Posted on Leave a comment

SANJ INVERTER PDG10 Series Water Pump Control Dedicated Usage Guide

I. Achieving Constant Pressure Water Supply with Single Pump Control

In single pump control mode, the PDG10 series SANJ INVERTER automatically adjusts the speed of the water pump motor by setting the pipe network pressure value, thereby maintaining a constant water supply pressure. Below are the steps to achieve constant pressure water supply:

1. Wiring

  • Main Circuit Wiring: Connect the three-phase power supply to the R, S, T terminals of the inverter and the motor to the U, V, W terminals, ensuring the grounding terminal is reliably grounded.
  • Control Circuit Wiring: Depending on requirements, connect the pressure sensor to the AI1 or AI2 terminal and set the F2.00 or F2.02 parameter according to the sensor type. If using external start/stop control, connect the start and stop signals to the DI1 and DI2 terminals.

2. Parameter Settings

  • Pressure Setting: Set the target pressure value through the F0.00 parameter. For example, to achieve a pipe network pressure of 3.0 kg, set F0.00=3.0.
  • Start Mode: If using external start/stop control, set F0.05=1 (terminal start/stop).
  • Sensor Settings: Set F0.08 (sensor range), F0.09 (sensor feedback channel selection), and F2.00 or F2.02 (sensor feedback type selection) according to the pressure sensor type.
  • Operating Mode: Set F0.15=0 to select the constant pressure control mode.
  • Other Parameters: Set acceleration time (F0.18) and deceleration time (F0.19) parameters according to actual needs.

II. One-to-Two Timed Rotation Control

In one-to-two timed rotation control mode, one inverter alternately controls two water pump motors to achieve timed rotation. Below are the implementation steps:

1. Wiring

  • Main Circuit Wiring: Connect the output terminals of the inverter to the U, V, W terminals of the two water pump motors respectively.
  • Control Circuit Wiring: Connect the pressure sensor to the AI1 or AI2 terminal and connect the relay output terminals of the inverter (e.g., T1A/T1B and T2A/T2B) to the control circuit of the contactors to achieve water pump rotation control.
  • Frequency Control: If frequency backup is required, connect the frequency power supply to the corresponding contactor and control the contactor’s engagement and disengagement through the inverter’s relay output.

2. Parameter Settings

  • One-to-Two Mode: Set F0.20=7 to select the one-to-two mode.
  • Rotation Mode: Set F1.08=1 to select the rotating variable frequency pump mode.
  • Pump Addition and Reduction Parameters: Set F1.09 (bias pressure for adding frequency pump), F1.10 (delay time for adding frequency pump), F1.11 (bias pressure for reducing frequency pump), F1.12 (delay time for reducing frequency pump), etc., according to actual needs.
  • Rotation Time: Set F1.05 to define the interval time for timed rotation of the main and auxiliary pumps.
  • Other Parameters: Set PID parameters (e.g., F3.00 proportional gain, F3.01 integral time) and other related parameters according to actual needs.

III. Multi-Pump Networking Scheme

The PDG10 series SANJ INVERTER supports multi-pump networking control via RS485 (MODBUS) or CAN bus. Below are the implementation steps:

1. Wiring

  • RS485 Communication Wiring: Connect the A+/B- terminals of the inverter to the RS485 communication ports of the host computer or other inverters using twisted pair or shielded cable.
  • CAN Communication Wiring: Connect the S+/S0/S- terminals of the inverter to the CAN communication ports of other inverters using twisted pair or shielded cable.

2. Parameter Settings

  • Communication Parameters: Set F8.00 (local address), F8.01 (RS485 communication baud rate setting), F8.02 (RS485 data format setting), etc., to ensure normal communication between inverters.
  • Multi-Pump Networking Mode: Set F0.20 (multi-pump macro debugging function) to select the corresponding multi-pump networking mode (e.g., master, slave, etc.).
  • Network Mode: Set F1.02 (multi-pump network mode selection) to define the network role of each inverter (e.g., master, slave, etc.).
  • Slave Settings: Set F1.00 (multi-pump networking communication address) on the slave to ensure each slave has a unique address.
  • Other Parameters: Set the number of multi-pump networking slaves (F1.03), multi-pump operation mode (F1.04), etc., according to actual needs.

IV. Fault Codes and Solutions

The PDG10 series SANJ INVERTER features comprehensive fault protection functions. When a fault occurs, the corresponding fault code will be displayed. Below are some common fault codes, their meanings, and solutions:

  • E002: Overcurrent during acceleration. Possible causes include too fast acceleration, low grid voltage, or undersized inverter. Solutions include increasing acceleration time, checking the input power supply, or selecting a larger inverter.
  • E015: External fault. Possible causes include activation of the external fault input terminal. The solution is to check whether the external device input is normal.
  • E027: Water shortage alarm. Possible causes include abnormal water pressure/level, disconnected or poorly contacted sensors, etc. Solutions include checking the water inlet pressure of the water pump, sensor installation and wiring, and related parameter settings.
  • E050: Multi-pump communication error. Possible causes include abnormal multi-pump communication or duplicate networking addresses. Solutions include power cycling, checking CAN networking communication address settings, or seeking service support.

When a fault occurs, first refer to the fault code to identify the possible cause and follow the corresponding solution. If the problem cannot be resolved, contact a professional technician for further inspection and repair.

Summary

The PDG10 series SANJ INVERTER, as a dedicated product for water pump control, features powerful functionality, easy operation, and high reliability. Through reasonable wiring and parameter settings, it can achieve various application modes such as single-pump constant pressure water supply, one-to-two timed rotation control, and multi-pump networking control. Additionally, the inverter provides comprehensive fault protection functions and fault code prompts, facilitating fault diagnosis and handling for users. It is hoped that this usage guide will help users better understand and use the PDG10 series SANJ INVERTER.

Posted on Leave a comment

LCGK (ZTV) Inverter LC400E Series Manual Operation Guide

I. Introduction

The LCGK (ZTV) LC400E series high-performance vector inverter boasts remarkable performance and flexible control functions, making it widely applicable in textile, paper, wire drawing, machine tools, packaging, food processing, fans, pumps, and other automated production equipment. This article aims to provide users with a detailed operation guide for the LC400E series inverter, covering panel function introductions, parameter initialization, password setting and removal, terminal start/stop operations, external potentiometer speed adjustment, and fault code analysis and troubleshooting methods.

ATV INVERTER operation panel function diagram

II. Inverter Panel Function Introduction

The LC400E series inverter is equipped with an intuitive and user-friendly operation panel. The primary function keys include the Programming Key (PRG), Enter Key (ENTER), Increment Key (Δ), Decrement Key (∨), Run Key (RUN), Stop/Reset Key (STOP/RES), and Multi-Function Key (MF.K). These keys allow users to easily modify parameters, monitor operating status, and control the inverter.

  • Programming Key (PRG): Used to enter or exit the function parameter settings interface.
  • Enter Key (ENTER): Used to confirm parameter settings or enter the next menu level.
  • Increment Key (Δ) and Decrement Key (∨): Used to modify parameter values or select function codes.
  • Run Key (RUN): Used to start the inverter.
  • Stop/Reset Key (STOP/RES): Used to stop the inverter or reset fault alarms.
  • Multi-Function Key (MF.K): Achieves different function switches based on the P7-00 parameter setting.

III. Parameter Initialization and Password Setting

Parameter Initialization

Parameter initialization restores all inverter parameters to their factory default settings. This function is useful when clearing user-defined settings or troubleshooting parameter errors. The specific operation steps are as follows:

  1. Enter the function parameter settings interface (press the PRG key).
  2. Find and modify the PP-01 parameter, setting it to 01 (restore factory parameters, excluding motor parameters) or 02 (clear record information).
  3. Press the ENTER key to save the settings and exit the parameter settings interface.

Password Setting and Removal

To prevent unauthorized modification of inverter parameters, users can set a password. The steps for setting and removing the password are as follows:

  • Password Setting:
    1. Enter the function parameter settings interface.
    2. Modify the PP-00 parameter, setting it to a non-zero value (the password).
    3. Press the ENTER key to save the settings.
  • Password Removal:
    1. Enter the function parameter settings interface.
    2. Set the PP-00 parameter to 0.
    3. Press the ENTER key to save the settings.
LCGK INVERTER LC400E Wiring Diagram

IV. Terminal Start/Stop and External Potentiometer Speed Adjustment

Wiring Terminals

To achieve terminal start/stop and external potentiometer speed adjustment, it is necessary to correctly wire the control terminals of the inverter. Commonly involved terminals include digital input terminals (DI1, DI2, etc.), analog input terminals (AI1, AI2, etc.), and run control terminals (such as RUN, STOP, etc.).

Parameter Settings

  1. Terminal Start/Stop:
    • Set the P0-02 parameter to 1 to select the terminal command channel.
    • According to requirements, set DI1, DI2, and other digital input terminals to forward rotation (P4-00=1), reverse rotation (P4-01=2), and stop (e.g., P4-02=3 for the stop terminal in three-wire operation control).
  2. External Potentiometer Speed Adjustment:
    • Set AI1 or AI2 terminals as analog input terminals to receive speed adjustment signals from an external potentiometer.
    • Set the P0-03 parameter to the corresponding analog input source (e.g., AI1 or AI2).
    • Adjust parameters such as P3-01 (torque boost) and P3-02 (torque boost cutoff frequency) as needed to achieve better speed adjustment performance.

V. Fault Code Meaning Analysis and Troubleshooting Methods

During operation, if the LC400E series inverter encounters a fault, it will immediately stop outputting and display the corresponding fault code. Users can quickly locate the problem and take corresponding measures based on the fault code. Below are the meanings and troubleshooting methods for some common fault codes:

  • Err01 (Inverter Unit Protection): Possible causes include output circuit short circuit, module overheat, etc. Solutions include checking and eliminating peripheral faults, cleaning the air duct, replacing the fan, etc.
  • Err02 (Acceleration Overcurrent): Possible causes include too short an acceleration time, low voltage, etc. Solutions include increasing the acceleration time, adjusting the voltage to the normal range, etc.
  • Err03 (Deceleration Overcurrent): Similar to acceleration overcurrent, possible causes include too short a deceleration time, low voltage, etc. Solutions include adjusting the deceleration time and voltage accordingly.
  • Err04 (Constant Speed Overcurrent): Possible causes include sudden load changes during operation, undersized inverter selection, etc. Solutions include eliminating sudden load changes, selecting an inverter with a higher power rating, etc.

In addition, there are various other fault codes, such as Err05 (Acceleration Overvoltage), Err06 (Deceleration Overvoltage), Err07 (Constant Speed Overvoltage), etc. Each fault code corresponds to specific possible causes and solutions. When encountering a fault, users should first refer to the fault information list in the manual for troubleshooting.

VI. Conclusion

The LCGK (ZTV) LC400E series high-performance vector inverter provides users with efficient and reliable automation solutions through its powerful functions and flexible control methods. Through this operation guide, users can better understand and use this series of inverters to achieve more precise and stable control effects. In practical applications, users should also consider specific application scenarios and requirements, reasonably set parameters, and regularly perform maintenance to ensure the long-term stable operation of the inverter.

Posted on Leave a comment

ENC INVERTER EDS1000 User Manual Usage Guide

I. Introduction to Inverter Panel Functions

The ENC INVERTER EDS1000’s panel integrates various control functions, allowing users to easily start, stop, and adjust the speed of the inverter. The main keys on the panel include:

ENC INVERTER EDS1000 Operation Panel Function Diagram
  • RUN: Forward operation key. Pressing this key will start the inverter to run forward at the set frequency.
  • STOP/RESET: Stop/Reset key. In normal operation, pressing this key will stop the inverter’s output; in fault mode, pressing this key will reset the inverter.
  • REV JOG: Reverse/Jog key. Depending on the setting of parameter F0.03, this key can be used as a reverse operation key or a jog operation key.
  • Analog Potentiometer: Used to manually adjust the inverter’s output frequency by rotating it, enabling speed control.

Steps to Achieve Panel Start/Stop and Speed Adjustment:

  1. Start the Inverter: Press the RUN key, and the inverter will start running at the currently set frequency and direction.
  2. Stop the Inverter: Press the STOP/RESET key, and the inverter will stop outputting.
  3. Speed Adjustment: Rotate the Analog Potentiometer on the panel to adjust the inverter’s output frequency in real-time, thereby achieving speed control.

II. Guide to Using the Simple PLC Function

The EDS1000 inverter provides a simple PLC function, allowing users to set different stages and corresponding times to automatically adjust the frequency and direction of the inverter within a cycle.

Terminal Connections:

  • FWD: Forward control terminal.
  • REV: Reverse control terminal.
  • COM: Common terminal, used in conjunction with the FWD or REV terminal.
  • X1-X8: Multifunctional input terminals, which can be used to set different stage controls.
ENC INVERTER EDS1000 Series Wiring Diagram

Parameter Settings:

  1. F4.00: Simple PLC operation settings. Select the operation mode as needed (e.g., stop after a single cycle, continuous cycle, etc.).
  2. F4.01-F4.14: Set the frequency, direction, and operation time for each stage. For example, F4.01 sets the frequency and direction for the first stage, and F4.02 sets the operation time for the first stage.

Implementation Steps:

  1. Set the frequency, direction, and operation time for each stage through the F4 group parameters based on actual requirements.
  2. Connect the FWD and REV terminals to the corresponding control signals to control the forward and reverse rotation of the inverter.
  3. Connect the X1-X8 multifunctional input terminals as needed to trigger different stages.
  4. Start the inverter, and the simple PLC function will automatically adjust the inverter’s frequency and direction according to the set stages and times.

III. Setting the Swing Frequency Function

The swing frequency function is a special variable frequency operation mode that periodically varies the output frequency of the inverter within a certain range by setting parameters such as swing frequency amplitude and period.

Parameter Settings:

  • F6.00: Swing frequency function selection. Set to 1 to enable the swing frequency function.
  • F6.01: Swing frequency operation mode. Select the swing frequency input mode (automatic or manual) and amplitude type (variable amplitude or fixed amplitude).
  • F6.02: Swing frequency amplitude. Set the amplitude of the swing frequency.
  • F6.03: Jump frequency. Set the jump frequency at the start of swing frequency.
  • F6.04: Swing frequency period. Set the time for one complete cycle of swing frequency.

Setting Steps:

  1. Set parameter F6.00 to 1 to enable the swing frequency function.
  2. Set parameter F6.01 as needed, selecting the swing frequency operation mode and amplitude type.
  3. Set parameter F6.02 to determine the amplitude of the swing frequency.
  4. Adjust the jump frequency and swing frequency period by setting parameters F6.03 and F6.04 as needed.
  5. Start the inverter, and the swing frequency function will operate according to the set parameters.

IV. Fault Codes and Handling Methods

The EDS1000 inverter provides extensive fault codes to help users quickly locate and resolve faults. Below are some common fault codes, their meanings, and handling methods:

  • E001: Overcurrent during inverter acceleration. Possible causes include too short an acceleration time, an inappropriate V/F curve, etc. Handling methods include extending the acceleration time, adjusting the V/F curve, etc.
  • E002: Overcurrent during inverter deceleration. Possible causes include too short a deceleration time, potential energy load or large inertia load, etc. Handling methods include extending the deceleration time, increasing external energy dissipation braking components, etc.
  • E008: Inverter overload. Possible causes include too short an acceleration time, excessive DC braking, etc. Handling methods include extending the acceleration time, reducing the DC braking current, etc.
  • E010: Inverter overheat. Possible causes include blocked air ducts, excessively high ambient temperature, etc. Handling methods include cleaning the air ducts, improving ventilation conditions, etc.
  • E013: Inverter module protection. Possible causes include instantaneous overcurrent of the inverter, phase-to-phase or ground short circuit in the output three-phase, etc. Handling methods include checking and reconnecting wires, replacing damaged components, etc.

When the inverter encounters a fault, users should first check the possible causes based on the fault code and troubleshoot according to the provided handling methods. If the issue cannot be resolved, users should promptly contact the manufacturer or a professional technician for assistance.

Conclusion

The ENC INVERTER EDS1000 User Manual provides a detailed usage guide, covering panel function introductions, simple PLC function usage, swing frequency function settings, and fault code handling methods. By carefully reading the manual and following the guide, users can fully leverage the inverter’s capabilities to achieve efficient and stable variable frequency control.

Posted on Leave a comment

Instruction Guide and Fault Handling for IS620P Series Servo System by Inovance

Inovance IS620P Series Servo System Instruction Guide

1. Setting Up Speed Mode with External Terminal Start and Potentiometer Speed Regulation

Parameter Settings

To configure the Inovance IS620P series servo system for speed mode control with external terminal start and potentiometer speed regulation, the following parameters need to be set:

  • H02-00: Set to 0 to select speed control mode.
  • H06-00: Set to 1 to select AI1 as the speed command source. If AI2 is used, set to 2.
  • H06-02: Set to 0 to select the main speed command A as the speed source.
  • H03-50 to H03-59: Configure the offset, gain, and other parameters of the AI1 channel according to the potentiometer’s voltage range to ensure a linear relationship between the potentiometer’s output voltage and the speed command.
  • H06-05 and H06-06: Set the acceleration and deceleration times for the speed command to ensure smooth start and stop.

Terminal Connections

  • AI1 Terminal: Connect the output of the potentiometer to receive the speed regulation signal.
  • DI1 Terminal: Set to servo enable (FunIN.1: S-ON) and connect to an external start signal.
  • Other DI Terminals: Configure other functions as needed, such as direction control and external reset.

2. Jog Operation

Parameter Settings

  • H06-04: Set the jog speed, typically in rpm.
  • H0D-11: Jog test run function entry code, which allows jog test runs to be performed through the panel settings.

Operation Steps

  1. Access the parameter settings interface through the panel.
  2. Set H06-04 to the desired jog speed.
  3. Use the jog buttons on the panel or activate jog operation through external DI terminals (such as FunIN.18 and FunIN.19).
  4. Control the direction and stopping of the jog operation through the panel or external signals.

3. CANOPEN Communication Setup

Hardware Connection

  • Connect the CAN interface of the servo drive to the CAN interface of the upper computer using shielded twisted pair cables.
  • Ensure that the shielding layer of the connecting cable is properly grounded to reduce interference.

Parameter Settings

  • H0C-00: Set the servo axis address to ensure each drive has a unique address.
  • H0C-08: Set the CAN communication rate to match the upper computer.
  • H0C-09: Enable communication VDI.
  • H17 Group Parameters: Configure virtual DI and DO functions as needed.
er.630 fault

Fault Code Meanings and Handling Methods for Inovance Servo IS620P Series

Fault Code er.630

Meaning

The er.630 fault code indicates motor stall overtemperature protection. When the motor stalls due to excessive load or mechanical obstruction during operation, and the motor temperature rises to a certain level, the servo drive will report this fault.

Solution

  1. Check Mechanical Load: Confirm whether there is any obstruction or excessive load in the mechanical part and address it promptly.
  2. Adjust Gain Parameters: Adjust the speed loop and position loop gain parameters according to the mechanical load to prevent the motor from stalling due to excessive gain.
  3. Increase Acceleration and Deceleration Time: Increase the settings of H06-05 and H06-06 to make the motor start and stop more smoothly, reducing the possibility of stalling.
  4. Check Motor and Drive Connections: Ensure that the connections between the motor and the drive are correct to avoid stalling caused by wiring errors.
  5. Monitor Motor and Drive Status: Use the Inovance drive debugging platform to monitor the motor’s operating status and the drive’s output commands to identify any anomalies.
IS620P Huichuan servo physical picture

If the above methods fail to resolve the issue, it may be necessary to replace the servo drive or motor with a higher capacity to accommodate the current load demand. Additionally, when handling faults, ensure safe operation to prevent personnel injury or equipment damage.

By following the above setup and fault handling methods, users can effectively use and maintain the Inovance IS620P series servo system, ensuring its stable and efficient operation.

Posted on Leave a comment

MIKOM Inverter MV Series User Guide and ER.03 Fault Cause Analysis and Solution

I. Introduction to MIKOM Inverter MV Series Operation Panel Functions

The MIKOM Inverter MV series features a comprehensive operation panel with LED display, indicators, multi-function MK key, programming keys, increment/decrement keys, stop/reset key, and run key.

Mikom inverter physical picture

1. LED Display Area

  • Displays current set frequency, output frequency, output voltage, output current, and other parameters.

2. Indicators

  • FWD: Forward/Reverse Indicator. Lit indicates reverse operation; off indicates forward operation or stop.
  • COMD: Command Channel Indicator. Lit indicates operation panel control; flashing indicates serial communication control; off indicates terminal control.
  • ALM: Fault Indicator. Lit indicates fault status; flashing indicates alarm status.
  • RUN: Run Status Indicator. Lit indicates running; off indicates stop.

3. Function Keys

  • MK Key: Multi-function key, whose function is defined by parameter P50.03.
  • Programming Key: Enters or exits the menu.
  • Increment/Decrement Keys: Increment or decrement data or function codes.
  • Stop/Reset Key: Stops operation during running and resets during fault alarm.
  • Run Key: Initiates operation in keyboard operation mode.

4. Restoring Factory Defaults

  • Set parameter P50.20 to 22, then press the run key to restore factory defaults.

5. Panel Start/Stop and Speed Adjustment Settings

  • Set P00.01 to 0 to select the operation panel control command channel.
  • Use the increment and decrement keys on the operation panel for speed adjustment.
Mikom inverter has an ER.03 fault

II. Terminal Start/Stop and Potentiometer Speed Adjustment Settings

1. Terminal Connections

  • Terminals to be connected include: run command terminals (e.g., FWD, REV), speed reference terminals (e.g., AI1, AI2), and common terminals (e.g., COM).

2. Parameter Settings

  • Set P00.01 to 1 to select the terminal run command channel.
  • Set P00.02 to the corresponding analog input channel (e.g., AI1 given).
  • Configure the functions of each terminal as needed in P10 group parameters.

3. Speed Adjustment Settings

  • Connect an external potentiometer to the speed reference terminal (e.g., AI1) and common terminal (e.g., COM) to adjust the speed by turning the potentiometer.

III. Fault Codes and ER.03 Fault Analysis

1. Fault Codes

The MIKOM Inverter MV series has comprehensive fault protection functions. Common fault codes include:

  • ER.01: Overcurrent Protection
  • ER.02: Overvoltage Protection
  • ER.03: Constant Speed Overcurrent
  • ER.04: Undervoltage Protection
  • ER.05: Overload Protection
  • ER.06: Overheat Protection
  • ER.07: Module Protection
  • ER.08: Phase Loss Protection
  • ER.09: External Reference Lost
  • ER.10: Excessive Speed Deviation

2. ER.03 Fault Analysis

ER.03 indicates a constant speed overcurrent fault, typically occurring when the inverter’s output current exceeds the rated current limit. This fault can be caused by:

  • Excessive motor load or mechanical blockage.
  • Incorrect motor parameter settings, leading to excessive inverter output current.
  • Inverter internal drive board fault, such as poor IGBT conduction or defective drive optocouplers.

3. Handling and Repair Methods

  • Check Load and Mechanical Parts: Ensure the motor load is normal and there is no mechanical blockage.
  • Check Motor Parameter Settings: Ensure motor parameters (e.g., rated power, rated current) are set correctly.
  • Check Drive Board: If the above two items are normal, the fault may be in the inverter’s internal drive board. Professional maintenance personnel are required for inspection and repair, replacing damaged IGBTs or drive optocouplers as necessary.

When handling ER.03 faults, always ensure power-off operation to avoid electrical shock hazards. Regular maintenance and inspection of the inverter are recommended to promptly identify and address potential faults, ensuring the normal operation of the inverter.

The MIKOM Inverter MV series is widely used in multiple industries due to its high performance and reliability. By correctly setting and operating panel functions, reasonably wiring and configuring parameters, and promptly and effectively handling faults and maintenance, the performance advantages of the inverter can be fully utilized, improving production efficiency and equipment reliability.

Posted on Leave a comment

Understanding and Solving A5001 Alarm Fault in ABB ACS510/ACS550/ACH550 Series Drives

When using ABB’s ACS510, ACS550, and ACH550 series of Drives, users may encounter the “A5001” alarm fault. This fault typically indicates that there is no response from the drive, meaning the operator panel is unable to read information from the main board despite being powered on and displaying. This article will provide a detailed analysis of the A5001 alarm fault based on ABB’s ACS510 manual and practical experience, along with targeted solutions.

ACS510 generates A5001 alarm

I. Overview of A5001 Alarm Fault

When the ABB ACS510/ACS550/ACH550 series of drives displays the “A5001” alarm, the operator panel usually shows this error code, and pressing any button has no effect. According to the ABB manual, the A5001 alarm represents “No Response from Drive,” indicating that although the operator panel is powered on and displaying, it is unable to communicate with the main board.

II. Analysis of Fault Causes

1. Operator Panel Failure

The operator panel itself may have issues, such as damage to the communication interface with the main board. In this case, even though the operator panel is powered on and displaying, it cannot exchange data with the main board.

2. Connection Cable Issues

The connection cable between the operator panel and the main board uses a network cable format. If the connectors on the cable are not properly seated or the cable is internally damaged, communication will be interrupted.

3. Main Board Failure

Main board failures are also a common cause of the A5001 alarm. Damage to the CPU chip or other key components on the main board will prevent it from functioning normally, thereby disrupting communication with the operator panel.

4. Fan Failure

If the fan is damaged or not rotating, it may affect the operating voltage of the main board, causing it to malfunction. While this scenario is less common, it still needs to be considered.

5. Power Board Issues

Although less frequently encountered in practice, abnormal power supply from the power board can also trigger the A5001 alarm. In such cases, the 10VDC and 24VDC voltages on the power board can be measured to confirm its functionality.

Internal diagram of ABB VFD

III. Fault Solutions

1. Replace the Operator Panel

If the operator panel itself is suspected to be the problem, a spare operator panel can be tried. Before replacement, ensure that the new panel is compatible with the inverter model.

2. Check and Replace the Connection Cable

Inspect the connection cable between the operator panel and the main board for any damage. If the cable is damaged or the connectors are not properly seated, replace the cable or remake the connectors. To rule out cable issues, the operator panel can be directly connected to the main board’s socket for testing.

3. Replace the Main Board

If it is confirmed that the main board is faulty, it needs to be replaced. Before replacing the main board, back up the parameter settings on the original board and reconfigure them on the new board to ensure the inverter functions normally.

4. Check and Replace the Fan

If fan failure is suspected, temporarily disconnect the fan’s working plug and conduct a power-on test. If the fault disappears after removing the fan, it indicates that the fan is indeed defective and needs to be replaced.

5. Check the Power Board

Although less common, power board issues cannot be ruled out. The 10VDC and 24VDC voltages on the power board can be measured to confirm its normal operation. If abnormal voltages are detected, further inspection of the power board or contact with professional maintenance personnel is recommended.

ABB VFD fan replacement

IV. Conclusion

When encountering the A5001 alarm fault in ABB’s ACS510/ACS550/ACH550 series of drives, users should first preliminarily diagnose the fault cause based on the fault symptoms and manual content. Then, they can follow the solutions provided in this article to troubleshoot and resolve the issue step by step. During troubleshooting, safety precautions should be taken to avoid further damage to the inverter. Additionally, users are advised to regularly maintain and service the inverter to reduce the likelihood of faults occurring.

Through the detailed analysis and solutions provided in this article, we hope to help users better understand and handle the A5001 alarm fault in ABB’s ACS510/ACS550/ACH550 series of drives, ensuring their normal operation and production efficiency.

Posted on Leave a comment

User Manual Guide for Yuqiang Inverter YQ3000-G11 Series

I. Introduction to Operation Panel Functions

The Yuqiang Inverter YQ3000-G11 series operation panel integrates multiple functions, facilitating parameter setting and status monitoring for users. The panel mainly includes the following parts:

Function diagram of Yuqiang INVERTER operation panel
  • Status Indicators: Including RUN/TUNE (running status), FWD/REV (forward/reverse indication), LOCAL/REMOT (local/remote operation indication), and TRIP (fault indication). These indicators visually display the current status of the inverter.
  • Unit Indicators: Used to indicate the currently displayed unit, such as Hz (frequency), RPM (rotational speed), A (current), etc.
  • Digital Display Area: A 5-digit LED display area used to display set frequency, output frequency, alarm codes, and other information.
  • Analog Potentiometer: Equivalent to Al1, used to adjust the frequency.
  • Button Area: Including PRG/ESC (program/exit), DATA/ENT (confirm), UP (increment), DOWN (decrement), SHIFT (right shift), RUN (run), STOP/RST (stop/reset), and QUICK/JOG (quick multifunction) buttons for parameter setting and function operation.

Setting and Eliminating Passwords

  1. Setting a Password:
    • Enter the function code editing state, locate the P07.00 parameter, and set a non-zero value as the user password.
    • After exiting the function code editing state, the password protection will take effect.
  2. Eliminating a Password:
    • Re-enter the function code editing state and set the P07.00 parameter to 0.
    • After exiting the function code editing state, the password protection will be canceled.

Restoring Default Parameters

  • Enter the function code editing state, locate the P00.18 parameter, and set it to 1.
  • The inverter will automatically restore the default parameter settings and clear the user password.
Wiring diagram of control circuit for Yuqiang INVERTER

II. Terminal Start/Stop Mode and External Potentiometer Speed Adjustment Mode Settings

Wiring Instructions

  • Terminal Start/Stop Mode:
    • Connect external control signals to the multifunction input terminals of the inverter, such as FWD (forward), REV (reverse), and RUN/STOP terminals.
    • Specific wiring should be done according to control requirements, referring to the wiring diagram.
  • External Potentiometer Speed Adjustment Mode:
    • Connect the output signal of the external potentiometer to the analog input terminals of the inverter, such as Al1 or Al2.
    • Adjust the output range of the potentiometer to match the input requirements of the inverter.

Parameter Settings

  1. Terminal Start/Stop Mode:
    • Set the P00.01 parameter to 1 to select the terminal operation command channel.
    • Set the functions of S1~S8 multifunction terminals as needed, such as setting S1 as forward operation (FWD) and S2 as reverse operation (REV).
  2. External Potentiometer Speed Adjustment Mode:
    • Set the P00.06 or P00.07 parameter to the corresponding analog input channel, such as selecting Al1 as the frequency setting source.
    • Adjust the analog input parameters of the inverter according to the output range of the external potentiometer, such as the lower limit (P05.32) and upper limit (P05.34) of Al1.

III. Alarm Codes and Handling Methods

The Yuqiang Inverter YQ3000-G11 series provides abundant alarm codes to help users quickly locate fault causes. The following are some common alarm codes, their meanings, and handling methods:

  • OC1 (Acceleration Overcurrent): Overcurrent occurs during the acceleration of the inverter.
    • Handling Method: Check if the motor load is too large or appropriately extend the acceleration time.
  • OC2 (Deceleration Overcurrent): Overcurrent occurs during the deceleration of the inverter.
    • Handling Method: Check if the motor load is too large or appropriately extend the deceleration time.
  • OV1 (Acceleration Overvoltage): Overvoltage occurs during the acceleration of the inverter.
    • Handling Method: Check if the power supply voltage is too high or appropriately extend the acceleration time.
  • UV (DC Bus Undervoltage Fault): The DC bus voltage of the inverter is lower than the undervoltage protection setting value.
    • Handling Method: Check if the power supply voltage is normal or if the power supply lines are poorly connected.
  • OL1 (Motor Overload): The operating current of the motor exceeds the overload protection setting value.
    • Handling Method: Check if the motor load is too large or appropriately adjust the overload protection setting value.
  • OL2 (Inverter Overload): The output current of the inverter exceeds the overload protection setting value.
    • Handling Method: Check if the load is too large or if the inverter cooling is adequate.
  • tE (Motor Self-learning Fault): A fault occurs during the motor self-learning process.
    • Handling Method: Check if the motor connection is correct or re-perform motor self-learning.
  • PIDE (PID Feedback Disconnection Fault): The PID feedback signal is lost.
    • Handling Method: Check if the PID feedback line is properly connected or if the feedback sensor is normal.

When the inverter malfunctions, users should quickly locate the fault cause based on the alarm code and troubleshoot and repair it according to the corresponding handling method. At the same time, users should regularly maintain and inspect the inverter to ensure its normal operation.

Through this guide, we hope users can better understand and use the user manual for the Yuqiang Inverter YQ3000-G11 series, achieving efficient and safe inverter operation and maintenance.

Posted on Leave a comment

User Manual Guide for Delta Inverter VFD-B Series

I. Operating Panel Function Description and Parameter Settings

1. Operating Panel Function Description

The Delta Inverter VFD-B series features an intuitive operating panel with various functions and a display screen. The panel includes buttons such as RUN, STOP, ▲ (frequency increase), ▼ (frequency decrease), MODE, and an LCD display to show current operating status and parameter settings.

Function diagram of Delta inverter operation panel

2. Restoring Factory Defaults

To restore the inverter to its factory default settings, follow these steps:

  1. Enter Parameter Setting Mode: Press the MODE button to enter parameter setting mode.
  2. Select User Parameters: Use the ▲ and ▼ buttons to select parameter group 00 (User Parameters).
  3. Select Parameter Reset: Continue using the ▲ and ▼ buttons to select parameter 00-02 (Parameter Reset Setting).
  4. Set Factory Defaults: Set the value of parameter 00-02 to 09 or 10, corresponding to different voltage and frequency factory default settings.
  5. Save and Exit: After confirming the settings, press the DATA button to save and exit parameter setting mode.

3. Setting and Removing Passwords

To protect the inverter’s parameter settings from unauthorized changes, you can set a password:

  1. Enter Password Setting: In parameter setting mode, select User Parameters in parameter group 00, then find parameter 00-08 (Parameter Protection Password Setting).
  2. Enter Password: Use the ▲ and ▼ buttons to input the desired password (00~65535).
  3. Confirm Password: Enter the same password again to confirm.

To remove an existing password, simply set the value of parameter 00-08 back to 00.

II. Terminal Start and External Potentiometer Speed Control Settings

To configure the inverter for terminal start and external potentiometer speed control, you need to set specific parameters and connect certain terminals:

1. Parameter Settings

  1. First Operation Command Source Setting: Set parameter 02-01 to 01, indicating that the operation command is controlled by external terminals.
  2. First Frequency Command Source Setting: Set parameter 02-00 to 01, indicating that the frequency command is controlled by the analog signal (0~10V) input from the external terminal AVI.
  3. Multi-function Input Command Setting: Depending on your needs, set parameters 04-04 to 04-09 to corresponding functions such as forward rotation, reverse rotation, start, stop, etc.

2. Terminal Connections

  1. Power Connection: Connect the inverter’s power terminals R, S, T to the three-phase AC power supply.
  2. Motor Connection: Connect the inverter’s output terminals U, V, W to the three-phase induction motor.
  3. Start and Stop Terminal Connection: Connect the external start button between the FWD terminal and the DCM terminal, and connect the stop button between the REV terminal and the DCM terminal (note that the connection method depends on the two/three-wire mode selection setting).
  4. External Potentiometer Connection: Connect the output of the external potentiometer between the AVI terminal and the GND terminal for speed control.
Delta VFD-B standard wiring diagram for frequency converters

III. Fault Codes, Their Meanings, and Solutions

The Delta Inverter VFD-B series will display corresponding fault codes when a fault occurs, allowing users to quickly locate the problem. Below are some common fault codes, their meanings, and solutions:

  1. OC (Overcurrent): Indicates that the output current of the inverter exceeds the rated value.
    • Solution: Check if the motor is overloaded, verify the motor wiring is correct, and adjust the acceleration and deceleration time parameters.
  2. OV (Overvoltage): Indicates that the DC bus voltage of the inverter is too high.
    • Solution: Check if the input power supply voltage is too high, ensure the braking resistor is connected correctly, and adjust the overvoltage protection parameters.
  3. OH (Overheat): Indicates that the internal temperature of the inverter is too high.
    • Solution: Check if the inverter installation environment is well-ventilated, ensure the cooling fan is working properly, reduce the load, or increase cooling measures.
  4. OL (Overload): Indicates that the motor is overloaded.
    • Solution: Check if the motor is operating under overload conditions, adjust the load, or increase the motor capacity.
  5. EF (External Fault): Indicates that an external fault signal has been input.
    • Solution: Check the source of the external fault signal and resolve the external fault.
  6. CF (Communication Fault): Indicates a communication anomaly.
    • Solution: Check if the communication lines are connected correctly and ensure the communication parameter settings are correct.

By following these steps, users can effectively use the Delta Inverter VFD-B series, including operating the panel, setting parameters, configuring functions, and troubleshooting faults. These operations will help users better control and maintain the inverter, ensuring its normal operation.

Posted on Leave a comment

User Manual Guide for Inovance Inverter MD380 Series

I. Introduction to the Operation Panel Functions and Parameter Settings

1.1 Operation Panel Functions

The operation panel of the Inovance MD380 series inverter is a crucial tool for users to set parameters, monitor status, and diagnose faults. The operation panel primarily consists of an LED display, function keys, and multiple input/output ports. The LED display shows current operating parameters such as frequency, voltage, and current. The function keys include PRG (Program), ENTER (Confirm), RUN (Run), STOP/RESET (Stop/Reset), and MF.K (Multi-Function Key), which users utilize for menu navigation and parameter modification.

1.2 Restoring Factory Defaults

Restoring factory defaults clears user-defined parameters, resetting the inverter to its default settings at the time of manufacture. The steps are as follows:

  1. Enter the Function Parameter Mode: Press the PRG key to enter the function parameter mode.
  2. Select the FP Group Function Code: Use the ▲ or ▼ keys to select the FP group function code (FP-01).
  3. Set to Restore Factory Defaults: Press the ENTER key to enter the FP-01 parameter setting, set the value of FP-01 to 1, and then press ENTER to confirm. The inverter will then automatically restart and restore to its factory default settings.

1.3 Setting and Clearing Passwords

Password protection prevents unauthorized users from modifying inverter parameters. The steps to set and clear passwords are as follows:

  1. Setting a Password: Set the value of the FP-00 function code to a non-zero number, such as 1234, and then press ENTER to confirm. Password protection is now enabled, and entering the function parameter mode will require a password.
  2. Clearing the Password: Set the value of the FP-00 function code to 0 and then press ENTER to confirm. This disables password protection, and entering the function parameter mode will no longer require a password.
Function Description Diagram of Huichuan MD380 Series Inverter Operation Panel

II. Terminal Start/Stop and External Potentiometer Speed Adjustment Settings

2.1 Wiring Instructions

To achieve terminal start/stop and external potentiometer speed adjustment, the control terminals of the inverter must be correctly connected. The specific wiring is as follows:

  • Start Terminal (DI1): Connect one end of the external start button to DI1 and the other end to the common terminal (COM).
  • Stop Terminal (DI2): Connect one end of the external stop button to DI2 and the other end to the common terminal (COM).
  • Speed Adjustment Terminal (AI1): Connect the center tap of the external potentiometer to AI1, and the two ends of the potentiometer to +10V and GND, respectively.

2.2 Parameter Settings

After completing the wiring, the inverter must be configured with specific parameters to achieve the desired functionality. The settings are as follows:

  1. Set the Command Source: Set the value of the F0-02 function code to 1 to select the terminal command channel.
  2. Set DI1 and DI2 Functions: Set the value of the F4-00 function code to 1 (forward operation) and the value of the F4-01 function code to 4 (reverse operation) or as required.
  3. Set AI1 Function: Configure the F4-13 to F4-16 function codes to set the input range and corresponding set values for AI1, ensuring that the output of the external potentiometer matches the frequency setting of the inverter.
  4. Other Related Settings: Set parameters such as acceleration and deceleration times and frequency limits as needed.
Basic wiring diagram of Huichuan MD380 series frequency converter

III. Fault Codes and Troubleshooting

3.1 Fault Codes and Their Meanings

The Inovance MD380 series inverter features comprehensive fault self-diagnosis functionality. When a fault occurs, the inverter displays the corresponding fault code. Common fault codes and their meanings are as follows:

  • Err01: Overcurrent fault, indicating that the inverter output current exceeds the set value.
  • Err02: Overvoltage fault, indicating that the inverter input voltage is too high.
  • Err03: Undervoltage fault, indicating that the inverter input voltage is too low.
  • Err07: Overload fault, indicating that the inverter output torque exceeds the set value.
  • Err11: Motor overload fault, indicating that the motor current is too high.
  • Err12: Input phase loss fault, indicating that the inverter input power supply is missing a phase.
  • Err15: External fault, indicating that the external fault input terminal is active.
  • Err16: Communication abnormality fault, indicating that communication between the inverter and the host computer is abnormal.

3.2 Troubleshooting

Different fault codes require specific troubleshooting steps:

  • Overcurrent Fault (Err01): Check if the motor and load are too large, and adjust the acceleration and deceleration times or reduce the output frequency.
  • Overvoltage Fault (Err02): Check if the input power supply voltage is too high or install a braking resistor to dissipate excess energy.
  • Undervoltage Fault (Err03): Check if the input power supply voltage is too low or if the power supply line connection is poor.
  • Overload Fault (Err07): Check if the load is too large and adjust the overload protection parameters.
  • Motor Overload Fault (Err11): Check if the motor is stalled or the load is too large, and adjust the motor overload protection parameters.
  • Input Phase Loss Fault (Err12): Check if the input power supply is missing a phase or if the power supply line connection is good.
  • External Fault (Err15): Check if the external fault input terminal is misconnected or damaged and eliminate the external fault source.
  • Communication Abnormality Fault (Err16): Check if the communication line is connected correctly or replace the communication cable.

By following the steps outlined above, users can gain a comprehensive understanding of the operation panel functions, parameter setting methods, terminal start/stop and external potentiometer speed adjustment settings, as well as fault code troubleshooting for the Inovance MD380 series inverter, thereby enabling better use and maintenance of the inverter equipment.

Posted on Leave a comment

User Manual Guide for Inovance CS700 Series Crane-specific Inverter

I. Operation Panel Function Description and Basic Operations

Operation Panel Functionality

The Inovance CS700 series crane-specific inverter is equipped with an intuitive and user-friendly operation panel, which primarily includes the following buttons and indicators:

  • Buttons: Including PRG (programming key), ENTER (confirmation key), increment key (▲), decrement key (▼), shift key (◀/▶), RUN (run key), STOP/RES (stop/reset key), MF.K (multi-function key), QUICK (menu key), etc.
  • Indicators: Including RUN (run indicator), LOCAL/REMOT (command source indicator), FWD/REV (forward/reverse indicator), TUNE/TC (tuning/torque control/fault indicator), etc.

Basic Operations

Function diagram of Huichuan CS700 crane dedicated VFD operation panel
  1. Start and Stop:
    • Press the RUN button to start the inverter, and the inverter run indicator (RUN) will light up.
    • Press the STOP/RES button to stop the inverter, and the inverter run indicator will go out.
  2. Speed Regulation:
    • Enter the programming mode by pressing the PRG button, adjust the target frequency using the increment key (▲) and decrement key (▼), and then press the ENTER button to confirm.

Password Setting and Removal

  • Password Setting: Set the password for all function parameters through parameter AF.00, the password for the second-level menu through parameter bF.00, and the password for the third-level menu through parameter FF.00.
  • Password Removal: Set the password parameter to 0 to remove the password protection.

Parameter Initialization

  • Press the PRG button to enter the programming mode, select parameter AF.01 (restore factory parameters for the first-level menu), bF.01 (restore factory parameters for the second-level menu), or FF.10 (restore factory parameters for the third-level menu), and press the ENTER button to confirm.
Typical wiring diagram of Huichuan CS700 crane specific VFD

II. Crane Mode and PG Encoder Feedback Settings

Crane Mode Selection

The CS700 series inverter supports multiple crane modes, generally achieved through the multi-speed function. The specific setting steps are as follows:

  1. Enter the programming mode, select parameter A0.07, and set it to 0 to choose multi-speed as the frequency source.
  2. Set parameters b3.01~b3.05 to define DI1~DI5 as multi-speed selections 1~5, respectively.
  3. Set the corresponding frequency for each speed in parameters b5.00~b5.07.

PG Encoder Feedback Settings

If PG encoder feedback is selected, the following settings and wiring are required:

  1. Parameter Settings:
    • Enter the programming mode, select parameter b1.00, and set it to 1 to choose encoder vector control (closed-loop control mode).
    • Set parameters b2.00 (encoder lines) and b2.01 (encoder type) according to the actual encoder type used.
  2. Wiring:
    • Connect the encoder signal wires to the PG card interface of the inverter, with specific wiring reference to the wiring diagram in the manual.

III. Fault Code Meanings and Solutions

The CS700 series inverter provides a wealth of fault codes to help users quickly locate and resolve issues. Below are some common fault codes, their meanings, and solutions:

  1. Er02: Acceleration Overcurrent
    • Meaning: Grounding or short circuit in the inverter output circuit, or too short acceleration time, etc.
    • Solution: Check the peripheral circuit and eliminate grounding or short circuit faults; increase the acceleration time.
  2. Er03: Deceleration Overcurrent
    • Meaning: Grounding or short circuit in the inverter output circuit, or too short deceleration time, etc.
    • Solution: Check the peripheral circuit and eliminate grounding or short circuit faults; increase the deceleration time.
  3. Er04: Constant Speed Overcurrent
    • Meaning: Grounding or short circuit in the inverter output circuit, or low voltage, etc.
    • Solution: Check the peripheral circuit and eliminate grounding or short circuit faults; adjust the voltage to the normal range.
  4. Er05: Acceleration Overvoltage
    • Meaning: High input voltage, or external force dragging the motor during acceleration, etc.
    • Solution: Adjust the voltage to the normal range; eliminate external force dragging or install braking resistors.
  5. Er08: Control Power Supply Fault
    • Meaning: Input voltage is not within the specified range.
    • Solution: Adjust the voltage to meet the specified requirements.
  6. Er10: Inverter Overload
    • Meaning: Excessive load or motor stall, or undersized inverter selection, etc.
    • Solution: Reduce the load and check the motor and machinery; select an inverter with a larger power rating.
  7. Er11: Motor Overload
    • Meaning: Improper setting of motor protection parameters, or excessive load, etc.
    • Solution: Set the motor protection parameters correctly; reduce the load.
  8. Er12: Input Phase Loss
    • Meaning: Abnormal three-phase input power.
    • Solution: Check and eliminate issues in the peripheral circuitry.
  9. Er14: Module Overheat
    • Meaning: High ambient temperature or blocked air duct, etc.
    • Solution: Lower the ambient temperature and clean the air duct.
  10. Er37: Frequency Direction Anomaly
    • Meaning: The direction of the given running frequency is opposite to that of the motor feedback frequency.
    • Solution: Check the motor parameter settings and adjust parameter bC.02 if necessary.
  11. Er41: Loose Brake Fault
    • Meaning: Error in the input of the loose brake feedback signal.
    • Solution: Check the brake circuit wiring and the function selection of the control panel’s loose brake feedback input point.
  12. Er42: Holding Brake Fault
    • Meaning: Error in the input of the holding brake feedback signal.
    • Solution: Check the brake circuit wiring and the function selection of the control panel’s holding brake feedback input point.

IV. Conclusion

The Inovance CS700 series crane-specific inverter is a powerful and easy-to-operate inverter dedicated to crane equipment. Through this guide, users can quickly master the basic functions of the operation panel, the setting method for crane modes, the configuration steps for PG encoder feedback, and solutions to common fault codes. It is hoped that this user guide will help users better use and maintain the CS700 series inverters, improving the work efficiency and safety of crane equipment.