Posted on Leave a comment

Fault Analysis and Handling for Inverter Displaying “88888” upon Power-up, with All Indicators Lit and No Response to Any Button Press

In inverter maintenance, it is common to encounter a situation where upon power-up, the inverter displays “88888”, all indicators are lit, and pressing any button results in no response. This fault typically indicates the following possibilities:

INDVS inverter shows 88888
  1. Power Issues: For example, voltage fluctuations or instability may prevent the inverter from completing its initialization process.
  2. Hardware Faults: Components such as the control board, drive board, or power supply may be damaged or malfunctioning.
  3. Communication Problems: Interruptions or errors in communication between the inverter and other devices may cause abnormal displays.
  4. Software or Firmware Issues: There may be bugs or incompatibilities in the inverter’s software or firmware that need to be addressed.

To troubleshoot this issue, the following steps can be taken:

Inovance inverter shows 88888
  1. Check Power Supply: Ensure that the voltage is stable and within the operating range specified by the inverter.
  2. Inspect Hardware: Open the inverter’s casing and inspect the control board, drive board, and power supply for any signs of damage or malfunction. Replace any faulty components as necessary.
  3. Test Communication: Verify that the communication lines between the inverter and other devices are properly connected and free from interference.
  4. Update Software/Firmware: If suspected, try updating the inverter’s software or firmware to the latest version.
  5. Reset the Inverter: Perform a hard reset of the inverter to see if it can recover from a stuck initialization state.

If the above steps fail to resolve the issue, it is recommended to contact the manufacturer’s technical support or a professional repair service for further assistance. Regular maintenance and inspections can also help prevent such faults from occurring in the first place.

Posted on Leave a comment

Shenzhen SHZHD Inverter V680 Series Operation Guide and E10 Fault Handling

Shenzhen SHZHD Inverter V680 Series Operation Guide and E10 Fault Handling

I. Operation Panel Function Introduction, Parameter Factory Reset, and Password Management

SHZHD INVERTER V680

1. Operation Panel Function Introduction

The operation panel of the Shenzhen SHZHD Inverter V680 series provides an intuitive operation interface, allowing users to set various parameters and operate the inverter through buttons and displays on the panel. The main functions of the panel include:

  • Display Area: Displays current set frequency, output frequency, current, voltage, and other parameters.
  • Function Keys: Such as MENU, ENTER, △, ▽, used for entering menus, confirming settings, and adjusting parameters.
  • Run Key: Starts and stops the inverter.
  • Fault Indicator: When the inverter malfunctions, the corresponding indicator light will illuminate, prompting the user to check the fault.

2. Parameter Factory Reset

To restore the inverter’s parameters to their factory defaults, follow these steps:

  1. Enter the menu interface and find the “Parameter Initialization” option.
  2. Select “Restore Factory Parameters” and confirm execution. At this point, all parameters except motor parameters will be restored to their factory settings.

3. Adding and Removing Passwords

To protect parameters from being modified casually, users can set passwords for the inverter.

  • Adding a Password: Enter the “User Password” setting, input the desired password, and confirm to save.
  • Removing a Password: Re-enter the “User Password” setting and set the password to 0 to remove password protection.

II. Torque Control and Vector Control

1. Torque Control

Torque control is a special control mode that allows users to directly set the output torque of the inverter instead of indirectly controlling the torque by setting the frequency. This control mode is very useful in situations where precise control of the load torque is required.

  • Setting Method: First, select “Torque Control” in the control mode. Then, choose the torque setting source through the corresponding parameter (such as A0-01), which can be the keyboard, analog input, communication, etc. Finally, set the desired torque value through parameters such as A0-03.

2. Vector Control

Vector control is a high-performance control method that achieves high-precision speed and torque control by precisely controlling the motor’s current and magnetic flux.

  • Optimizing Parameters: To obtain better vector control performance, users need to adjust related parameters based on the actual load conditions, such as the speed loop proportional gain (P2-00, P2-03) and speed loop integral time (P2-01, P2-04). The adjustment of these parameters requires certain professional knowledge and experience.

III. Terminal Start/Stop and Potentiometer Speed Regulation

1. Terminal Start/Stop

Controlling the start and stop of the inverter through external terminals is a commonly used control method. Users need to set the control mode of the inverter to “Terminal Control” and wire it correctly.

  • Wiring Terminals: Typically include the forward start terminal (e.g., DI1), reverse start terminal (e.g., DI2), and stop terminal (e.g., DI3).
  • Parameter Settings: Select “Terminal Command Channel” in P0-02 and set the corresponding terminal functions.

2. Potentiometer Speed Regulation

Potentiometer speed regulation is a simple speed regulation method where users can change the set frequency of the inverter by rotating the potentiometer, thereby achieving speed regulation.

  • Wiring Terminals: Connect the output end of the potentiometer to the analog input terminal of the inverter (e.g., AI1).
  • Parameter Settings: Select “Analog AI1 Setting” as the frequency source in P0-03.
E10 FAULT

IV. E10 Fault Handling

1. On-site Handling

The E10 fault typically indicates an overload of the inverter. When an overload fault occurs, users should first check if the load is too heavy or if the motor is stalled. If the load is normal, try increasing the inverter’s acceleration and deceleration times to reduce the impact on the motor.

2. Maintenance Handling

If on-site handling fails to resolve the issue, it may be necessary to disassemble the inverter for maintenance. During the maintenance process, focus on the following aspects:

  • Motor and Load: Confirm whether the motor and load are normal and free from mechanical faults or obstructions.
  • Inverter Parameters: Check whether the inverter’s overload protection parameters (such as P9-00, P9-01) are set reasonably.
  • Hardware Faults: If the parameter settings are normal and the load is without abnormality, it may be a hardware fault within the inverter, such as damaged power devices or poor heat dissipation. At this point, professional maintenance personnel should be sought for assistance.

Conclusion

The Shenzhen SHZHD Inverter V680 series is a powerful and flexible inverter product. Through this guide, users can better understand the inverter’s operation panel functions, parameter setting methods, the application of torque control and vector control, and common fault handling methods. In practical applications, users should configure parameters and control modes based on specific needs and load conditions to ensure stable operation and high performance of the inverter.

Posted on Leave a comment

Kingda Inverter V380 Series User Manual Operation Guide

Kingda Inverter V380 Series User Manual Operation Guide

I. Introduction to Inverter Operation Panel Functions and Factory Reset

The Kingda Inverter V380 series features a versatile operation panel with the following main keys:

  • Run/Stop Key: Used to start or stop the inverter.
  • Forward/Reverse Key: Used to control the motor’s forward and reverse rotation, respectively.
  • Stop/Fault Reset Key: Used to reset or stop the inverter in case of a fault.
  • Return Key: Used to switch between monitoring modes or return to the previous state.
  • Confirm Key: Confirms the current status or parameter and enters the next level of the function menu.
  • Data Modify Key: Used to modify function codes or parameters.
  • Shift Key: Used to move the cursor position when setting parameters.
Kingda Inverter V380 Operation Panel

Factory Reset:

  • To restore factory settings, enter the parameter settings interface, find the P0.03 parameter (Parameter Initialization), set it to 1, and then press the confirm key to execute the initialization. This operation will clear all user-defined parameters, and the inverter will revert to its factory default settings.

Carrier Frequency and Carrier Characteristic Parameters:

  • Carrier Frequency: Refers to the frequency of the PWM (Pulse Width Modulation) signal within the inverter, affecting the harmonic content of the output current and motor noise levels. A higher carrier frequency reduces harmonic content but increases switching losses, potentially leading to increased inverter heat generation.
  • Carrier Characteristic Parameter (P0.12): Controls whether the carrier frequency changes with the output frequency. When set to 0, the carrier frequency does not change with the output frequency; when set to 1, the carrier frequency increases with the output frequency, helping to reduce noise and vibration at lower frequencies.
  • Setting Carrier Frequency: Enter the parameter settings interface, find the P0.11 parameter (Carrier Frequency), and adjust its value according to actual needs, typically ranging from 0.8 to 15.0 KHz.

II. Terminal Start/Stop and External Potentiometer Speed Regulation Settings

Terminal Start/Stop:

  • Wiring: Connect external control signals to the inverter’s DI (Digital Input) terminals. Typically, the forward start signal is connected to DI1, the reverse start signal to DI2, and the stop signal to DI3 (or a combination of states shared by DI1 and DI2).
  • Parameter Settings: Enter the parameter settings interface and set P1.05 (Run Command Channel) to 1 (Terminal Control Start/Stop).
Kingda Inverter V380

External Potentiometer Speed Regulation:

  • Wiring: Connect the output of the external potentiometer to the inverter’s AI1 (Analog Input 1) terminal. The sliding end of the potentiometer is used to adjust the output voltage, thereby controlling the inverter’s output frequency.
  • Parameter Settings: Enter the parameter settings interface, set P1.00 (Main Frequency Channel A Selection) to 3 (Panel Potentiometer), and set P2.00 and P2.01 to the lower and upper voltage limits of AI1 input, respectively.

III. Modbus Protocol Settings and PID Control via Siemens PLC (S7-200)

To achieve PID control (e.g., single-pump constant pressure water supply) of the inverter via a Siemens PLC (S7-200) using the Modbus protocol, the following settings are required:

  • Modbus Parameter Settings:
    • Enter the parameter settings interface, set the units place of P9.00 (Communication Settings) to the corresponding baud rate (e.g., 4 for 9600 bps), and the tens place to the data format (e.g., 0 for no parity).
    • Set P9.01 (Device Address) to the Modbus address of the inverter.
    • Ensure P9.04 (Communication Timeout Fault Detection Time) is set reasonably to avoid communication interruptions.
  • PID Control Parameter Settings:
    • Enter the parameter settings interface and enable the built-in PID control (P8.00 set to a non-zero value).
    • Set the PID setpoint and feedback channels (P8.01), typically selecting the external voltage signal AI1 as the feedback channel.
    • Adjust PID proportional constant (P8.07), integral constant (P8.08), and other parameters according to control requirements.
  • PLC Programming:
    • Write a Modbus communication program in the Siemens PLC (S7-200) to read the current status of the inverter and send PID setpoints.
    • Write a PID control algorithm program to adjust the setpoint based on the feedback signal, achieving control objectives such as constant pressure water supply.

IV. Fault Code Analysis and Solutions

The Kingda Inverter V380 series features comprehensive fault protection. When a fault occurs, the inverter displays the corresponding fault code. Below are some common fault codes, their analysis, and solutions:

  • EC.01: Overcurrent during acceleration. Possible causes include too short an acceleration time, an inappropriate V/F curve, etc. Solutions include extending the acceleration time, adjusting the V/F curve, etc.
  • EC.02: Overcurrent during deceleration of the inverter. A possible cause is too short a deceleration time. The solution is to increase the deceleration time.
  • EC.03: Overcurrent during inverter operation or stoppage. Possible causes include sudden load changes, low grid voltage, etc. Solutions include reducing load fluctuations and checking the power supply voltage.
  • EC.04 to EC.07: Related to overvoltage faults, possible causes include abnormal power supply voltage, improper deceleration time settings, etc. Solutions include checking the power supply voltage and adjusting the deceleration time.
  • EC.12 and EC.13: Indicate inverter and motor overload, respectively. Possible causes include excessive load, too short an acceleration time, etc. Solutions include reducing the load and extending the acceleration time.

For other fault codes, refer to the Fault Diagnosis and Countermeasures section of the user manual for detailed analysis and solutions. When troubleshooting, ensure that the inverter is powered off and take necessary safety measures.

V. Conclusion

This document provides a detailed introduction to the operation guide of the Kingda Inverter V380 series, including the operation panel function introduction, factory reset method, carrier frequency and carrier characteristic parameter settings, terminal start/stop and external potentiometer speed regulation settings, Modbus protocol and PLC PID control settings, as well as fault code analysis and solutions. With this guide, users can better understand and utilize this inverter to achieve efficient and stable motor control.

Posted on Leave a comment

User Manual and Operating Guide for Hitachi Inverter SJ300


I. Basic Operation and Monitoring Functions

  1. Panel Setting and Monitoring
    Setting to Display Current, Bus Voltage, and Frequency

Display Current: First, enter the monitoring mode via the panel buttons (typically by selecting the monitoring mode with the “FUNC” key). In monitoring mode, use the up and down arrow keys to browse through different monitoring parameters, find the current monitoring item, and confirm.
Display Bus Voltage: Similarly, in monitoring mode, use the up and down arrow keys to find the bus voltage monitoring item and confirm.
Display Frequency: Frequency is one of the most commonly used monitoring parameters and is usually directly displayed on the main interface of the monitoring mode. If not displayed, select the frequency monitoring item with the arrow keys.
Monitoring Terminal Status

Enter monitoring mode, then select “Smart Input Terminal Status” or “Smart Output Terminal Status” for monitoring. These statuses include the switching state of the terminals, signal voltage, etc.
Panel Start/Stop and Speed Adjustment

Functional diagram of the operation panel for Hitachi inverter SJ300.

Start and Stop: In standard setting mode, start the inverter with the “RUN” key and stop it with the “STOP/RESET” key.
Speed Adjustment: Speed adjustment is typically achieved by changing the frequency setting value. On the panel, use the up and down arrow keys to adjust the frequency setting value, then press the “Store” key to confirm.
II. Multi-Speed Function Setting

  1. Setting Multi-Speed
    Assuming four speeds are needed, namely 10Hz, 20Hz, 40Hz, and 50Hz, the specific steps are as follows:

Wiring:
Connect external control signals (such as switch signals) to the inverter’s multi-speed control terminals (such as FW, 8, 7, 6, etc.).
Ensure correct connection of the control signal power supply and grounding.
Parameter Setting:
Enter standard setting mode and find parameters related to multi-speed control (such as A038, A039, etc.).
Set A038=00 (indicating external terminal control for multi-speed).
Set A039=04 (indicating 4-speed control).
Set the corresponding frequency values for the four speeds in the “F001” parameter: F001=10Hz (first speed), A020=20Hz (second speed), A220=40Hz (third speed), A320=50Hz (fourth speed).
III. Communication Protocol Setting

Standard wiring diagram for Hitachi inverter SJ300.
  1. Communication with Mitsubishi FX2N Series PLC
    Communication Method: Assuming RS485 communication is used.
    Parameter Setting:
    In the inverter, set C070=03 (select RS485 communication).
    Set C071 to the desired baud rate (e.g., C071=04 for 4800bps).
    Set C072=1 (8 data bits).
    Set C073=7 (no parity check).
    Set C074=0 (1 stop bit).
    On the PLC side, configure the corresponding RS485 communication parameters to match the inverter.
    IV. Simple Analysis and Handling of Fault Codes
  2. Common Fault Codes
    E02: Overcurrent Alarm. Possible causes include excessive motor load, motor stall, etc. Troubleshooting includes checking motor load, checking for motor stall, etc.
    E03: Overload Alarm. Possible causes include the motor operating overloaded for a long time. Troubleshooting includes reducing the load, increasing motor capacity, etc.
    E05: Overvoltage Alarm. Possible causes include excessively high input voltage. Troubleshooting includes checking if the input voltage is normal, adding input voltage protection, etc.
  3. Handling Steps
    Check the Alarm Code: When the inverter alarms, first check the alarm code displayed on the panel.
    Analyze Possible Causes: Based on the alarm code and site conditions, analyze possible fault causes.
    Take Measures: Based on the analysis results, take corresponding troubleshooting measures.
    Reset the Inverter: After troubleshooting, press the “STOP/RESET” key to reset the inverter and restart it.
    V. Summary

The Hitachi Inverter SJ300 series user manual provides detailed operating instructions and parameter setting methods. By carefully reading the manual and following the guidelines, users can easily monitor, control, and troubleshoot the inverter. Particular attention should be paid to correct parameter configuration and wiring accuracy when setting the multi-speed function and communicating with PLCs. Proper use of the inverter can significantly improve the operational efficiency and stability of the motor system.

Posted on Leave a comment

Operation Guide for Hitachi Inverter SJH300 Series User Manual

I. Introduction to Operation Panel Functions, Factory Default Reset, and Password Management

The Hitachi Inverter SJH300 series features an intuitive operation panel that integrates various functions for easy configuration and monitoring. The operation panel includes:

Functional Diagram of the Operation Panel for Hitachi Inverter SJH300
  1. Operation Panel Function Introduction:
    • Digital Operator (OPE-S): The standard-equipped digital operator provides a user-friendly interface for setting parameters, monitoring operating conditions, and controlling the inverter. Key functions include setting output frequency, selecting operation direction, and initiating start/stop commands.
    • Monitor Modes: The panel displays various monitor modes, such as output frequency, output current, operation direction, and alarm status, to provide real-time feedback on the inverter’s performance.
  2. Resetting to Factory Defaults:
    • To restore the inverter to its factory default settings, you need to navigate to the appropriate parameter (typically b084) in the function mode and set it to 01 for data initialization or 02 for both trip history clear and data initialization. This action resets all parameters to their default values, effectively restoring the inverter to its out-of-the-box state.
  3. Password Management:
    • Setting a Password: To set a password for parameter access, use the C070 parameter to select the data command mode (e.g., 03 for RS485 communication). Then, configure the relevant communication parameters (such as transmission speed, code, bit, and parity) to establish a secure communication channel.
    • Eliminating a Password: To remove the password, simply reset the C070 parameter to its default value (02 for operator mode), which disables password protection and allows unrestricted access to all parameters.
Standard wiring diagram for Hitachi Inverter SJH300 series.

II. Terminal Start/Stop, Forward/Reverse Control, and External Potentiometer Speed Adjustment

The Hitachi Inverter SJH300 series offers flexible control options, including terminal start/stop, forward/reverse control, and external potentiometer speed adjustment. Here’s how to configure these features:

  1. Terminal Start/Stop and Forward/Reverse Control:
    • Wiring: Connect the start (FW) and stop (RV) terminals to the appropriate control signals. For forward/reverse control, you may need to assign specific intelligent input terminals (e.g., terminals 7, 8 for forward/reverse commands).
    • Parameter Setting:
      • Set A002 to 01 to select terminal operation command.
      • Configure F004 to select the desired operation direction (00 for forward, 01 for reverse).
      • If using intelligent input terminals for forward/reverse control, assign the corresponding terminals (e.g., terminals 7, 8) and set the appropriate function codes (C001-C008).
  2. External Potentiometer Speed Adjustment:
    • Wiring: Connect the external potentiometer (typically a 10kΩ linear potentiometer) across the O-L (0-10V) terminals. Ensure proper grounding and shielding to avoid noise interference.
    • Parameter Setting:
      • Set A001 to 01 to select terminal frequency command.
      • Configure A011 (O start) and A012 (O end) to define the minimum and maximum output frequencies corresponding to the potentiometer’s minimum and maximum resistance values.
      • Adjust A013 (O start rate) and A014 (O end rate) if linear adjustment is not achieved directly with the potentiometer.

By following these steps, you can effectively configure the Hitachi Inverter SJH300 series for terminal-based start/stop and forward/reverse control, as well as external potentiometer speed adjustment, to suit your specific application requirements.

Posted on Leave a comment

Analysis, Types, and Maintenance Solutions for Delta Inverter GFF Fault

I. Meaning and Internal Mechanism of Delta Inverter GFF Fault

When a Delta inverter reports a “GFF” fault code, it indicates a “Ground Fault” (GFF) has occurred at the output terminal. This fault typically involves issues with the output circuit, such as damage to the IGBT, a short circuit in the output, or problems with the driver circuit, particularly when using PC929 optocouplers.

Physical picture of Delta INVERTER MS300 series

II. Analysis of the GFF Fault Scenario Described

In the scenario provided, the Delta inverter reports a GFF fault immediately upon connecting the motor, but the fault disappears when the motor wires are disconnected and the inverter is started alone. This suggests that the issue lies with the motor or the connection between the motor and the inverter, rather than the inverter itself.

Possible Causes:

  1. Motor Wiring Issues:
    • Short circuit or ground fault in the motor wiring.
    • Poor connection or loose wires at the motor terminals.
  2. Motor Problems:
    • Internal short circuit or ground fault within the motor.
    • Insulation failure or damage in the motor windings.
  3. External Interference:
    • Electromagnetic interference from nearby equipment affecting the inverter’s output circuit.
  4. IGBT or Driver Circuit Damage:
    • Although less likely in this case (since the fault disappears without the motor), damage to the IGBT or driver circuit could still be a factor if there are underlying issues with the inverter’s output stage.
b4GFF fault

III. Steps for Troubleshooting and Maintenance

  1. Check Motor Wiring:
    • Ensure all motor wires are properly connected and tightened.
    • Inspect the wires for any signs of damage, wear, or short circuits.
  2. Insulation Resistance Test:
    • Perform an insulation resistance test on the motor to check for insulation failure.
  3. Disconnect and Reconnect Motor:
    • Disconnect and then reconnect the motor wires to ensure a good connection.
    • Use a multimeter to test for continuity and shorts between the motor wires and ground.
  4. Isolate the Motor:
    • Try running the inverter with a different motor (if available) to determine if the fault lies with the motor or the inverter.
  5. Check Inverter Output Circuit:
    • Inspect the inverter’s output circuit for any signs of damage, particularly around the IGBTs and driver circuitry.
    • Replace any damaged components if necessary.
  6. Consult the Manual and Technical Support:
    • Refer to the Delta Inverter manual for more detailed troubleshooting steps and fault codes.
    • Contact Delta technical support for assistance if the issue cannot be resolved.

IV. Conclusion

The GFF fault reported by the Delta inverter is likely related to the motor or its connection to the inverter. By systematically checking the motor wiring, performing insulation resistance tests, and isolating the motor, the root cause of the fault can be identified and resolved. If the fault persists, further inspection of the inverter’s output circuit may be necessary.

Posted on Leave a comment

SHZK INVERTER ZK880 Series User Guide and ERR13 Fault Handling Method

SHZK INVERTER ZK880 Series User Guide

I. Operation Panel Function Introduction

The SHZK INVERTER ZK880 series provides an intuitive operation panel, facilitating easy setup and control of the inverter.

II. Setting Key Parameters

1. Acceleration and Deceleration Time

To set the acceleration and deceleration time:

  1. Press the PRG key to enter the programming mode.
  2. Use the  and  keys to navigate to the relevant parameters (e.g., F0-17 for acceleration time, F0-18 for deceleration time).
  3. Use the  and  keys to adjust the values.
  4. Press the ENT key to confirm the settings.
SHZK ZK880 INVERTER

2. Starting Frequency

To set the starting frequency:

  1. Enter the programming mode by pressing the PRG key.
  2. Navigate to the starting frequency parameter (F6-03).
  3. Adjust the value using the  and  keys.
  4. Confirm the setting with the ENT key.

3. Upper and Maximum Frequency

To set the upper and maximum frequency:

  1. Enter the programming mode.
  2. Navigate to the maximum frequency parameter (F0-10).
  3. Adjust the value to the desired maximum frequency.
  4. For the upper frequency limit, navigate to F0-12 and set accordingly.
  5. Confirm each setting with the ENT key.

4. Minimum Frequency

To set the minimum frequency:

  1. Enter the programming mode.
  2. Navigate to the minimum frequency parameter (F0-14).
  3. Adjust the value to the desired minimum frequency.
  4. Confirm with the ENT key.

5. Current and Power

To monitor or limit the current and power:

  1. The current and power values can be monitored in real-time via the operation panel or through the monitoring parameters (U0-04 for output current, U0-05 for output power).
  2. For current limiting, navigate to the relevant protection parameters (e.g., F9-06 for over-current trip level).
  3. Adjust the values as needed and confirm with the ENT key.

6. Restoring Initialization Parameters

To restore the inverter to its factory settings:

  1. Power off the inverter.
  2. Hold down the STOP/RES key while powering on the inverter.
  3. Continue holding the key until the display shows “rE”, indicating that the parameters have been reset.
  4. Release the key and allow the inverter to restart.

III. Terminal Start and Direction Control

1. Terminal Start

To start the inverter via terminals:

  1. Ensure the command source is set to terminal control (F0-02 = 1).
  2. Connect the appropriate terminal (e.g., FWD for forward rotation) to a closed contact or power source.
  3. The inverter will start running according to the terminal configuration.

2. Direction Control

To control the rotation direction:

  1. Ensure the necessary terminals (e.g., FWD for forward, REV for reverse) are properly connected.
  2. Activate the corresponding terminal to start the inverter in the desired direction.
  3. For reversing, deactivate the forward terminal and activate the reverse terminal.
ERR13 FAULT

ERR13 Fault Handling Method

Common Causes of ERR13 Fault

  • Overcurrent fault due to excessive load or short circuit.
  • Motor parameters not properly set or identified.
  • Insufficient cooling of the inverter or motor.

Handling Steps

  1. Check the Load: Ensure the load is within the inverter’s rated capacity and there are no short circuits or ground faults.
  2. Review Motor Parameters: Verify that the motor parameters (e.g., rated current, power) are correctly entered into the inverter.
  3. Check Cooling: Ensure adequate ventilation and cooling of both the inverter and the motor.
  4. Reset the Inverter: If the fault persists, try resetting the inverter by power cycling it or using the STOP/RES key.
  5. Consult the Manual: Refer to the user manual for more detailed troubleshooting steps and parameter adjustments.

By following these guidelines, users can effectively operate and troubleshoot the SHZK INVERTER ZK880 series, ensuring optimal performance and reliability.

Posted on Leave a comment

Emerson Inverter MEV2000 Series User Guide and Er.0234 Fault Meaning and Solution

I. Introduction

The Emerson Inverter MEV2000 series, with its high performance, high reliability, and wide range of applications, has become a preferred choice in the field of industrial control. This article will provide a detailed introduction to the panel functions, password setting and removal, parameter initialization methods of the MEV2000 series inverters. Additionally, it will explain how to use terminal control for forward and reverse starting and potentiometer speed adjustment. Finally, it will address the common Er.0234 fault, explaining its meaning and providing detailed solutions.

Emerson inverter MEV2000 physical picture

II. Inverter Panel Function Introduction

The operation panel of the Emerson Inverter MEV2000 series serves as the primary interface between the user and the device, featuring an LED display, function keys, and indicator lights. Users can utilize the panel to view inverter status, set operational parameters, and monitor input and output signals. The primary function keys on the panel include the program/exit key, function/data key, increase/decrease keys, and run/stop keys, which can be combined to perform various operations.

Password Setting and Removal

To protect the inverter parameters from unauthorized modification, the MEV2000 series inverters offer a password protection function. Users can set a password by configuring the FP.000 parameter. Once set, a password is required to modify parameters. If password protection needs to be removed, the following steps can be followed: first, unlock the user password using the correct password, then set the FP.001 parameter to 0, and finally reset the inverter to disable password protection.

Parameter Initialization

When users need to restore the inverter parameters to the factory settings, they can do so by configuring the FP.002 parameter. Setting FP.002 to 2 will clear all user-set parameters and restore them to the default factory settings. However, please note that this operation will not restore the motor parameters. To restore motor parameters, FP.002 should be set to 4.

III. Terminal Control for Forward and Reverse Starting and Potentiometer Speed Adjustment

Setting Parameters

To use terminal control for forward and reverse starting and potentiometer speed adjustment, the following parameters need to be configured:

  • F0.000: Set the frequency given channel to digital given 1 (adjusted by the operation panel potentiometer).
  • F0.004: Set the operation command channel to the terminal operation command channel.
  • F7.008: Set the operation mode to two-wire operation mode 1 or 2, depending on the specific wiring method.

Wiring Terminals

  • FWD: Forward control terminal, connected to an external forward start button or switch.
  • REV: Reverse control terminal, connected to an external reverse start button or switch.
  • +10V and 0V: Provide power to the potentiometer, connected to both ends of the speed adjustment potentiometer.
  • AI1: Analog input terminal, connected to the sliding end of the speed adjustment potentiometer to receive the speed adjustment signal.
ER.2034 malfunction

IV. Er.0234 Fault Meaning and Solution

Fault Meaning

When the Emerson Inverter MEV2000 series displays the Er.0234 fault code, it indicates that either the OLX2 (overload relay board) or the STO (safety signal input board) is not installed or improperly connected. These two boards are crucial for the normal operation of the inverter, with the OLX2 responsible for monitoring overload conditions and the STO responsible for processing safety signals.

Solution

  1. Check Board Installation:
    • First, confirm that the OLX2 board and STO board are correctly installed inside the inverter.
    • Inspect the connections between the boards and the inverter’s mainboard to ensure they are secure and free from looseness or detachment.
  2. Check Wiring:
    • Verify that the wiring for the OLX2 board and STO board is correct, with no misconnections or missing connections.
    • Confirm that all connection wires are securely fastened and free from shorts or opens.
  3. Restart the Inverter:
    • After confirming that the boards are installed and wired correctly, attempt to restart the inverter to see if the fault is resolved.
    • If the fault persists, further inspection of the boards for potential damage may be necessary.
  4. Replace the Boards:
    • If damage to the boards is confirmed, replace them with new OLX2 and STO boards promptly.
    • After replacing the boards, reinstall and rewire them, then try to start the inverter again.
  5. Contact After-Sales Service:
    • If the above steps fail to resolve the issue, it is recommended to contact Emerson Inverter’s after-sales service personnel for professional assistance.

V. Conclusion

The Emerson Inverter MEV2000 series plays a vital role in the field of industrial control due to its powerful functions and reliable performance. Through this article, users can gain a better understanding of the inverter’s panel functions, password setting and removal, parameter initialization methods, and how to use terminal control for forward and reverse starting and potentiometer speed adjustment. Additionally, for the common Er.0234 fault, this article provides detailed solutions to help users quickly locate and resolve the issue, ensuring the normal operation of the inverter.

Posted on Leave a comment

User Manual Guide for GTAKE Inverter GK600 Series

I. Introduction to the Operating Panel Functions and Password Settings

The operating panel of the GTAKE Inverter GK600 series serves as its core human-machine interface, providing parameter setting, operational status display, and more. The primary indicators and button functions on the operating panel are as follows:

  • Indicators: Include frequency indication, current indication, voltage indication, speed indication, etc., used to display the current operating status of the inverter.
  • Buttons: Include RUN, STOP/RESET, MF (multi-function button), etc., used to control the start, stop, and parameter settings of the inverter.
GTAKE INVERTER GK600 series operation panel diagram

Setting and Removing Passwords

To protect the inverter parameters from unauthorized changes, users can set passwords to restrict access. The specific operations are as follows:

  1. Setting a Password:
    • Enter function code A0-00, input a four-digit non-zero password, and press ENT to confirm.
    • Re-enter the same password within 10 seconds to confirm, and “P-Set” will be displayed upon successful setting.
    • If there are no button operations within 5 minutes or after a complete power-off and power-on cycle, the password will automatically take effect.
  2. Removing a Password:
    • Enter function code A0-00 and input the original four-digit password.
    • Input 0000 twice and press ENT to confirm, and the password will be cleared successfully with “P-Set” displayed.

Initializing Parameters

Users can restore the inverter parameters to their factory settings through the initialization function. The specific operations are as follows:

  • Enter function code A0-03 and set it to 2 (restore all function code group parameters to factory settings, excluding motor parameters) or 3 (restore all function code group parameters to factory settings, including motor parameters), then press ENT to confirm and the parameters will be initialized.

II. Terminal Forward/Reverse Start/Stop and Potentiometer External Speed Regulation

Terminal Forward/Reverse Start/Stop

The GK600 series inverter supports forward/reverse start/stop functions through terminals. The specific settings and wiring are as follows:

  1. Parameter Settings:
    • Enter the C0 group function codes and set the functions of terminals X1, X2, X3, and X4 to forward jog, reverse jog, forward run, reverse run, etc.
    • Set C0-00 to 0 (edge trigger + level valid) or 1 (level valid) based on actual needs.
  2. Wiring:
    • Connect the external control signals to the corresponding forward/reverse start/stop terminals.

Potentiometer External Speed Regulation

Speed regulation can be achieved through an external potentiometer. The specific settings and wiring are as follows:

  1. Parameter Settings:
    • Enter the b0 group function codes and set the frequency main given method b0-01 to 2 (analog input AI1).
    • Ensure that the AI1 terminal is correctly connected to the potentiometer, and select voltage or current input via the jumper.
  2. Wiring:
    • Connect the three pins of the potentiometer to the positive, negative, and ground terminals of the AI1 terminal.
GTAKE INVERTER GK600 Series Standard Wiring Diagram

III. Swing Frequency Function and Length Control

Swing Frequency Function

The swing frequency function allows the inverter to operate with fluctuating frequencies within a set range, suitable for applications requiring periodic frequency changes. The specific parameter settings are as follows:

  • Enter the F3 group function codes and set F3-00 to 1 (select swing frequency function).
  • Set parameters such as F3-01 swing frequency operation mode, F3-02 swing frequency preset, F3-03 swing frequency preset hold time, and F3-04 swing frequency amplitude.

Length Control

Length control automatically stops the inverter based on a set length. The specific wiring and parameter settings are as follows:

  1. Wiring:
    • Connect the length counting pulse signal to the X6/DI terminal.
    • Ensure that the external length sensor or pulse generator is correctly connected.
  2. Parameter Settings:
    • Enter the F3 group function codes and set parameters such as F3-08 set length unit and F3-09 set length.
    • Ensure that C0-06 has set the X6/DI terminal function to length counting.

IV. Fault Code Analysis

The GK600 series inverter features comprehensive fault protection functions, displaying corresponding fault codes when anomalies are detected. Users can quickly locate the cause of the issue based on the fault code and take corresponding measures. Common fault codes and their meanings are as follows:

  • oC1/oC2/oC3: Indicate acceleration overcurrent, constant speed overcurrent, and deceleration overcurrent faults, respectively.
  • ov1/ov2/ov3: Indicate acceleration overvoltage, constant speed overvoltage, and deceleration overvoltage faults, respectively.
  • FAL: Indicates IGBT module protection fault.
  • oL1/oL2: Indicate inverter overload and motor overload faults, respectively.
  • ISF: Indicates input power supply abnormality fault.

Users can analyze the fault cause in detail according to the fault code table in the manual and perform corresponding repairs.

V. Conclusion

The user manual for the GTAKE Inverter GK600 series provides detailed information on the operating panel functions, parameter settings, terminal wiring, and fault code analysis of the inverter. Through this guide, users can quickly master the basic operations of the inverter, realize forward/reverse start/stop and external speed regulation functions, configure swing frequency and length control parameters, and quickly locate and resolve fault issues based on fault codes. It is hoped that this article will provide strong assistance to users when using the GK600 series inverter.

Posted on Leave a comment

KCLY INVERTER KOC600 Series User Manual Guide

1. Panel Startup, Speed Adjustment, Password Setting & Removal, and Parameter Initialization

Panel Startup and Speed Adjustment

The KCLY INVERTER KOC600 series supports startup and speed adjustment via the operation panel. To set up panel startup:

  1. Ensure the command source is set to the operation panel: Navigate to the parameter b0-02 and set it to 0 (Operation Panel Command Channel). This ensures that the startup and speed commands come from the panel.
  2. Adjust the frequency: Use the  and  keys on the panel to increase or decrease the set frequency (b0-12). The motor will run at the set frequency once the startup command is given.
Function diagram of KCLY INVERTER KOC600 series operation panel

Password Setting and Removal

To set a password for the KOC600 series inverter:

  1. Navigate to the password parameter: Go to parameter A0-00 and enter the desired password value (0-65535).
  2. Save and exit: Press the DATA/ENTER key to save the password setting.

To remove the password:

  1. Enter the current password: Go to parameter A0-00 and enter the current password.
  2. Clear the password: Set the value to 0 and press the DATA/ENTER key to save.

Parameter Initialization

To initialize the parameters to their factory defaults:

  1. Navigate to the initialization parameter: Go to parameter A0-09.
  2. Select the initialization option: Set A0-09 to 1 to restore factory settings excluding motor parameters, 2 to restore factory settings including motor parameters, or 3 for reserved purposes.
  3. Save and reset: Press the DATA/ENTER key to save and reset the parameters.
KCLY INVERTER KOC600 Series Wiring Diagram

2. External Terminal Startup and Pulse Frequency Speed Adjustment

Terminal Connection and Settings

To set up external terminal startup and pulse frequency speed adjustment, you need to connect and configure specific terminals:

  1. Connect the external startup terminal: Typically, you would connect an external switch or relay to the FWD (forward) and REV (reverse) terminals on the inverter. Ensure proper grounding and wiring according to the manual.
  2. Set the command source to terminal control: Navigate to parameter b0-02 and set it to 1 (Terminal Command Channel). This allows the inverter to receive startup and speed commands from the external terminals.
  3. Configure the pulse input terminal: If using pulse frequency for speed adjustment, connect the pulse generator to the DI6 (High-Speed Pulse Input) terminal.
  4. Set the frequency source to pulse input: Go to parameter b0-03 and set it to 5 (PULSE pulse setting). This configures the inverter to use the pulse input on DI6 as the frequency source.
  5. Adjust pulse-to-frequency parameters: Configure parameters b5-00 to b5-03 to define the relationship between the pulse input frequency and the inverter’s output frequency.

Example Configuration Steps

  1. Connect the external switch to FWD: Use a normally open switch connected between FWD and COM.
  2. Set the command source:
    • Navigate to b0-02 and set it to 1.
  3. Connect the pulse generator to DI6: Ensure the pulse generator outputs a compatible voltage and frequency range.
  4. Configure the pulse input:
    • Set b0-03 to 5 (PULSE pulse setting).
    • Adjust b5-00 to 0.00kHzb5-02 to the maximum expected pulse frequency (e.g., 50.00kHz), b5-01 to 0.0%, and b5-03 to 100.0%.
  5. Save the settings: Press the DATA/ENTER key to save all configurations.

By following these steps, you can set up the KCLY INVERTER KOC600 series for external terminal startup and pulse frequency speed adjustment. Always refer to the user manual for detailed wiring diagrams and additional configuration options.