Posted on Leave a comment

ABB DRIVE ACS510 Constant Pressure Water Supply Control One to Two Scheme, Wiring and Parameter Settings

Take advantage of ABB’s ACS510 VSD for seamless multi-pump pressure control. With its advanced PFC application macro, you can effortlessly manage up to 7 pumps while ensuring consistent pressure regulation. This powerful feature eliminates the need for a separate constant pressure water supply controller, simplifying your system design. By implementing the SPFC macro, you can enjoy the added benefit of reducing stress on your pumps and power grid through gentle soft-start sequences. Consider SPFC as an enhanced version of PFC, providing superior control and reliability for your critical applications.

According to your description, DL6 is used for start commands, DL1 and DL2 for PFC control. SA1, SA2, and SA3 are three-position switches, with the middle position as stop. When manually operating at rated frequency, the switch is set to the right, and when the automatic allow signal is present, the switch is set to the left. The connections at 19, 21 and 22, 24 are connected to the relay terminals below the VFD, corresponding to the normally open contacts of RO1 (Relay 1) and RO2 (Relay 2).

The difference between PFC and SPFC:

In automatic mode with PFC: When SA2 and SA3 are set to the automatic position and the power is turned on, relay 1 on the inverter engages, which causes KM1 to engage and the motor M1 to start operating at variable frequency. If the frequency reaches the start-up frequency +1, the auxiliary motor is engaged, and relay 2 on the inverter engages, causing KM3 to engage and motor M2 to start operating at rated frequency. With PFC in automatic mode, it is possible to switch pumps at regular intervals.

In automatic mode with SPFC: When SA1 and SA2 are set to the automatic position and the power is turned on, relay 1 on the inverter engages, which causes KM1 to engage and the motor M1 to start operating at variable frequency. When the frequency reaches the start-up frequency +1, relay 1 is first disengaged and then relay 2 is engaged, causing KM4 to engage and motor M2 to start operating at variable frequency. Simultaneously, relay 1 re-engages to cause KM2 to engage and motor M1 to operate at rated frequency. With SPFC in automatic mode, it is not possible to switch pumps at regular intervals.

CODE NAME SET VALUE NOTES
9902 APPLIC MACRO 15=SPFC control
1002 EXT2 COMMANDS 6=DI6 VSD startup command
1102 EXT1/EXT2 SEL 7=EXT2
1106 REF2 SELECT 19=PID1OUT After SPFC takes effect, 1106 defaults to 19 and does not require adjustment
1401 RELAY OUTPUT 1 31=PFC control
1402 RELAY OUTPUT 2 31=PFC control
1403 RELAY OUTPUT 3 4=FAULT
1601 RUN ENABLE 6=DI6
2008 MAXIMUM FREQ 50HZ
2202 ACCELER TIME 1 15S Set according to actual situation
2203 DECELER TIME 1 15S Set according to actual situation
3104 AR OVERCURRENT 1=ENABLE
4001 GAIN(PID) 1.5-2
4002 INTEGRATION TIME(PID) 2.5
4009 100% VALUE ” Defines (together with 4008) the scaling Set according to actual situation
applied to the PID controller’s actual values”
4010 SET POINT SEL 0=keypad – Control panel provides reference.
4016 ACT1 INPUT 1=AI1 is ACT1(Remote transmission meter);2=AI2 is ACT1(Pressure sensor)
4022 SLEEP SELECTION 7=INTERNAL
4023 PID SLEEP LEVEL 38HZ Set according to actual situation
4024 PID SLEEP DELAY 30S
4025 WAKE-UP DEV 2.5
8118 AUTOCHNG INTERV 1h
8119 AUTOCHNG LEVEL 85%
8120 INTERLOCKS 1=DI1 Enables the Interlock function
8123 PFC ENABLE 1 = ACTIVE – Enables PFC control
8127 MOTORS 2 After SPFC takes effect, it defaults to 2, and there is no need to adjust the two pumps

The parameters mentioned in this article use SPFC macros, and PFC is also similar, except that the macro parameter is 7.VSDs such as ACS550 and ACS355 should also be able to achieve constant pressure water supply frequency converter control through similar operations. Please refer to their technical manuals for details, or contact us for guidance

Posted on Leave a comment

Global Ultrasonic Equipment Maintenance Center – Longi Electromechanical Company

Professional Ultrasonic Equipment Repair Services

Longi Electromechanical Company specializes in the repair of various types of ultrasonic equipment using advanced AI methods and a dedicated technical team. We offer component-level maintenance and can resolve common issues on the same day, minimizing downtime and maximizing customer productivity. With a vast experience of repairing over 2000 ultrasonic devices, we have honed our skills to handle a wide range of brands and models.

Produktion mit CNC-Maschine, Bohren und Schweißen und Konstruktionszeichnung im Industriebetrieb.

Contact Us:
Phone/WhatsApp: +8618028667265

Key Services and Features:

  • Comprehensive Repair Solutions: From plastic hot plate welding machines to ultrasonic flaw detectors, we repair a diverse range of ultrasonic equipment.
  • Brand Expertise: We have experience with numerous brands, including Minghe, Changrong, Swiss RINCO, and many more, ensuring optimal performance restoration.
  • Warranty and Cost-Effectiveness: Repaired equipment comes with a one-year warranty for the same problem point, and our maintenance costs are competitive.
  • Quick Turnaround: We prioritize efficient repairs to get your equipment back in operation as soon as possible.

Types of Ultrasonic Equipment We Repair:

  • Plastic Welding Equipment: Ultrasonic welding machines, hot plate welding machines, multi-head ultrasonic welding machines, and more.
  • Metal Welding Equipment: Ultrasonic metal welding machines, spot welding machines, wire welding machines, and roll welding machines.
  • Automotive Welding Equipment: Door panel welding machines, interior part welding machines, instrument panel welding machines, and more.
  • Specialized Equipment: Ultrasonic flaw detectors, cutting machines, food cutting machines, tool heads, and various other ultrasonic devices.
  • Components and Parts: Ultrasonic vibrating plates, power boards, transducers, generators, and supporting tooling.

Common Faults We Address:

  • Cleaning water surface not vibrating
  • Debonding between vibrator and load
  • Mold head misalignment
  • No display on startup
  • Overload or overcurrent during welding
  • High current during testing
  • Insufficient or excessive welding heat
  • Vibrator leakage waves
  • Unresponsive buttons
  • Travel protection issues
  • Power adjustment problems
  • Insufficient ultrasonic intensity
  • Cracked transducer ceramic
  • Burned-out power tube
  • Voltage stabilization issues
  • Inductor and isolation transformer problems
  • Disconnected vibrator wire

Repair Principles:

  1. Observe, Understand, Act: Begin by inquiring about the issue from frontline staff, checking for voltage fluctuations, and understanding the context before taking action.
  2. Simple Before Complex: Rule out peripheral issues like the environment, electricity, load, raw materials, and molds before diving into more complex repairs.
  3. Address Mechanical Issues First: Visible mechanical problems, such as mold issues, should be addressed before exploring electrical causes.

Trust Longi Electromechanical Company for reliable, efficient, and cost-effective ultrasonic equipment repair services. Contact us today to learn more about our services and how we can help keep your ultrasonic equipment running smoothly.

    Posted on Leave a comment

    Global Instrument Maintenance Center

    Intelligent Precision Instrument Maintenance Base,Professional maintenance of various intelligent instruments and meters, phone/WhatsApp:+8618028667265, Mr. Guo

    Longi Electromechanical specializes in repairing various imported intelligent precision instruments and meters, and has accumulated rich maintenance experience over the years, especially environmental testing instruments, electrical instruments, thermal instruments, acoustic and flow instruments, and electrical instruments. Environmental testing instruments, thermal instruments, acoustic and flow instruments,
    We can quickly repair radio instruments, length instruments, environmental testing equipment, quality inspection instruments, etc.
    Different instruments have different characteristics and functions, and their circuits and structures are also different. Even for the same instrument, if there are different faults, repairing them is still a different solution. Rongji Company has numerous high-end maintenance engineers equipped with artificial intelligence AI detection instruments, which can provide you with multi-dimensional solutions to various tricky instrument problems.

    Over the years, Longi Electromechanical has repaired instruments including but not limited to:

    Spectrum analyzers, network analyzers, integrated test instruments, 3D laser scanners, noise figure testers, receivers, telephone testers, high and low-frequency signal sources, audio and video signal analyzers, constant temperature and humidity chambers, thermal shock chambers, simulated transport vibration tables, mechanical vibration tables, AC grounding impedance safety testers, safety comprehensive analyzers, withstand voltage testers, battery internal resistance testers, high-precision multimeters, precision analyzers, gas and liquid analyzers, metal detectors, LCR digital bridges, oscilloscopes, electronic loads, power meters, power analyzers, multimeters, DC power supplies, AC power supplies, CNC power supplies, variable frequency power supplies, and various communication power supplies.

    We have repaired the following brands:

    Chroma, ITECH, Tonghui, Agilent, Tektronix, Keysight, Fluke, Keithley, Rohde & Schwarz, Lecroy, Anritsu, Rigol, and many more.

    Longi Electromechanical strives to provide comprehensive repair services for a wide range of instruments and equipment, ensuring that our customers’ devices are restored to optimal performance.

    Longi maintenance engineers possess over twenty years of experience in instrument repair. We have multiple engineers who excel in repairing imported precision instruments. The team works together, enabling faster troubleshooting and quick resolution of complex issues while improving the repair rate of instruments.

    Spare parts are fundamental to successful repairs. Many imported instruments and meters require specialized components that cannot be easily replaced with generic market parts. Rongji Electromechanical maintains a long-term stock of electronic components for various instruments, ensuring their availability when needed.

    Documentation and manuals are also crucial tools for ensuring rapid repairs. Accessing these resources allows for quick research and analysis of faults, enabling engineers to quickly identify the repair priorities. Longi Electromechanical has a long history of collecting specifications for various brands and models of instruments, greatly aiding in the repair process.

    The intelligent instruments that have been carefully repaired by us can generally continue to be used for about 5 years. We promise that when the same malfunction occurs again, our repair service will provide a one-year warranty service.

    Posted on Leave a comment

    Global Touch Screen Repair Services: Expert Maintenance for All Your Touch Screen Needs

    Global Touch Screen Repair Services: Expert Maintenance for All Your Touch Screen Needs

    Touch screens have become an integral part of our daily lives, revolutionizing the way we interact with machines in various industries including industrial, commercial, and medical fields. These versatile devices come in different forms such as resistive, capacitive, infrared, and ultrasonic screens, each serving unique purposes. However, due to their frequent use and delicate glass structure, touch screens are prone to damage, particularly to the outer touch surface known as the “touchpad.”

    For over two decades, Rongji Electromechanical Maintenance has been a trusted name in the touch screen repair industry. With extensive experience in handling touch screens across diverse sectors, we specialize in repairing both resistive and capacitive screens used in automobiles and other critical applications. Our expertise ensures that your touch screens are restored to optimal functionality, minimizing downtime and maximizing efficiency.

    The Repair Process: A Step-by-Step Guide

    Disassembly and Inspection:
    We begin by carefully removing the back cover and motherboard screws of the touch screen. This step allows us to access the internal components and assess the extent of the damage.

    Heating and Peeling:
    Our skilled technicians use a hair dryer to gently heat the film adhering to the touch screen. This softens the adhesive, making it easier to peel off the outer layer without causing further damage.

    Touchpad Replacement:
    Once the old touchpad is removed, we replace it with a high-quality touchpad from our inventory. Longi Electromechanical Company has reverse-engineered various touch screen models, ensuring that our replacement parts are fully compatible with the original equipment.

    Reassembly:
    We apply double-sided tape to the touch screen border and securely attach the new touchpad. This ensures a perfect fit and optimal performance.

    Testing and Fine-Tuning:
    With the new touchpad in place, we reinstall the motherboard and LCD, then flip the unit over to test its functionality. Our rigorous testing process ensures that the touch screen operates smoothly and accurately.

    Final Assembly and Quality Check:
    After successful testing, we apply a protective film to the touch screen and reassemble the unit. A final quality check is performed to ensure that the repair meets our high standards.

    Addressing Complex Issues

    In addition to touchpad replacements, we also handle more complex issues such as circuit failures and software problems. Our team uses professional software analysis and hardware processing techniques to diagnose and repair these issues, ensuring that your touch screen is fully restored to its original state.

    Our Repair Services Cover a Wide Range of Brands

    At Rongji Electromechanical Company, we have repaired touch screens from numerous brands including Siemens, Proface, Mitsubishi, Fuji, Panasonic, OMRON, and many more. Our extensive experience and expertise enable us to provide reliable repair services for a wide variety of touch screen models.

    Common Touch Screen Problems We Solve

    • Unresponsive Touch Screen: If your touch screen is visible but cannot be touched or clicked, it may be due to a faulty touch panel. Our experts can replace the panel to restore functionality.
    • No Display: If your touch screen does not display anything and the indicator lights are off, it could be a power supply issue. We can diagnose and repair the problem to get your touch screen back up and running.
    • Black Screen: If your touch screen functions but displays a black screen, it may be due to a burned-out backlight tube. We can replace the tube to restore the display.
    • Distorted Image or Abnormal Colors: Issues with the LCD or connecting cables can cause distorted images or abnormal colors. Our technicians can diagnose and repair these issues to ensure clear and accurate display.
    • Communication Errors: If your touch screen displays a communication error and responds slowly to touch, it may be due to issues with the PLC or other connected devices. We can troubleshoot and repair the connection to ensure smooth communication.

    Choose Rongji Electromechanical Maintenance for reliable and professional touch screen repair services. Contact us today to learn more about our services and how we can help you keep your touch screens in optimal condition.

    Posted on Leave a comment

    Global Servo CNC maintenance center

    Global Servo CNC maintenance center,Professional maintenance of servo CNC systems

    Remember to contact Longi Electromechanical for any issues with servo and CNC systems!

    Servo systems differ from VFDs in that they offer higher precision and typically come with delicate encoders. Servo motors are synchronous motors with magnets inside, and if not handled carefully during disassembly and assembly, their original performance may not be restored. Additionally, different servo drivers cannot be used interchangeably with other servo motors. This means that during the repair of a servo driver, a corresponding servo motor and cable plug are required for proper testing. Similarly, repairing a servo motor also requires a matching servo driver for testing, which can pose challenges for many maintenance personnel.

    As for CNC (Computer Numerical Control) systems, most are embedded industrial computer types with closed control systems. Each manufacturer has its own design ideas, programming methods, wiring, and communication architectures, making them incompatible with one another.

    Longi Electromechanical Company has designed various styles of servo and CNC maintenance test benches to test the working conditions of different CNC systems, servo drivers, or servo motors. When servo systems encounter issues such as no display, phase loss, overvoltage, undervoltage, overcurrent, grounding, overload, module explosion, magnet loss, parameter errors, encoder failures, communication alarms, etc., the corresponding platform can be used to test and diagnose the problem.

    Repair Hotline: +8618028667265 Mr. Guo

    After resolving these issues, the servo system also needs to undergo a simulated load test to avoid problems such as overcurrent under load conditions, even if it performs well under no-load conditions. This ensures that the servo system is fully functional and ready for use in actual applications.

    For the CNC system, it is also necessary to conduct simulated operation before normal delivery to avoid any discrepancy with the on-site parameters. Currently, Rongji Electromechanical possesses hundreds of servo and CNC test benches, which can quickly identify problem areas and promptly resolve issues. With these advanced testing facilities, Longi Electromechanical ensures the smooth operation and reliability of the repaired equipment.

    The Servo and CNC Repair Center established by Longi Company currently has over 20 skilled and experienced maintenance engineers who specialize in providing repair services for different brands and specifications of servo and CNC systems. They implement tailored repair solutions for different maintenance projects, ensuring efficient and high-quality service for customers. By helping customers save valuable production time and reducing their maintenance costs, Rongji truly cares about the urgent needs of its customers and strives for common development and progress together.

    We have repaired the following brands of servo and CNC systems:

    Servo Systems

    • Lenze Servo Systems
    • Siemens Servo Systems
    • Panasonic Servo Systems
    • Eurotherm Servo Systems
    • Yaskawa Servo Systems
    • Fuji Servo Systems
    • Delta Servo Systems
    • Omron Servo Systems
    • Fanuc Servo Systems
    • Moog Servo Systems
    • TECO Servo Systems
    • Norgren Servo Systems
    • SSB Servo Drive Systems
    • Hitachi Servo Systems
    • Toshiba Servo Systems
    • Denso Servo Systems
    • Parvex Servo Systems

    CNC Systems

    • Mitsubishi Servo Systems
    • Sanyo Servo Systems
    • Mitsubishi CNC (MITSUBISHI)
    • Fanuc CNC (FANUC)
    • Siemens CNC (SIEMENS)
    • Brother CNC (BROTHER)
    • Mazak CNC (MAZAK)
    • GSK (Guangzhou Numerical Control)
    • Huazhong Numerical Control
    • Fagor CNC
    • Heidenhain
    • Haas CNC
    • NUM (France)
    • Hurco (USA)
    • KND (Beijing KND Technology Co., Ltd.)
    • Leadshine
    • Syntec
    • Shenyang Machine Tool i5
      *凯恩帝 (KND)

    Note: Some of the brand names mentioned may be trademarks or registered trademarks of their respective owners. The listing here is for informational purposes only and does not imply any affiliation or endorsement by Rongji Electromechanical or any of the mentioned brands.

    Machine Tool Brands

    (1) European and American Machine Tools:

    • Gildemeister
    • Cincinnati
    • Fidia
    • Hardinge
    • Micron
    • Giddings
    • Fadal
    • Hermle
    • Pittler
    • Gleason
    • Thyssen Group
    • Mandelli
    • Sachman
    • Bridgeport
    • Hueller-Hille
    • Starrag
    • Heckert
    • Emag
    • Milltronics
    • Hass
    • Strojimport
    • Spinner
    • Parpas

    (2) Japanese and Korean Machine Tools:

    • Makino
    • Mazak
    • Okuma
    • Nigata
    • SNK
    • Koyo Machinery Industry
    • Hyundai Heavy Industries
    • Daewoo Machine Tool
    • Mori Seiki
    • Mectron

    (3) Taiwanese and Hong Kong Machine Tools:

    • Hardford
    • Yang Iron Machine Tool
    • Leadwell
    • Taichung Precision Machinery
    • Dick Lyons
    • Feeler
    • Chen Ho Iron Works
    • Chi Fa Machinery
    • Hunghsin Precision Machinery
    • Johnford
    • Kaofong Industrial
    • Tong-Tai Machinery
    • OUMA Technology
    • Yeongchin Machinery Industry
    • AWEA
    • Kaoming Precision Machinery
    • Jiate Machinery
    • Leeport (Hong Kong)
    • Protechnic (Hong Kong)

    (4) Chinese Mainland Machine Tools:

    • Guilin Machine Tool
    • Yunnan Machine Tool
    • Beijing No.2 Machine Tool Plant
    • Beijing No.3 Machine Tool Plant
    • Tianjin No.1 Machine Tool Plant
    • Shenyang No.1 Machine Tool Plant
    • Jinan No.1 Machine Tool Plant
    • Qinghai No.1 Machine Tool Plant
    • Changzhou Machine Tool Factory
    • Zongheng International (formerly Nantong Machine Tool)
    • Dahe Machine Tool Plant
    • Baoji Machine Tool Plant
    • Guilin No.2 Machine Tool Plant
    • Wanjia Machine Tool Co., Ltd.
    • Tianjin Delian Machine Tool Service Co., Ltd.

    Note: The list provided above is comprehensive but not exhaustive. Machine tool brands and manufacturers are constantly evolving, and new players may have emerged since the compilation of this list. Always refer to the latest industry updates for the most accurate information.

    Posted on Leave a comment

    Global Variable Frequency Drive (VFD) repair center

    “Longi Electromechanical” has more than 20 years of experience in industrial control maintenance, and is one of the earliest companies engaged in VFD repair. Equipped with artificial intelligence AI maintenance instruments, it specializes in emergency repair of various equipment, with high technical efficiency. It has repaired more than 200,000 units of equipment, including ultrasonic, robot, charging pile, inverter,Variable Frequency Drive (VFD), touch screen, servo, intelligent instrument, industrial control machine, PLC and other products. General problems can be repaired on the same day. LONGI promises you that “if it can’t be repaired, we won’t charge you”. And it provides lifelong maintenance service and free technical consultation for inspection! For urgent repair consultation, please call the contact number or add WHATSAPP maintenance hotline: +8618028667265 Mr. Guo

    From European and American brands to Japanese, Korean, and Taiwanese ones, until various domestic brands, we have repaired countless models and specifications of VFDs. In the process of serving our customers, we have continuously learned and accumulated maintenance experience to enhance our skills. We specialize not only in repairing VFDs but also in summarizing various maintenance experiences, elevating them to a theoretical level. We have published the book “VFD Maintenance Technology” and offered VFD maintenance training, thereby promoting the development of the VFD maintenance industry. Longi Electromechanical Company has repaired VFDs from the following brands:

    European and American Brands

    ABB drives, SEW drives, LUST VFD, LENZE VSD, Schneider drives, CT drives, KEB VSD, Siemens drives, Eurotherm VFD, G.E. VFD, VACON VSD, Danfoss VFD, SIEI VFD, AB VFD, Emerson VFD, ROBICON VFD, Ansaldo VFD, Bosch Rexroth VSD, etc.

    Japanese Brands:

    Fuji INVERTER, Mitsubishi INVERTER, Yaskawa INVERTER, Omron INVERTER, Panasonic INVERTER, Toshiba INVERTER, Sumner INVERTER, Tooka INVERTER, Higashikawa INVERTER, Sanken INVERTER, Kasia INVERTER, Toyo INVERTER, Hitachi INVERTER, Meidensha INVERTER, etc.

    Taiwanese Brands:

    Oulin INVERTER, Delta INVERTER, Taian INVERTER, Teco INVERTER, Powtran INVERTER, Dongling INVERTER, Lijia INVERTER, Ningmao INVERTER, Sanji INVERTER, Hongquan INVERTER, Dongli INVERTER, Kaichi INVERTER, Shenghua INVERTER, Adlee INVERTER, Shihlin INVERTER, Teco INVERTER, Sanchuan INVERTER, Dongweiting INVERTER, Fuhua INVERTER, Taian INVERTER (note: Taian is repeated, possibly a mistake in the original list), Longxing INVERTER, Jiudesongyi INVERTER, Tend INVERTER, Chuangjie INVERTER, etc.

    Chinese Mainland brands:

    Senlan Inverter, Jialing Inverter, Yineng Inverter, Hailipu Inverter, Haili Inverter, Lebang Inverter, Xinnuo Inverter, Kemron Inverter, Alpha Inverter, Rifeng Inverter, Shidai Inverter, Bost Inverter, Gaobang Inverter, Kaituo Inverter, Sinus Inverter, Sepaxin Inverter, Huifeng Inverter, Saipu Inverter, Weier Inverter, Huawei Inverter, Ansheng Inverter, Anbangxin Inverter, Jiaxin Inverter, Ripu Inverter, Chint Inverter, Delixi Inverter, Sifang Inverter, Geli Te Inverter, Kangwo Inverter, Jina Inverter, Richuan Inverter, Weikeda Inverter, Oura Inverter, Sanjing Inverter, Jintian Inverter, Xilin Inverter, Delixi Inverter, Yingweiteng Inverter, Chunri Inverter, Xinjie, Kemron-Bong Inverter, Nihonye Inverter, Edison Inverter

    Other brands:
    Migao VFD, Rongqi VFD, Kaiqi VFD, Shiyunjie VFD, Huichuan VFD, Yuzhang VFD, Tianchong VFD, Rongshang Tongda VFD, LG VFD, Hyundai VFD, Daewoo VFD, Samsung VFD, etc.

    Longi Electromechanical Company specializes in the maintenance of VFDs and strictly requires its engineers to followlow standard operating procedures. Upon receiving a unit, the engineers carefully inspect its exterior and clarify any fault conditions with the customer before beginning work. Any removed circuit boards are cleaned using ultrasonic cleaning equipment. Repaired circuit boards are coated with high-temperature and high-pressure-resistant insulating paint, dried in a drying machine, and then reinstalled in the VFD, with measures taken to prevent corrosion and interference.

    The repaired VFD will undergo a simulated operation with load using a heavy-load test bench to avoid any potential issues that may arise under actual load conditions on site.

    When it comes to VFD maintenance, most cases are related to the equipment on site. Sometimes a standalone unit may have been repaired, but it doesn’t work properly when installed on site. In some cases, the problem lies with the system rather than the VFD itself. For such issues, if the customer requests on-site service, we will do our utmost to resolve the problem for them. If the location is far away, such as in another province, we can use tools like video conferencing and phone calls to allow our engineers to remotely diagnose and resolve the on-site issues for the customer.

    Posted on Leave a comment

    Debugging of ABB VFD for ACS800 Enhancement

    A. Motor Auto-tuning (Quick Debugging Steps)

    1. Power On: Ensure the system is powered on.
    2. Input Initialization:
      • Press PAR to select the language. Set 99.1 to ENGLISH.
      • Choose the application macro. Set 99.2 to CRANE.
      • Determine if parameters should be reset to factory defaults. Set 99.3 to YES or NO.
      • Select the motor control mode in 99.4: DTC (Direct Torque Control) or SCALAR.
      • Enter the rated voltage in 99.5 V.
      • Input the rated current in 99.6 A.
      • Specify the rated frequency in 99.7 HZ.
      • Set the motor’s rated speed in 99.8 RPM.
      • Define the motor’s rated power in 99.9 KW.
    3. Motor Identification Run:
      • Proceed to motor identification by selecting 99.10.
      • Generally, choose ID MAGN (the motor won’t rotate).
      • For STANDARD mode (motor rotates), the motor must be disconnected from the equipment.
      • In REDUCED identification mode (motor rotates), the motor remains connected.
      • After selecting the identification mode, a “WARNING” signal may appear.
      • Press the start button to begin motor identification. This process can be stopped at any time using the stop button.
      • Once the motor identification is complete, press RESET to enter actual signal display mode.
    4. Motor Direction Check: Verify the motor’s rotation direction using the control panel.
    5. Input Speed Limits and Acceleration/Deceleration Times: Enter the necessary parameters.

    B. Parameter Configuration – Optimized for Google SEO

    1. Set parameter 10.1 to DI1 for brake acknowledgment digital input.
    2. Leave parameter 10.2 as NOT SEL for zero-position digital input.
    3. Parameter 10.3 remains NOT SEL for deceleration digital input.
    4. Parameter 10.4 is NOT SEL for rapid stop digital input.
    5. Parameter 10.5 is NOT SEL for power-on acknowledgment digital input.
    6. Keep parameter 10.6 as NOT SEL for synchronization request digital input.
    7. Set parameter 10.7 to EXT DI1.1 for chopper fault digital input.
    8. Configure parameter 10.8 to DI2 for the second speed level digital input.
    9. Set parameter 10.9 to DI5 for the third speed level digital input.
    10. Parameter 10.10 is set to DI6 for the fourth speed level digital input.
    11. Parameters 10.11 to 10.15 and 10.17, 10.18 remain NOT SEL.
    12. Set parameter 10.16 to DI-1L for fault reset digital input.
    13. Parameter group 13 deals with analog input signals. No need for modification.
    14. Set parameter 14.1 to BRAKE LIFT for relay output 1.
    15. Configure parameter 14.2 to WATCHDOG-N for relay output 2.
    16. Parameter 14.3 is set for relay output 3 to indicate a FAULT-N signal. When a fault occurs, the relay releases, and during power-on, the fault relay engages.
    17. Parameter group 15 covers analog output signals. No modifications required.
    18. Parameter group 16 deals with password settings. No need to change.
    19. Parameter group 20 defines limit values:
      • Parameter 20.1: Minimum speed for the operating range.
      • Parameter 20.2: Maximum speed for the operating range.
      • Parameter 20.3: Maximum output current.
      • Parameter 20.4: Maximum positive output torque.
      • Parameter 20.5: Maximum negative output torque.
      • Parameter 20.6: DC overvoltage controller.
      • Parameter 20.7: DC undervoltage controller.
      • Parameter 20.8: Minimum frequency for the operating range.
      • Parameter 20.9: Maximum frequency for the operating range.
      • Parameters 20.10 to 20.13 relate to analog inputs but are not detailed here.
    20. Parameter 21.1 is not to be changed.
    21. Set parameter 21.2 for the field excitation time, approximately 4 times the motor’s rated KW (in milliseconds).
    22. Parameter group 23 covers speed control gains, integral and derivative times, motor slip, etc. Generally left unchanged.
    23. Parameter group 24 deals with torque build-up time. Typically not modified.
    24. Parameter group 26 allows compensation voltage setting for the motor (only in SCALAR mode).
    25. Parameter group 27 configures the braking chopper:
      • Set parameter 27.1 to ON for brake chopper control.
      • Parameter 27.2 is set to FAULT to activate overload protection for the braking resistor.
      • Enter the actual value for the braking resistor in parameter 27.3.
      • Set the time constant for the braking resistor in parameter 27.4 to 300S.
      • Define the maximum continuous braking power for the resistor in parameter 27.5.
      • Set the control mode for the brake chopper control to AS GENERATOR in parameter 27.6.
    26. Parameter group 28 deals with motor modeling. Typically not modified.
    27. Parameter group 30 covers fault functions. Generally left unchanged.
    28. Parameter group 50 configures encoder values:
      • Set the number of encoder pulses in parameter 50.1.
      • Define the calculation method for encoder pulses in parameter 50.2.
      • Parameter 50.3 is set to FAULT for encoder fault action.
      • Set the encoder monitoring delay time in parameter 50.4 (avoid setting to 0).
      • Parameter 50.5 determines the encoder feedback usage, typically set to TRUE.
    29. Parameter group 60 handles the switch between local and external operation.
    30. Parameter groups 61 and 62 deal with speed monitoring. Generally not modified.
    31. Parameter group 63 covers torque monitoring. Typically left unchanged.
    32. Parameter group 64 is for crane mode:
      • Set parameter 64.1 to TRUE for STAND ALONE mode.
      • Parameter 64.10 is configured to STEPJOYST or STEPRADIO.
      • Parameters 64.13 to 64.16 define the speeds for the four speed levels (as a percentage of rated speed).
    33. Parameter group 65 deals with motor field current settings. Generally not modified.
    34. Parameter group 66 covers torque verification, typically left unchanged.
    35. Parameter group 67 configures brake control:
      • Set the brake application time to 0.5S in parameter 67.1.
      • Define the brake fault delay as 0.5S in parameter 67.2.
      • Parameters 67.3 to 67.10 are not detailed but can be set as needed.
    36. Parameter group 68 is for power optimization, typically not modified.
    37. Parameter group 69 defines the maximum speed and acceleration/deceleration times.
    38. Parameter group 98 activates optional modules.
    Posted on Leave a comment

    ACS800 Variable Speed Drive (VSD) Debugging Steps

    I. Basic Local Control Process for ACS800 VSD

    Ensure that the air switch is closed and the contactor is energized.
    Press the LOC/REM key to switch to local control mode.
    Press the FAR key to enter the parameter setting interface. Use the double arrow keys to navigate to the 99 parameter group, then use the single arrow keys to select item 04. Press ENTER to confirm. Here, you can choose between DTC mode (suitable for most cases) or SCALA mode. After selecting, press ENTER to save or ACT to exit.
    Press the ACT key to return to the main operation interface.
    Press the REF key, use the up/down arrow keys to input the desired parameter value, and then press ENTER to confirm.
    Press the start key to begin operating the VSD.
    To replace the displayed actual signal, follow these steps:
    a. Press the ACT key to enter signal display mode.
    b. Select the row you want to change and press ENTER.
    c. Use the arrow keys to browse and select a new signal (such as actual motor speed – SPEED, transmission output frequency – FREQ, etc.).
    d. Press ENTER to confirm the change or ACT to exit.

    II. Data Upload and Download Operations

    To upload set motor parameters to the CDP-312 panel:

    Verify that item 98.02 is set to FIELDBUS and item 98.07 is set to ABB DRIVES.
    Switch to local control mode (LOC).
    Press the FUNC key to access the function menu.
    Use the arrow keys to navigate to the UPLOAD function and press ENTER to execute the upload.
    If you need to move the control panel, ensure it is in remote control mode first.
    To download data from the control panel to the drive unit:

    Connect the control panel containing the uploaded data.
    Ensure you are currently in local control mode.
    Press the FUNC key to access the function menu.
    Navigate to the DOWNLOAD function and press ENTER to execute the download.
    III. Achieving PLC and VSD PROFIBUS-DP Communication

    After confirming that the communication module is installed and the DP network cable is correctly connected, follow these steps to set the parameters:

    In local mode, use FAR and the arrow keys to enter parameter settings.
    Set 98.02 to FIELDBUS to activate the RPBA-01 communication module.
    Set 98.07 to ABB DRIVES to determine the communication protocol.
    Configure items 10.01, 10.02, and 10.03 as needed to define the external control source.
    Set 16.01 to YES to allow operation.
    Select the fault reset signal source for 16.04.
    From 11.01 to 11.08, set the source of the control word and given value.
    In items 22.01 to 22.03, define acceleration/deceleration time and stop function.
    For the 51 group of parameters, configure according to the fieldbus adapter module’s settings.
    Adjust the actual signal transmission content in the 92 group as needed.
    IV. Additional Parameter Setting Reference (Not Currently Used)

    This section provides guidance on setting speed limits, protection functions, and parameter locking for future reference.

    Note: Before making any parameter changes, ensure you fully understand their impact and consult a professional if necessary.

    Posted on Leave a comment

    Adjusting the Power Rating of ABB VFDs: A Step-by-Step Guide

    Adjusting the Power Rating of ABB VFDs: A Step-by-Step Guide

    When it comes to flexibility in power rating adjustments, ABB’s ACS510/ACS550/ACS350/ACS355/ACH550 Variable Frequency Drives (VFDs) offer a seamless solution. Whether you need to upgrade from a 1.1KW to a 5.5KW VFD or make any other power adjustment, these drives provide the capability to adapt to your specific requirements. This is especially beneficial in scenarios where you have a limited number of VFD main boards, like the SMIO-01C, and need to utilize them across different power ranges. Below is a detailed guide on how to access and modify the power rating parameters of these VFDs.

    Accessing and Modifying Parameters

    1. Open the Parameter Table:
      • Navigate to the deepest level of parameters, which may include numbers like 0102 or any other displayed values.
      • If you see 9905, for instance, hold the UP (arrow up), DOWN (arrow down), and RETURN (button next to LOC on the upper left) buttons simultaneously for 3 seconds.
      • You will observe a flash on the screen, and the top line should display “PARAMETERS+”.
    2. Expand Parameter Groups:
      • Exit and re-enter the parameter groups.
      • Notice that the number of parameter groups has increased from 99 to a maximum of 120.
      • Navigate to parameter group 105.

    Modifying Power Capacity

    Follow these precise steps to adjust the power capacity:

    1. Find and Modify Parameter 10509:
      • Change 105.09 to the desired current value.
      • Ensure the corresponding power value matches the VFD label. For example:
        • For ACS510-01-017A-4, change to 0174H.
        • For ACS510-01-031A-4, change to 0314H.
    2. Set 10502 to 1 and confirm.
    3. Set 10511 to 4012 and confirm.

    Note: The order of these modifications is crucial. Any mistake may require you to restart the process.

    Verifying Parameter Changes

    • Re-enter the parameter table.
    • Check if parameter 3304 (transmission capacity) reflects the correct modifications.

    Important Considerations

    • The process outlined above modifies the power rating on the ABB drive motherboard (SMIO-01C). It does not alter the power of the drive board itself.
    • Despite the appearance of expanded power capabilities, the actual output power of the VFD remains unchanged unless the power board is also modified.
    • This guide is specific to ACS510/ACS550/ACS350/ACS355/ACH550 VFDs and is not applicable to the ACS800 series.

    For assistance with power modification methods for ACS800 inverters, please reach out to us directly. Our team is here to help you navigate the intricacies of VFD power adjustments and ensure your equipment operates at its optimal capacity.

    Posted on Leave a comment

    Exploring the Circuitry and Modification Techniques of Frequency Inverter Transformers

    In the realm of frequency inverter circuits, transformers have evolved significantly. While early models relied on traditional transformers wound with through-core inductor coils, modern, mature circuits predominantly feature integrated, sealed current transformers constructed using Hall elements and pre-current detection circuits. These are often referred to as electronic current transformers and are categorized as either standard or non-standard types.

    Physical picture of frequency converter current sensor

    Standard electronic current transformers are readily available molded products in the market. For instance, a 10A/1V current transformer outputs a 1V signal for every 10A of current flowing through the circuit. On the other hand, non-standard types are custom-designed by frequency converter manufacturers and are not interchangeable. In case of damage, replacing them with the same model from the original manufacturer is usually necessary. However, with in-depth maintenance knowledge, different models can sometimes be used as temporary solutions until a permanent replacement is sourced.

    The construction of electronic current transformers often involves the use of sealants, making them difficult to repair once damaged. This has led to much curiosity about their internal circuitry and repairability. During my experience repairing a Fuji frequency inverter, I needed to adjust the A/V ratio of the electronic current transformer, which required accessing its internal circuit. This prompted me to carefully dissect and map the internal circuits of current transformers from three different frequency inverter models, a process that was both challenging and rewarding.

    At its core, an electronic current transformer is essentially a current-to-voltage converter circuit. The current transformer used in a Taian 7.5kW inverter serves as a representative example. The main body of the transformer is a circular hollow magnetic ring through which the U, V, and W output lines of the frequency inverter pass as the primary winding. As the output current of the frequency inverter varies, the magnetic field lines generated by the magnetic ring also change in density.

    Embedded within the gap of this magnetic ring is a Hall element with four lead terminals. The Hall element, packaged in sheet form, has its packaging end face (also known as the magnetic field line collection area or magnetic induction surface) exposed to the magnetic field lines. The Hall element converts changes in magnetic field lines into induced voltage outputs.

    Internal circuit diagram of the current sensor in a frequency converter.

    The circuit of the current transformer comprises the Hall element and a precision dual operational amplifier circuit, such as the 4570. For the Hall element to operate, a constant current of approximately 3-5mA must be supplied. In this circuit, the 4570A is configured as a constant current source to provide the necessary mA-level constant current for the Hall element (approximately 5.77mA in this case). This current is applied to pins 4 and 2 of the Hall element.

    The induced voltage, which varies with the output current, is present at pins 1 and 3 of the Hall element and is applied to the input terminals 2 and 3 of the 4570B. The three pins are connected to a reference voltage (zero potential point), and any change in the input voltage at the two pins is amplified and output by the 4570B.

    Electronic current transformers typically have four terminal components: two terminals supply power to the internal amplifiers (+15V and -15V), while the other two serve as signal output terminals (one grounded and one as the signal OUT terminal). In addition to powering the dual operational amplifier IC4570, the +15V and -15V are further stabilized to form a zero potential point that is introduced into the three pins of the 4570. When the frequency converter is off, the ground measurement at the OUT point should read 0V. During operation, it outputs an AC signal voltage proportional to the output current, typically below 4V.

    If an electronic current transformer is damaged, it may output a higher positive or negative DC voltage in the static state (when the frequency inverter is off). This is often due to damage to the internal operational amplifier. When the frequency inverter performs a power-on self-test, it may display a fault code (sometimes not listed in the manual) and refuse to start or even operate with its parameters.

    The current transformer circuit of a TECO 3.7kW frequency converter utilizes a programmable operational amplifier chip. Although I have not yet identified the specific model of this chip, modification tests have revealed some of its circuit characteristics. Experimental results indicate that pin 2 is the constant current power supply terminal, pins 3 and 4 are the input terminals of the differential amplifier, and pin 13 is the signal output terminal. By short-circuiting the solder gaps of pins 11, 12, and 13 in a stepwise manner, the amplification factor decreases; conversely, opening the circuit step-by-step increases the amplification factor. This adjustability allows for easier matching of the chip with frequency converters of different power outputs. I successfully applied this current transformer to a 45kW Fuji frequency inverter by taking appropriate measures.

    It is important to note that the voltage and current detection signals of the frequency converter may be used by the program to control the output three-phase voltage and current. Therefore, when repairing or modifying the original circuit, it is crucial to maintain the original circuit parameters to ensure proper operation. Whenever possible, it is recommended to use original accessories to repair the frequency converter while preserving the original circuit form.