Ensure that the common terminal is correctly wired.
  2. Parameter Setting:
    • Enter the parameter setting menu, select function code F0.03 (main frequency source X selection), and set it to “analog VCI setting” (or “analog CCI setting”, depending on the output type of the potentiometer).
    • Adjust parameters such as function code F5.11 (VCI lower limit), F5.12 (VCI lower limit corresponding setting), F5.13 (VCI upper limit), and F5.14 (VCI upper limit corresponding setting) as needed to match the output range of the potentiometer.

评论 2626 条评论待审

YS510标准配线图

VII. Fault Codes and Their Solutions

The Yushu Inverter YS510 series provides a wealth of fault codes to help users quickly locate and resolve fault issues. The following are some common fault codes, their meanings, and solutions:

  • E-01: Acceleration Overcurrent
    • Meaning: Overcurrent occurred during the acceleration process of the inverter.
    • Solution: Check if the motor is overloaded, if the grid voltage is too low, if the inverter power is too small, etc., and appropriately increase the acceleration time.
  • E-02: Deceleration Overcurrent
    • Meaning: Overcurrent occurred during the deceleration process of the inverter.
    • Solution: Check if the load inertia torque is too large, if the inverter power is too small, etc., and appropriately increase the deceleration time or add an appropriate energy dissipation brake component.
  • E-04: Acceleration Overvoltage
    • Meaning: Overvoltage occurred during the acceleration process of the inverter.
    • Solution: Check if the input power supply is abnormal, if stopping and restarting are avoided, etc.
  • E-07: Rectifier Module Overheat
    • Meaning: The rectifier module of the inverter is overheated.
    • Solution: Check if the inverter has an instantaneous overcurrent, if there is a phase-to-phase or ground short circuit in the output three-phase, if the air duct is blocked or the fan is damaged, etc., and take corresponding measures to resolve the issue.
  • E-10: Motor Overload
    • Meaning: The motor is overloaded.
    • Solution: Check if the grid voltage is too low, if the motor rated current setting is correct, if the motor is jammed or the load suddenly changes too much, etc., and reset the motor rated current or check the load condition.
  • E-15: Communication Fault
    • Meaning: A communication fault occurred between the inverter and the upper computer.
    • Solution: Check if the baud rate setting is appropriate, if the communication interface wiring is correct, etc., and reset using the STOP/RST key or seek service.

By thoroughly reading and understanding the Yushu Inverter YS510 series user manual, users can better master the operation methods and fault resolution techniques of the inverter, ensuring its normal operation and efficient use.

Posted on Leave a comment

DARING Inverter DR300A Manual User Guide

I. Introduction to the Operation Panel Functions and Parameter Management

1.1 Introduction to the Operation Panel Functions

The DARING Inverter DR300A features a simple and intuitive operation panel with powerful functions. The panel is equipped with an LED display that shows the inverter’s working status, parameter settings, and fault information. The main function keys include the Run key, Stop/Reset key, Confirm key, Cancel key, Increment/Decrement key, Shift key, and Multi-function key.

  • Run Key: Press this key to start the inverter.
  • Stop/Reset Key: Press this key to stop the inverter during operation or to reset faults.
  • Confirm Key: Used to confirm parameter settings or function selections.
  • Cancel Key: Used to cancel the current operation or return to the previous menu.
  • Increment/Decrement Key: Used to adjust parameter values or select menu items.
  • Shift Key: Used to switch display contents or adjust the decimal point position of parameter values.
  • Multi-function Key: Through settings, it can realize functions such as jog operation, positive/negative input switching, function code display switching, etc.
DR300A physical picture

1.2 Copying Parameters to Another Inverter

To quickly copy parameters, the DR300A inverter provides parameter upload and download functions. The specific operation steps are as follows:

  1. Parameter Upload: Upload the parameters from the source inverter to the operation panel. First, ensure that the source inverter is properly connected to the operation panel. Enter the parameter copy mode, select the “Parameter Upload” function, and follow the prompts to complete the upload.
  2. Parameter Download: Download the parameters from the operation panel to the target inverter. Connect the target inverter to the operation panel, enter the parameter copy mode, select the “Parameter Download (with Motor Parameters)” function, and follow the prompts to complete the download.

1.3 Restoring Factory Default Settings

When it is necessary to restore the inverter parameters to their factory default values, follow these steps:

  1. Enter the parameter settings menu.
  2. Locate the “Restore Factory Defaults” function code (F0.28).
  3. Use the Increment/Decrement keys to select “Parameter Recovery Mode 1” or “Parameter Recovery Mode 2” (depending on whether to retain analog input/output offset parameters).
  4. Press the Confirm key to execute the restoration.

1.4 Setting Parameter Access Restrictions

To prevent misoperations or unauthorized access to inverter parameters, the DR300A provides a parameter protection function. By setting function code F0.01, you can choose the parameter modification permissions and initialization levels:

  • 0: Both keyboard and communication port can modify parameters.
  • 1: Only the keyboard can modify parameters.
  • 2: Only the communication port can modify parameters.
  • 3: Neither the keyboard nor the communication port can modify parameters.

Select the appropriate parameter protection level based on actual needs to ensure the security and stability of the inverter parameters.

II. External Terminal Control and Speed Regulation

2.1 External Terminal Forward/Reverse Control

The DR300A inverter supports forward/reverse control of the motor through external terminals. The specific wiring and parameter settings are as follows:

  • Wiring: Connect the forward control terminal (e.g., X1) to the forward control signal source, and connect the reverse control terminal (e.g., X2) to the reverse control signal source. Ensure that the common terminal (e.g., COM) is correctly wired.
  • Parameter Settings:
    • Enter function code F0.05 and select “External Terminal” as the operation command source.
    • Enter function code group F2 and set the functions of multifunction input terminals X1 and X2 to “Forward” and “Reverse,” respectively.

2.2 External Potentiometer Speed Regulation

The DR300A inverter also supports motor speed regulation through an external potentiometer. The specific wiring and parameter settings are as follows:

  • Wiring: Connect the output terminal of the external potentiometer to the analog input terminal of the inverter (e.g., AI0), and ensure that the power supply and grounding of the potentiometer are correctly wired.
  • Parameter Settings:
    • Enter function code F0.08 and select “AI0 (Keyboard Potentiometer)” as the main speed setting source.
    • Adjust the analog input filter time (e.g., F2.11) as needed to improve the smoothness and stability of speed regulation.
DR300A standard wiring diagram

III. Fault Codes and Troubleshooting

3.1 Fault Codes and Meanings

During operation, the DARING Inverter DR300A may encounter various faults, and the corresponding fault codes will be displayed on the screen. Here are some common fault codes and their meanings:

  • Err.01: Inverter unit protection. Possible causes include short circuit in the inverter output circuit, excessive motor and inverter wiring length, overheated module, etc.
  • Err.02: Acceleration overcurrent. Possible causes include grounding or short circuit in the inverter output circuit, vector control without parameter tuning, too short acceleration time, etc.
  • Err.03: Constant speed overcurrent. Possible causes include short circuit or leakage current in the inverter output circuit, vector control without parameter tuning, sudden load increase during operation, etc.
  • Err.05: Acceleration overvoltage. Possible causes include high input voltage, external force dragging the motor during acceleration, too short acceleration time, etc.
  • Err.10: Overheated module. Possible causes include high ambient temperature, blocked airflow, damaged fan, etc.

3.2 Troubleshooting Methods

For the above fault codes, the following troubleshooting methods can be adopted:

  • Err.01: Check and eliminate peripheral faults, such as motor wiring and output circuits; check for blocked airflow and fan operation; if the problem persists, seek technical support.
  • Err.02/Err.03: Check and eliminate peripheral faults; perform motor parameter tuning; increase acceleration/deceleration time; if the load fluctuates greatly, consider selecting an inverter with a higher power rating.
  • Err.05: Adjust the input voltage to the normal range; eliminate external force dragging or install braking resistors; increase acceleration time.
  • Err.10: Reduce ambient temperature; clean airflow paths; replace damaged fans or thermistors.

When troubleshooting, always follow safety operating procedures to ensure personal and equipment safety. If the fault cannot be resolved independently, promptly contact a professional technician for repair.

By thoroughly understanding the DARING Inverter DR300A manual, users can better grasp the operation panel functions, parameter management methods, external terminal control and speed regulation settings, as well as fault codes and troubleshooting methods, providing a strong guarantee for the safe and stable operation of the inverter.

Posted on Leave a comment

User Guide for Huayuan Z230 Series Inverter

The Huayuan Z230 series is a high-performance inverter designed specifically for electric hoists, widely used in lifting, traversing, and slewing control of small lifting equipment. This article provides a detailed introduction to the operation panel functions, parameter settings, external control implementation, and fault handling of the Z230 series inverter, helping users better understand and use the device.


Z230 physical image

I. Introduction to the Operation Panel

1. Overview of the Operation Panel

The operation panel of the Huayuan Z230 series inverter integrates a display screen, indicator lights, and multifunctional buttons. Users can perform parameter settings, operation control, and fault diagnosis through the panel. The main functions are as follows:

  • Display Screen: Used to display output frequency, current, parameter settings, and fault codes.
  • Indicator Lights: Includes power indicator (Power) and inverter status indicator (Status), which lights up during operation and turns off when stopped.
  • Multifunctional Keys: Includes programming key (PRG), confirmation key (ENT), shift key (↑↓), run key (RUN), and stop/reset key (STOP), etc.

2. How to Restore Factory Parameters

When the inverter malfunctions or needs to be reconfigured, the factory parameters can be restored. The specific operations are as follows:

  1. Enter the parameter setting interface and find the function code P00.26.
  2. Set P00.26 = 1 to restore factory parameters (excluding motor parameters).
  3. Set P00.26 = 2 to restore factory parameters (including motor parameters).

3. How to Set a Password

To prevent unauthorized personnel from operating the inverter, a password can be set for protection. The specific steps are as follows:

  1. Enter the parameter setting interface and find the function code P07.11.
  2. Set P07.11 to a value between 0 and 65535, which will be the password.
  3. After setting, the password must be entered each time the parameter setting interface is accessed.

4. Motor Parameter Self-Learning

Motor parameter self-learning is a key step to ensure the matching between the inverter and the motor. The specific operations are as follows:

  1. Set the function code P00.25 = 3 to perform static complete tuning.
  2. Press the run key, and the inverter will automatically start motor parameter self-learning, with the display showing “TUNE”.
  3. During the self-learning process, the motor will emit a howling sound and vibrate, which is normal.
  4. After the self-learning is completed, the display will exit the “TUNE” state, and the parameter tuning is completed.

II. Implementation of External Control

1. External Terminal Forward and Reverse Control

The Huayuan Z230 series inverter supports forward and reverse control through external terminals. The specific wiring and parameter settings are as follows:

Wiring:

  • DI1 Terminal: Forward running command.
  • DI2 Terminal: Reverse running command.

Parameter Settings:

  1. Set P00.01 = 1 to select the terminal command channel.
  2. Set P05.00 = 1 to select the function of DI1 terminal as forward running.
  3. Set P05.01 = 2 to select the function of DI2 terminal as reverse running.

2. External Terminal Multi-Speed Control

Multi-speed control can be achieved through external terminals. The specific wiring and parameter settings are as follows:

Wiring:

  • DI3 Terminal: Multi-command terminal 1.
  • DI4 Terminal: Multi-command terminal 2.

Parameter Settings:

  1. Set P00.02 = 4 to select the multi-command mode.
  2. Set P05.02 = 12 to select the function of DI3 terminal as multi-command terminal 1.
  3. Set P05.03 = 13 to select the function of DI4 terminal as multi-command terminal 2.
  4. Set P11.00 and P11.01 to different speed values, corresponding to the speeds of the multi-commands.

3. Use of Brake and Braking Modules

The brake and braking modules are important functions of the inverter, used to enhance the safety and stability of the equipment.

Brake Module Parameter Settings:

  1. Set P06.00 = 39 to set the inverter function as brake output.
  2. Set P19.00 = 1 to enable the brake output function.
  3. Set P19.01 = 50 for the brake release current threshold.
  4. Set P19.02 = 10 for the brake application current threshold.
  5. Set P19.03 = 1.00 for the brake release frequency threshold.
  6. Set P19.04 = 2.00 for the brake application frequency threshold.

Braking Module Parameter Settings:

  1. Set P09.15 = 1 to enable energy-consuming braking.
  2. Set P09.16 = 160 for the energy-consuming braking voltage point.
  3. Set P09.17 = 100 for the energy-consuming braking usage rate.

Z230 standard wiring diagram

III. Fault Codes and Handling Methods

The Huayuan Z230 series inverter may encounter various faults during operation. Users can quickly locate problems through the fault codes displayed on the screen. The following are common fault codes and handling methods:

1. Overvoltage During Deceleration

  • Causes: Input voltage is too high, external force drags the motor during deceleration, deceleration time is too short, or no braking unit is installed.
  • Handling: Adjust the voltage to the normal range, increase the deceleration time, and install the braking unit and braking resistor.

2. Undervoltage

  • Causes: Momentary power outage, low input voltage of the inverter, or abnormal rectifier bridge.
  • Handling: Reset the fault, adjust the voltage to the normal range, and seek technical support.

3. Inverter Overload

  • Causes: Excessive load, motor stalling, or undersized inverter selection.
  • Handling: Reduce the load, check the motor and mechanical conditions, and select a larger capacity inverter.

4. Module Temperature Abnormality

  • Causes: Excessively high or low ambient temperature, blocked air duct, fan failure, or damaged thermistor.
  • Handling: Lower or raise the ambient temperature, clean the air duct, replace the fan or thermistor.

5. Motor Tuning Abnormality

  • Causes: Motor parameters not set according to the nameplate or tuning process timeout.
  • Handling: Correctly set the parameters according to the motor nameplate and check the wiring from the inverter to the motor.

IV. Conclusion

The Huayuan Z230 series inverter is a powerful and easy-to-operate inverter specifically designed for electric hoists. By reasonably setting parameters, correctly wiring, and promptly handling faults, users can fully utilize its performance, enhancing the stability and safety of the equipment. This article provides a detailed introduction to the operation panel functions, external control implementation methods, and fault handling of the inverter, aiming to provide valuable references for users. If any difficulties are encountered, it is recommended to contact the manufacturer’s technical support for professional assistance.

Posted on Leave a comment

V&T Inverter V5-H Manual Usage Guide

I. Introduction to the Operation Panel Functions and Parameter Management

1.1 Introduction to the Operation Panel Functions

The V&T Inverter V5-H from Blue Ocean Huateng boasts an intuitive and easy-to-use operation panel that offers a wealth of control functions. The operation panel comes in two types: button-type and joystick-type, allowing users to choose based on their actual needs. The indicator lights on the operation panel provide a clear display of the current status of the inverter, such as frequency, current, voltage, and other parameters. Through keys like PRG (program key), ESC (exit key), and the rotary knob (+, -), users can conveniently access various menus for data setting and viewing.

Front image of V5-H

1.2 Parameter Copy

The parameter copy function allows users to quickly replicate the parameters of one inverter to another, significantly improving setup efficiency. The specific operation steps are as follows:

  1. Connect the Operation Panel: Use the operation panel cable to connect the source inverter and the target inverter.
  2. Upload Parameters: On the source inverter, enter the operation panel menu, select the parameter upload function, and upload the parameters to the operation panel.
  3. Download Parameters: Connect the operation panel to the target inverter, select the parameter download function, and download the parameters from the operation panel to the target inverter.

1.3 Restore Parameter Initialization Settings

Restoring the parameter initialization settings can revert all parameters of the inverter to their factory defaults, making it convenient for users to reconfigure the parameters. The specific operation steps are as follows:

  1. Enter the operation panel menu and locate the “Function Code Protection” parameter (P0.01).
  2. Set P0.01 to “2”, then press the confirm key, and the inverter will restore all parameters except motor group parameters (P9 group) to their factory settings.

1.4 Set and Clear Passwords

To protect the inverter parameters from unauthorized modifications, users can set a password. The specific operation steps are as follows:

  1. Set Password: Enter the operation panel menu, locate the “User Password” parameter (P0.00), and set the same password twice consecutively to successfully set the password.
  2. Verify Password: Enter P0.00 again, input the correct password, and you will be able to access the parameter area protected by the password.
  3. Clear Password: After verifying the password, set P0.00 to “0000” to clear the password.

1.5 Set Parameter Access Restrictions

By setting parameter access restrictions, users can control the operation permissions of different users on the inverter. The specific operation steps are as follows:

  1. Enter the operation panel menu and locate the “Function Code Protection” parameter (P0.01).
  2. Set P0.01 to the desired value according to your needs, such as “1” to prohibit changes to all parameters, or “3” to restore all parameters except motor group parameters to their factory settings.

II. External Control and Speed Adjustment Settings

2.1 External Terminal Forward and Reverse Control

The V&T Inverter V5-H supports forward and reverse control of the motor through external terminals. Users need to connect the FWD (forward) and REV (reverse) terminals to the control signal source, such as a PLC or button switch. At the same time, corresponding parameters need to be set in the inverter:

  1. Enter the operation panel menu and locate the “Run Command Given Mode” parameter (P0.06).
  2. Set P0.06 to “1”, indicating that the run command is given through terminals.

2.2 External Potentiometer Given Frequency Speed Regulation

By connecting an external potentiometer to the AI1 (Analog Input 1) terminal of the inverter, users can achieve speed control of the motor frequency. The specific steps are as follows:

  1. Wiring: Connect the output terminal of the external potentiometer to the AI1 terminal of the inverter, and connect the COM terminal of AI1 to the common terminal of the inverter.
  2. Parameter Setting:
    • Enter the operation panel menu and locate the “Open-Loop Main Given Mode” parameter (P0.04).
    • Set P0.04 to “1”, indicating that the frequency is given by AI1 analog input.
    • Set the AI1 analog input curve (P6.00) as needed to achieve linear or nonlinear speed regulation.
V5-H standard wiring diagram

III. Fault Codes and Solutions

The V&T Inverter V5-H features a comprehensive fault diagnosis function that can display fault codes and fault information in real-time, helping users quickly locate problems. The following are some common fault codes, their meanings, and solutions:

3.1 E.oc1: Overcurrent Protection During Acceleration

Meaning: The inverter detects an overcurrent phenomenon during acceleration.

Solution:

  • Check if the grid voltage is too low.
  • Extend the acceleration time to reduce load mutation.
  • Check if the motor parameter settings are correct.
  • Consider replacing with a higher-power inverter.

3.2 E.oc2: Overcurrent Protection During Deceleration

Meaning: The inverter detects an overcurrent phenomenon during deceleration.

Solution:

  • Extend the deceleration time.
  • Use a suitable energy dissipation braking component.
  • Check the motor parameter settings.

3.3 E.AUt: Self-Tuning Fault

Meaning: The inverter encounters a fault during self-tuning.

Solution:

  • Ensure that the motor is in a stationary state before performing self-tuning.
  • Check if the motor wires are properly connected and within the specified length.
  • Reset the P9 group motor parameters according to the motor nameplate.

3.4 E.oL2: Motor Overload Protection

Meaning: The inverter detects motor overload.

Solution:

  • Check if the load is too heavy or if the motor is jammed.
  • Adjust the inverter overload protection parameters (P9.16, P9.18).
  • Check if the motor is overheating, and replace it if necessary.

IV. Conclusion

The V&T Inverter V5-H manual provides users with detailed operation guides and troubleshooting methods. By mastering the functions of the operation panel and parameter setting methods, users can conveniently control and manage the inverter. At the same time, understanding common fault codes and their solutions can help users quickly locate and resolve issues, ensuring the stable operation of the inverter. In practical applications, users should also make flexible adjustments and optimizations based on specific needs and site conditions.