Posted on Leave a comment

User Manual Operation Guide for SenDao Inverter SD5000 Series

I. Introduction to the Operation Panel

The SenDao Inverter SD5000 series features an intuitive operation panel, facilitating easy operation and monitoring for users. The operation panel includes a display screen, function selection keys, shift keys, confirm keys, run/stop keys, and more.

Function diagram of SD5000 operation panel

Setting and Releasing the Password

To ensure secure operation, the inverter supports password protection. To set a password:

  1. Enter the Password Setting Menu: Press the PRG key to enter the function parameter menu. Navigate to the password setting function code (typically BP-00).
  2. Set the Password: Use the  and  keys to set the desired password value (ranging from 0 to 65535). Press the ENTER key to confirm.

To release the password:

  1. Enter the Password Setting Menu: Press the PRG key and navigate to the password setting function code (BP-00).
  2. Set the Password to Zero: Use the  and  keys to set the password value to 0. Press the ENTER key to confirm.

Setting Parameter Access Restrictions

To restrict access to certain parameters, you can set the parameter modification attribute. To do this:

  1. Enter the Parameter Attribute Setting Menu: Press the PRG key and navigate to the function code for parameter modification attribute (typically BP-04).
  2. Set the Attribute: Use the  and  keys to set the attribute to “unmodifiable” (value 1). Press the ENTER key to confirm.
SD5000 standard wiring diagram

II. Using the Multi-speed Function

The multi-speed function allows the inverter to operate at different preset speeds. To set up a 5-speed configuration, follow these steps:

Terminal Wiring

  1. Connect the Multi-speed Terminals: Connect the required digital input terminals (DI1 to DI5) to the external control signals that will trigger the different speeds.

Parameter Settings

  1. Enter the Multi-speed Setting Menu: Press the PRG key and navigate to the multi-speed setting function codes (typically BC-00 to BC-15).
  2. Set the Speed Values: Use the  and  keys to set the desired speed values for each multi-speed segment (BC-00 to BC-04 for the first 5 speeds). These values are relative to the maximum frequency set in BO-10.
  3. Configure Terminal Function: Navigate to the input terminal function setting function codes (typically B4-00 to B4-09). Set the desired function for the terminals used for multi-speed control (e.g., DI1 to DI5 as multi-speed terminals 1 to 5).

III. Fault Codes and Troubleshooting

The SenDao Inverter SD5000 series provides fault codes to help users quickly identify and troubleshoot issues. Common fault codes include:

  • E-02: Acceleration overcurrent
  • E-03: Deceleration overcurrent
  • E-04: Constant speed overcurrent
  • E-05: Acceleration overvoltage
  • E-06: Deceleration overvoltage
  • E-07: Constant speed overvoltage
  • E-09: Undervoltage fault
  • E-10: Inverter overload
  • E-11: Motor overload
  • E-12: Input phase loss
  • E-13: Output phase loss
  • E-15: External fault
  • E-16: Communication fault

When a fault occurs, the inverter will stop output, and the fault code will be displayed on the operation panel. To troubleshoot, refer to the fault code and the corresponding troubleshooting steps in the user manual.

By following this operation guide, users can effectively utilize the SenDao Inverter SD5000 series for their control needs, ensuring efficient and reliable operation.

Posted on Leave a comment

HOLIP Inverter HLP-A Series User Manual Operation Guide

I. Introduction to Operation Panel Functions and Parameter Settings

HLP-A Front View

The HOLIP Inverter HLP-A series boasts a comprehensive operation panel that allows users to perform parameter settings, monitor operating status, and diagnose faults. The operation panel primarily includes a display screen, directional keys, set keys, run keys, stop keys, and other functional keys.

Setting and Resetting Passwords

To protect against unauthorized modification of inverter parameters, the HLP-A series supports password protection. Users can enable password protection by setting parameter CD010 to 1, at which point all parameters except CD010 become unmodifiable. To reset the password, simply set CD010 back to 0.

Locking Parameters

To prevent non-maintenance personnel from accidentally modifying parameters, users can lock all parameters except CD010 by setting CD010 to 1. Once locked, only the correct password (set through parameter CD011) can unlock the parameters for modification.

HLP-A Side View

Initializing Parameters

When it is necessary to restore the inverter to its factory settings, users can set parameter CD011 to 08 and then press the run and stop keys simultaneously. The inverter will automatically restart and revert to its factory settings.

II. Terminal Forward/Reverse Control and External Potentiometer Frequency Adjustment

Terminal Forward/Reverse Control

HLP-A Operation Panel Function Diagram

The HLP-A series inverter supports forward/reverse control via external terminals. Users need to set the multi-function input terminal FOR to forward (parameter CD050=02) and REV to reverse (parameter CD051=03). Then, by controlling the on/off state of these terminals with external switches, motor forward/reverse control can be achieved.

External Potentiometer Frequency Adjustment

External potentiometer speed control is a commonly used method for variable frequency speed control. Users need to set the inverter’s operation command source to external terminals (parameter CD033=1) and the operation frequency source to external analog (parameter CD034=1). Connect the potentiometer’s center tap to the VI terminal and its ends to the +10V and ACM terminals, respectively. By adjusting the potentiometer’s resistance, the inverter’s output frequency can be changed, thereby achieving motor speed control.

HLP-A Basic Wiring Diagram

III. Fault Codes and Solutions

The HLP-A series inverter features comprehensive fault protection functions. When a fault occurs, the inverter will display the corresponding fault code. Below are some common fault codes, their meanings, and solutions:

E.OC.A (Overcurrent During Acceleration)

Meaning: The inverter experiences overcurrent during acceleration.

Solution: Check for short circuits or partial short circuits in the motor, and ensure good insulation of output wires; extend the acceleration time; check the inverter configuration for reasonableness and increase the inverter capacity if necessary; reduce the torque boost setting.

E.GF.S (Ground Fault)

Meaning: The inverter output is short-circuited to ground.

Solution: Check for short circuits in motor connections and ensure good insulation of output wires; if the fault cannot be resolved, contact the manufacturer for repair.

E.OU.S (Overvoltage During Stopping)

Meaning: The inverter experiences overvoltage during stopping.

Solution: Extend the deceleration time or install a braking resistor; improve the grid voltage quality and check for sudden voltage fluctuations.

E.OL.A (Inverter Overload)

Meaning: The inverter is overloaded.

Solution: Check if the inverter capacity is too small and increase it if necessary; check for stuck mechanical loads; reset the V/F curve.

E.OT.A (Motor Overtorque)

Meaning: The motor experiences overtorque.

Solution: Check for fluctuations in mechanical loads; check if the motor configuration is too small; check for deterioration in motor insulation due to overheating; check for significant voltage fluctuations; check for phase loss; check for increased mechanical loads.

IV. Conclusion

The HOLIP Inverter HLP-A series user manual provides users with detailed operation guides and fault solutions. By understanding the operation panel functions, mastering terminal control and potentiometer speed adjustment methods, and being familiar with fault code meanings and solutions, users can better utilize and maintain the inverter, ensuring its stable operation and extended service life. In practical applications, users should strictly follow the instructions in the manual for operation and maintenance to ensure the performance and safety of the inverter.

Posted on Leave a comment

V&T V6-H Inverter User Manual Guide and Solution to E.FAL Fault

I. Introduction to the V&T V6-H Inverter Operation Panel Functions

E.FAL

1.1 Overview of Operation Panel Functions

The V&T V6-H inverter is equipped with an intuitive and user-friendly operation panel, providing convenient control and monitoring of the inverter’s operations. The operation panel features various buttons and indicators that allow users to perform various tasks such as setting parameters, monitoring operational status, and troubleshooting faults.

1.2 Setting and Resetting Passwords

Setting a Password:

  1. Enter the Password Function Code: Press the PRG button to enter the menu, and navigate to the password function code (P0.00).
  2. Set the Password: Enter the desired four-digit password and confirm it by pressing the PRG button again. The display will show “P.Set” indicating that the password has been successfully set.

Resetting a Password:

  1. Enter the Password Function Code: Press the PRG button to enter the menu, and navigate to the password function code (P0.00).
  2. Enter the Current Password: Enter the current password.
  3. Clear the Password: Set the password to “0000” and confirm by pressing the PRG button twice. The display will show “P.Clr” indicating that the password has been successfully reset.
V6-h standard wiring diagram

1.3 Setting Parameter Viewing Levels

The V6-H inverter provides different menu modes to control the visibility of parameters, allowing users to customize the level of access based on their needs.

Menu Modes:

  • Basic Menu Mode (P0.02 = 0): Displays all parameters.
  • Quick Menu Mode (P0.02 = 1): Displays only commonly used parameters, ideal for quick setup.
  • Non-Factory Default Menu Mode (P0.02 = 2): Displays only parameters that have been changed from their factory defaults.
  • Recent Changes Menu Mode (P0.02 = 3): Displays the last 10 parameters that have been changed.

To change the menu mode, navigate to the function code P0.02, select the desired menu mode, and confirm by pressing the PRG button.

1.4 Restoring Factory Defaults

Restoring the inverter to its factory default settings can be useful when troubleshooting or resetting the inverter to its initial configuration.

Steps to Restore Factory Defaults:

  1. Enter the Function Code for Restoring Defaults: Navigate to the function code P0.01.
  2. Select the Restore Option: Set P0.01 to “2” to restore all parameters (except motor parameters) to their factory defaults. Alternatively, set P0.01 to “5” to restore all parameters, including those in the reserved areas.
  3. Confirm the Operation: Press the PRG button to confirm the setting. The inverter will then restart and load the factory default parameters.
V6-H

1.5 Setting the Maximum Frequency to 3000Hz

The V6-H inverter supports a maximum output frequency of up to 3000Hz, making it suitable for applications requiring high-speed motor control.

Steps to Set the Maximum Frequency:

  1. Enter the Basic Function Parameters: Navigate to the function code P0.11.
  2. Set the Maximum Output Frequency: Enter “3000” and confirm by pressing the PRG button. This sets the maximum output frequency of the inverter to 3000Hz.

II. Implementing Terminal Forward/Reverse Control

The V&T V6-H inverter provides multiple methods for controlling the direction of rotation of the motor, including through terminal inputs. This section describes how to set up terminal forward/reverse control.

2.1 Terminal Configuration for Forward/Reverse Control

To control the motor’s direction of rotation using terminal inputs, the inverter’s control terminals must be properly configured.

Steps to Configure Terminal Forward/Reverse Control:

  1. Identify the Forward and Reverse Terminals: Typically, the forward and reverse terminals are labeled as FWD and REV, respectively.
  2. Set the Terminal Function: Navigate to the function codes P5.00 to P5.06 (corresponding to terminals X1 to X7) in the multi-function input parameters (P5 group). Set the desired terminal (e.g., X1) to function “9” (forward/reverse control).
  3. Connect the Terminals: Connect the forward and reverse control signals from the external control system to the corresponding terminals on the inverter.
  4. Configure the Run Command Source: Ensure that the run command source is set to terminal control (P0.06 = 1). This allows the inverter to respond to the forward and reverse control signals from the terminals.

2.2 Operating the Inverter in Forward/Reverse Mode

Once the terminal configuration is complete, the inverter can be operated in forward/reverse mode by controlling the signals applied to the forward and reverse terminals.

Operating the Inverter:

  • Forward Rotation: Apply a signal to the FWD terminal to start the motor in the forward direction.
  • Reverse Rotation: Apply a signal to the REV terminal to start the motor in the reverse direction.
  • Stopping the Motor: Remove the signal from both the FWD and REV terminals to stop the motor.

By following these steps, users can easily configure and operate the V&T V6-H inverter for terminal forward/reverse control, enabling precise motor control in a wide range of applications.

III. Solution to E.FAL Fault

The E.FAL fault code on the V&T V6-H inverter indicates a problem with the fan, specifically a fan alarm. This fault can occur due to various reasons such as fan malfunction, overheating, or wiring issues.

3.1 Troubleshooting Steps for E.FAL Fault

Steps to Troubleshoot and Resolve E.FAL Fault:

  1. Check the Fan Operation: Visually inspect the inverter’s cooling fan to ensure it is spinning properly. If the fan is not operating, it may need to be replaced.
  2. Check the Fan Wiring: Verify that the fan wiring is correct and free of damage. Loose or damaged wires can prevent the fan from receiving power.
  3. Check the Fan Sensor: The inverter may have a sensor to monitor fan operation. Ensure that the sensor is functioning correctly and not obstructed.
  4. Environmental Conditions: Consider the ambient temperature and ensure that the inverter is not overheating due to poor ventilation or high ambient temperatures.
  5. Reset the Inverter: If no issues are found with the fan or wiring, try resetting the inverter by turning it off and on again. This may clear the fault code if it was caused by a temporary issue.

3.2 Preventive Measures

To prevent future occurrences of the E.FAL fault, consider the following preventive measures:

  • Regular Maintenance: Schedule regular maintenance checks to inspect the fan and other cooling components.
  • Cleanliness: Keep the inverter and its surroundings clean to prevent dust and debris from obstructing the fan or cooling system.
  • Ventilation: Ensure adequate ventilation around the inverter to prevent overheating.
  • Monitoring: Use the inverter’s monitoring features to keep track of operating temperatures and fan status.

By following these guidelines and troubleshooting steps, users can effectively use the V&T V6-H inverter’s operation panel, configure terminal forward/reverse control, and resolve the E.FAL fault when it occurs.

Posted on Leave a comment

Communication Setup Method for Prolet Controller and Yuanxin Inverter YX3000

In modern industrial automation systems, the communication setup between controllers and inverters is crucial for achieving efficient and stable operation. This article will combine the “Prolet Air Compressor Controller and Inverter Communication Setup Manual” and the “Yuanxin Inverter YX3000 Manual” to provide a comprehensive guide on setting up the communication between the Prolet controller and the Yuanxin Inverter YX3000.

Actual working status of Pulet

1. Communication Protocol Description of Prolet Controller

The Prolet controller adopts a communication protocol that is compatible with industry standards, such as MODBUS RTU. This protocol ensures reliable data transmission between the controller and various devices, including inverters. The key features of the Prolet controller’s communication protocol include:

  • Baud Rate: Typically set at 9600 bps, which is a common baud rate for industrial communication.
  • Parity: No parity bit is used to simplify the communication process and reduce errors.
  • Data Bits: 8 data bits are used to ensure sufficient data transmission capacity.
  • Stop Bits: 1 stop bit is employed to mark the end of each data frame.

To establish communication with the Yuanxin Inverter YX3000, the Prolet controller needs to be configured with the appropriate communication parameters, such as the address of the inverter, baud rate, and data format.

2. Communication Protocol Description of Yuanxin Inverter YX3000

The Yuanxin Inverter YX3000 also supports the MODBUS RTU communication protocol, making it compatible with the Prolet controller. The YX3000 offers a wide range of communication settings to meet different application requirements:

  • Communication Interface: Equipped with standard RS485 communication interfaces, the YX3000 can be easily connected to the Prolet controller using shielded twisted-pair cables.
  • Communication Address: Users can set a unique address for each inverter on the network to facilitate multi-inverter communication.
  • Baud Rate and Data Format: The YX3000 supports various baud rates (e.g., 1200, 2400, 4800, 9600, 19200, 38400 bps) and data formats (e.g., 8N1, 8N2).

To establish communication with the Prolet controller, the YX3000 needs to be configured with the same baud rate, data format, and communication address as the controller.

Yuanxin YX3000 physical product

3. Detailed Parameters Required for Communication Between Prolet Controller and YX3000

To set up communication between the Prolet controller and the Yuanxin Inverter YX3000, users need to configure the following detailed parameters on both devices:

  • Communication Address:
    • Prolet Controller: Set the communication address of the YX3000 in the controller’s communication parameters. This address should be unique on the network.
    • YX3000 Inverter: Set the communication address of the inverter to match the address configured in the controller.
  • Baud Rate:
    • Prolet Controller: Set the baud rate to 9600 bps (or other compatible baud rates) in the controller’s communication parameters.
    • YX3000 Inverter: Set the baud rate to 9600 bps (or the same baud rate as the controller) in the inverter’s communication parameters.
  • Data Format:
    • Prolet Controller: Set the data format to 8N1 (8 data bits, no parity, 1 stop bit) in the controller’s communication parameters.
    • YX3000 Inverter: Set the data format to 8N1 (or the same data format as the controller) in the inverter’s communication parameters.
  • Additional Parameters:
    • Prolet Controller: Depending on the specific model and functionality, the controller may require additional communication-related parameters to be configured, such as communication timeout settings, retry intervals, etc.
    • YX3000 Inverter: Similarly, the inverter may also have additional communication parameters that need to be configured, such as communication port settings, communication protocol selection, etc.

After configuring the above parameters, users can test the communication between the Prolet controller and the Yuanxin Inverter YX3000 by sending test commands from the controller and observing the responses from the inverter. If the communication is successful, users can proceed with the integration of the two devices into their industrial automation system.

Posted on Leave a comment

Operation Guide for EURA Inverter E2000 Series User Manual

I. Introduction to Operation Panel Functions and Initialization Settings

The EURA Inverter E2000 series comes equipped with an intuitive and user-friendly operation panel, enabling users to easily set parameters and monitor the inverter’s status. The operation panel typically includes a display screen, direction keys, function keys, and operation control keys.

Restoring Parameter Initialization Settings:

To restore the inverter’s parameters to their factory settings, users need to enter the programming menu and locate function code F160. The specific steps are as follows:

  1. Press the “Mode” key to display the function codes.
  2. Use the “Up” or “Down” key to select function code F160.
  3. Press the “Set” key to enter the setting value interface for F160.
  4. Change the setting value of F160 to 1 and press the “Set” key again to confirm.

At this point, the inverter will begin the initialization process, restoring all parameters to their factory default values.

Setting Passwords and Parameter Locking:

To ensure the security of parameter settings, the E2000 series inverter supports password protection and parameter locking functions. Users can enable or disable password protection by setting function code F107 and set the user password through F100. Once password protection is enabled, users must enter the correct password before modifying parameters.

Setting Reserved Parameter Areas:

The reserved parameter area allows users to save a set of parameters as a macro for quick recall. Users can select the saved macro by setting function code F135 and restore the user macro through F160.

II. Terminal Control and External Input

Terminal Forward/Reverse Control and External Potentiometer Given:

The E2000 series inverter supports forward/reverse control via terminals and frequency given by an external potentiometer. The specific settings are as follows:

  • Forward/Reverse Control: It is necessary to set function codes F200 and F201 to select terminals as the source of start and stop commands. Simultaneously, set F202 to determine the direction of operation.
  • External Potentiometer Given: It is necessary to set function code F203 to select the main frequency source X and choose analog input AI3 (i.e., external potentiometer) as the given source. Additionally, set F422 to select between panel potentiometer and remote panel potentiometer.

For wiring, users need to connect the output terminal of the external potentiometer to the AI3 terminal of the inverter and ensure proper grounding.

Pulse Input/Output Control:

The E2000 series inverter also supports pulse input/output control, suitable for applications requiring high-precision speed control. Users need to set function codes F440 to F449 to configure pulse input parameters such as minimum frequency, maximum frequency, filter constant, etc. Simultaneously, set F450 to F453 to configure pulse output parameters.

For wiring, users need to connect the output terminal of the pulse generator to the FI terminal of the inverter and connect the FO terminal of the inverter to the device receiving the pulse.

III. Fault Code Analysis and Solutions

The EURA Inverter E2000 series is equipped with a comprehensive fault protection mechanism, capable of real-time monitoring and reporting of various faults. Common fault codes include:

  • OC: Overcurrent protection. Possible causes include motor jam, excessive load, etc. Solutions include checking the motor and load, extending acceleration time, etc.
  • OE: DC overvoltage protection. Possible causes include excessive power supply voltage, brake unit failure, etc. Solutions include checking the power supply voltage, inspecting the brake unit, etc.
  • OL1: Inverter overload protection. Possible causes include excessive load, poor heat dissipation, etc. Solutions include reducing the load, improving heat dissipation conditions, etc.
  • OH: Inverter overheat protection. Possible causes include high ambient temperature, fan failure, etc. Solutions include improving ventilation conditions, replacing the fan, etc.

Users can view fault codes through the operation panel and follow the guidance in the manual for troubleshooting and resolution.

IV. Conclusion

The EURA Inverter E2000 series user manual provides a detailed operation guide covering operation panel function introduction, parameter setting, terminal control, fault troubleshooting, and other aspects. By carefully reading the manual and following the guidance, users can easily achieve the installation, commissioning, and maintenance of the inverter. At the same time, the fault code analysis and solutions in the manual also provide strong support for users, helping them quickly resolve issues that may arise during the operation of the inverter.

Posted on Leave a comment

MC Huikai Induction Heater User Guide


Introduction
Induction heaters use electromagnetic induction to convert electrical energy into heat energy and are widely used in metal heating, hardening, annealing, and other industrial processes. The MC Huikai induction heater is known for its fast heating speed, high efficiency, and ease of operation. This guide will provide a detailed overview of the MC Huikai induction heater’s key technical parameters, wiring methods, control parameters, and usage precautions to help users properly install, commission, and maintain the equipment.


I. Key Parameters of the MC Huikai Induction Heater

The performance of the MC Huikai induction heater is influenced by key parameters that directly impact its heating efficiency. Below are the main technical specifications of the device:

  1. Rated Power
    The rated power of the induction heater typically ranges from 10kW to 500kW. Users can select the appropriate power based on the size and heating requirements of the workpiece. Higher power enables faster and more efficient heating, suitable for larger metal workpieces.
  2. Operating Frequency
    The operating frequency of the heater ranges from 20kHz to 80kHz. The frequency affects the heating depth and speed: lower frequencies are better for heating thicker materials, while higher frequencies are suited for quick heating of thinner materials.
  3. Input Voltage
    The input voltage is typically 380V or 660V, depending on the specific model and power requirements. It is essential to confirm the appropriate voltage rating for the equipment to ensure proper operation.
  4. Heating Temperature Range
    The heating temperature range of the MC Huikai induction heater generally extends from ambient temperature up to 1200°C, making it suitable for most metal heating applications. Some models may support even higher temperatures for specialized applications.
  5. Cooling Method
    The induction heater is equipped with a water cooling system to ensure proper heat dissipation and prevent overheating. The cooling water flow rate should be maintained within the recommended range for stable operation.
  6. Control Method
    The system features digital control, allowing users to adjust parameters such as power and temperature via the control panel or external PLC, ensuring precise control of the heating process.

II. Device Parameter Settings and Command Source Selection

The MC Huikai induction heater offers several adjustable parameters for users to fine-tune based on specific heating requirements. Below are the common parameters and their functions:

  1. P0.00: Command Source Selection
    This parameter selects the control command source for the heater. Common options include:
    • 0: External Control
      When this option is selected, the operation of the heater is determined by an external controller or signal source, suitable for integration with other systems.
    • 1: Panel Control
      In this mode, the heater is operated directly from the front panel, ideal for standalone use.
    • 2: RS485 Communication
      This option allows remote control and monitoring through RS485 communication with other devices, such as PLCs or computers.
  2. P0.01: Power Adjustment Range
    This parameter sets the power adjustment range of the heater. It can be adjusted to suit different heating needs:
    • 0: 0-100% Power Range
      A general setting for most heating applications, where power can be adjusted from 0 to 100%.
    • 1: 0-50% Power Range
      Suitable for applications requiring lower heating speeds or lower power settings.
  3. P1.00: Overload Protection Setting
    This parameter sets the overload protection threshold to prevent the heater from being damaged due to excessive load. The protection function can be enabled or disabled based on user needs:
    • 0: No Protection
      Overload protection is disabled, and the heater may be damaged in case of overload.
    • 1: Enable Overload Protection
      When enabled, the heater will automatically shut down if the load exceeds the set threshold.
  4. P2.00: Temperature Control Mode Selection
    This parameter selects the temperature control mode for the heater. The heating method is influenced by this setting:
    • 0: Open-loop Control
      The heater does not monitor temperature changes in real-time and relies on preset power values for heating, suitable for applications that do not require precise temperature control.
    • 1: Closed-loop Control
      In closed-loop control mode, the heater uses temperature sensors to monitor the workpiece’s temperature and adjusts power output accordingly to maintain accurate temperature control.

III. Wiring Instructions for the Induction Heater

The wiring of the MC Huikai induction heater is crucial for its proper operation. Correct wiring ensures the safety and reliability of the device. Below are the typical wiring instructions:

  1. Power Supply Wiring
    • The power supply should be connected to a three-phase AC power source, typically with voltages of 380V or 660V. Ensure that the wiring is compatible with the rated power of the device and that the appropriate circuit protection (fuses, circuit breakers) is used.
    • Verify that the power supply wiring is stable, and choose appropriately sized cables to avoid overheating or system malfunctions.
  2. Cooling System Piping
    The induction heater is equipped with a water cooling system to regulate the temperature during operation. The cooling system includes an inlet and outlet pipe, both of which need to be connected securely.
    • Inlet: Connect to a clean water source with the required temperature and quality.
    • Outlet: Ensure that water flows freely through the system and that the return pipe is not blocked.
  3. Control System Wiring
    The control system typically involves connecting the control panel, temperature sensors, and external control signals. Wiring should be done correctly to avoid electromagnetic interference and ensure accurate operation.
    • Ensure proper connections for the control panel and signal inputs.
    • Minimize the risk of interference by avoiding running control cables parallel to high-voltage power cables.

IV. Installation and Commissioning

  1. Installation Location
    The induction heater should be installed in a dry, well-ventilated area with no corrosive gases or excessive humidity. The device should be placed on a stable surface to prevent vibrations from affecting performance.
  2. Installation Steps
    • First, confirm the correct wiring for the power supply, cooling system, and signal connections.
    • Then, install the induction coil properly and ensure the distance between the coil and workpiece is suitable for efficient heating.
    • Finally, connect the control system and perform initial tests.
  3. Commissioning and Operation
    After installation, carry out the following steps:
    • Verify that the power supply, cooling system, and control panel are working correctly.
    • Adjust the power, temperature, and overload protection parameters.
    • Start the system, check the heating effect, cooling performance, and control panel response.

V. Daily Maintenance and Usage Precautions

  1. Maintenance
    • Regularly check the cooling system to ensure proper water flow and water quality.
    • Inspect power and control cables for wear or aging and replace them as needed.
    • Clean the heater’s surface and heat dissipation components to maintain proper cooling efficiency.
  2. Usage Precautions
    • Ensure that the heater is not placed near flammable materials to prevent fire hazards.
    • Avoid overloading the device or making improper adjustments, which could cause damage.
    • If the device is unused for extended periods, perform proper shutdown maintenance to maintain its condition.

Conclusion

The MC Huikai induction heater is a high-efficiency, energy-saving device widely used in various metal processing and heat treatment applications. This guide has provided a comprehensive introduction to the device’s technical parameters, wiring instructions, control settings, and daily usage precautions. By correctly installing, commissioning, and maintaining the heater, users can maximize its performance and ensure long-term reliability.


Posted on Leave a comment

Analysis and Repair Guide for ERR14 Fault on Botten A900 Inverter

The ERR14 fault displayed on the Botten A900 inverter indicates a specific issue that must be analyzed and resolved for proper operation. This guide will cover the meaning of this fault, potential causes, and detailed repair methods, including electronic circuit analysis.

ERR14

1. Understanding the ERR14 Fault Code

The ERR14 fault in the Botten A900 inverter typically relates to a parameter mismatch, EEPROM error, or data storage issue. This error occurs when the inverter detects inconsistencies or corruptions in the stored data or parameters used for its operation.

Key Meaning of ERR14

  • EEPROM Error: The EEPROM (Electrically Erasable Programmable Read-Only Memory) is responsible for storing key operational parameters. If the EEPROM fails to save or retrieve data correctly, the ERR14 fault is triggered.
  • Parameter Mismatch: If parameters stored in the EEPROM do not match the expected operational values (due to manual tampering, firmware updates, or memory corruption), this error is displayed.

Actual working diagram of A900

2. Possible Causes of ERR14

To repair this fault, it’s essential to identify the root cause. Below are some potential reasons:

a. Software/Parameter Issues

  1. Incorrect parameter input or corruption during setup.
  2. Power interruption during parameter saving or initialization.
  3. Firmware update failure, leading to corrupted or mismatched data.
  4. Overwriting of EEPROM memory due to repeated write cycles.

b. Hardware Issues

  1. EEPROM Failure: The EEPROM chip may be damaged or unable to retain data properly.
  2. PCB Track Damage: Faulty PCB tracks or poor soldering can cause inconsistent signals between the EEPROM and the microcontroller.
  3. Voltage Instability: Power supply fluctuations may damage or temporarily disrupt the EEPROM’s ability to write and read data.
  4. Microcontroller Fault: The main control IC may fail to communicate correctly with the EEPROM.

c. External Factors

  1. High-temperature operation leading to degradation of electronic components.
  2. Environmental factors such as humidity causing corrosion on the PCB.
  3. Electrostatic discharge (ESD) damage to sensitive components during maintenance.

A900 label

3. Steps to Diagnose ERR14

Before proceeding with repair, a step-by-step diagnosis is crucial:

a. Preliminary Checks

  1. Reset the Inverter:
    • Press the STOP/RESET button.
    • Turn off the power for 5-10 minutes to allow a complete reset.
    • Power on the inverter and observe if the ERR14 fault persists.
  2. Restore Factory Parameters:
    • Access parameter P0-00 and set it to 1 to restore default values.
    • If the fault clears, it indicates a parameter corruption issue.

b. Advanced Diagnostics

  1. Check Power Supply:
    • Measure the DC bus voltage and ensure stability.
    • Inspect the power supply capacitors for bulging or leakage.
  2. EEPROM Testing:
    • Locate the EEPROM chip on the main PCB (often marked as 24Cxx series).
    • Use an oscilloscope to verify data signal integrity on the EEPROM pins during read/write operations.
    • Replace the EEPROM if abnormal signals or communication failures are detected.
  3. Microcontroller Testing:
    • Verify the connections between the microcontroller and EEPROM.
    • Inspect for loose solder joints or damaged tracks using a magnifying glass.
  4. Environmental Inspection:
    • Examine the PCB for signs of corrosion or contamination.
    • Clean the board using isopropyl alcohol and a soft brush if necessary.

4. Repair Methods for ERR14

Based on the diagnosis, apply the following repair methods:

a. Software/Parameter Repairs

  1. Firmware Reinstallation:
    • Obtain the latest firmware version from the manufacturer.
    • Use a USB or serial communication tool to flash the inverter’s firmware.
    • Reinitialize parameters after installation.
  2. EEPROM Reset:
    • Replace parameter settings with factory defaults (via P0-00).
    • If this does not work, proceed to hardware repairs.

b. Hardware Repairs

  1. EEPROM Replacement:
    • Desolder the faulty EEPROM chip using a hot air rework station.
    • Replace it with a new chip of the same model.
    • Reprogram the EEPROM with default parameters if required.
  2. Microcontroller and Signal Line Repair:
    • Check for continuity between the EEPROM and the microcontroller using a multimeter.
    • Reflow solder joints on the microcontroller and EEPROM to fix potential cold joints.
  3. PCB and Power Circuit Repair:
    • Inspect the voltage regulators and capacitors on the PCB.
    • Replace any damaged components to ensure stable power supply to the EEPROM and other ICs.

c. Preventive Maintenance

  1. Environmental Protection:
    • Apply conformal coating to the PCB to protect against moisture and dust.
    • Ensure the inverter is installed in a well-ventilated area to prevent overheating.
  2. Regular Parameter Backups:
    • Periodically back up parameters to an external storage device or memory module to reduce recovery time in case of future errors.

5. Summary

The ERR14 fault on the Botten A900 inverter is primarily related to EEPROM or parameter inconsistencies, and it requires a systematic approach for resolution. By following the detailed diagnostic and repair steps provided, you can efficiently identify and rectify the root cause. Below is a concise summary:

  1. Perform basic resets and factory parameter initialization.
  2. Test the EEPROM and microcontroller connections for hardware integrity.
  3. Replace or reprogram faulty components if necessary.
  4. Implement preventive measures to minimize future occurrences.

With proper repair and maintenance, the Botten A900 inverter can continue to operate reliably in industrial environments.

Posted on Leave a comment

User Guide for Botain A900 Series Inverter Manual

The Botain A900 series inverter is a high-performance, feature-rich industrial-grade device widely used in various industrial scenarios. To help users better understand and operate this inverter, this article provides a detailed introduction to the control panel functions, parameter initialization, password setting and locking, parameter copying, external terminal control, and fault code analysis and troubleshooting methods.


1. Introduction to the Control Panel Functions

Actual working diagram of A900

The A900 series inverter’s control panel is designed intuitively, with the following main buttons and display areas:

  1. RUN Key: Starts the inverter operation.
  2. STOP/RESET Key: Stops the operation or resets faults.
  3. Arrow Keys (Up, Down, Left, Right): Used for browsing parameters or adjusting settings.
  4. ENTER Key: Confirms parameter settings.
  5. ESC Key: Exits the current menu.
  6. LED Numeric Display Screen: Displays current frequency, operating status, fault codes, etc.

How to Restore Parameter Initialization?

To reset the inverter to factory settings, follow these steps:

  1. Enter the parameter setting mode and locate parameter P0-00.
  2. Set P0-00 to 1 and press ENTER to confirm.
  3. The inverter will automatically restore all parameters to their factory default values.

How to Set Passwords and Lock Parameters?

To prevent parameters from being accidentally operated or changed, follow these steps to set a password:

  1. Locate parameter P0-14 and set a 4-digit password.
  2. After confirmation, some parameters will be locked.
  3. To unlock, enter the correct password in P0-15.

How to Copy Parameters to Another Inverter?

The parameter copy function allows users to quickly transfer the settings of the current inverter to another one. Follow these steps:

  1. Insert the control panel into the current inverter and enter the parameter setting mode.
  2. Set P0-50 to 1 to save parameters to the panel.
  3. Insert the control panel into the target inverter, set P0-50 to 2, and load the parameters from the panel to the inverter.
  4. Once parameter copying is complete, the inverter will reset automatically.

A900 standard wiring diagram

2. External Terminal Control and Speed Adjustment Settings

How to Achieve External Terminal Forward/Reverse Control?

To control forward/reverse rotation via external terminals, complete the following wiring and parameter settings:

  1. Wiring Requirements:
    • Forward Control: Connect the control signal to terminal FWD.
    • Reverse Control: Connect the control signal to terminal REV.
    • Common Terminal: Connect to terminal COM.
  2. Parameter Settings:
    • Set P0-02 to 1 (External Terminal Control Mode).
    • Set P3-01 and P3-02 for the logic input definitions of forward and reverse rotation.

How to Achieve Frequency Adjustment with an External Potentiometer?

  1. Wiring Requirements:
    • Connect the middle terminal of the potentiometer to AI1 (Analog Input 1).
    • Connect the two side terminals of the potentiometer to +10V and GND, respectively.
  2. Parameter Settings:
    • Set P0-03 to 1 (Analog Voltage Input).
    • Adjust P1-01 and P1-02 to the minimum and maximum frequency values to ensure that the potentiometer adjustment range meets actual needs.

Through the above settings, you can achieve forward/reverse control via external terminals and adjust output frequency via the potentiometer for precise speed control.


3. Fault Codes and Troubleshooting Methods

During operation, the inverter may encounter faults for various reasons. Below are common fault codes, their meanings, and troubleshooting methods:

Fault CodeFault DescriptionTroubleshooting
E001Overcurrent ProtectionCheck if the motor is overloaded or if the output line is short-circuited.
E002Overvoltage ProtectionCheck if the power supply voltage is abnormal or if feedback is too high.
E003Undervoltage ProtectionCheck if the power supply voltage is too low or if there is a loose connection.
E004Overtemperature ProtectionCheck if the inverter’s cooling system is working properly and clean the heat sink.
E005Phase Loss ProtectionCheck if the three-phase power input is normal and if the motor has a disconnection.
E006Ground FaultCheck if the grounding line is properly connected or if there is a short circuit.
E007External Fault TriggeredCheck the signal source and cause of the external fault input terminal.

If the above faults occur, follow the fault code and analysis methods to troubleshoot and take appropriate measures step by step.


4. Conclusion

The Botain A900 series inverter offers powerful functions and flexible control methods. By familiarizing yourself with the control panel functions, parameter initialization, password setting and locking, and parameter copying, you can quickly master its basic operations. Additionally, with correct external terminal and potentiometer wiring and parameter settings, forward/reverse control and speed adjustment can be easily achieved, significantly improving the efficiency and reliability of industrial equipment.

Furthermore, understanding the meanings and solutions of common fault codes will help users quickly identify issues and take effective measures in case of faults, avoiding production interruptions.

With this user guide, users can operate the Botain A900 series inverter more efficiently, ensuring the smooth operation of industrial automation equipment.

Posted on Leave a comment

LS Inverter SV-iGxA Series User Manual Usage Guide

I. Introduction to the Operation Panel Functions and Parameter Settings

Operation Panel Functions

The LS Inverter SV-iGxA series features an intuitive operation panel that includes RUN, STOP/RESET, up and down arrow keys, as well as a confirmation key. The panel’s 7-segment LED display provides clear visual feedback on operational data and parameter settings. Here’s a detailed look at the functions of the operation panel:

  • RUN Key: Starts the motor when pressed.
  • STOP/RESET Key: Stops the motor during operation and resets fault conditions when pressed after a fault occurs.
  • Arrow Keys: The up and down arrow keys are used to navigate through parameters and adjust their values.
  • Confirmation Key: Confirms parameter settings and saves changes.
  • 7-Segment LED Display: Shows operational data such as output frequency, output current, and fault codes.
SV-IGXA main circuit wiring diagram

Parameter Initialization

To initialize the parameters to their factory default settings, follow these steps:

  1. Navigate to Parameter H93: Use the arrow keys to select parameter H93 (Parameter Initialization) in the function group 2.
  2. Set Initialization Value: Press the confirmation key to enter the setting, then use the arrow keys to select the desired initialization level (e.g., 1 for initializing all parameter groups).
  3. Confirm Initialization: Press the confirmation key again to save the setting and initialize the parameters.

Reading, Writing, and Copying Parameters

The SV-iGxA series supports reading and writing parameters using a remote panel or communication interface.

  • Reading Parameters:
    1. Navigate to parameter H91 (Parameter Read) in the function group 2.
    2. Press the confirmation key to initiate the parameter read process.
    3. Follow the prompts on the remote panel or software interface to complete the read operation.
  • Writing Parameters:
    1. Navigate to parameter H92 (Parameter Write) in the function group 2.
    2. Press the confirmation key to initiate the parameter write process.
    3. Follow the prompts on the remote panel or software interface to upload the new parameter settings to the inverter.
SV-IGXA Terminal Wiring Diagram

Setting a Password and Locking Parameters

To enhance security, the SV-iGxA series allows users to set a password and lock specific parameters.

  • Registering a Password:
    1. Navigate to parameter H94 (Password Registration) in the function group 2.
    2. Press the confirmation key to enter the setting.
    3. Use the arrow keys to input the desired password (in hexadecimal format).
    4. Press the confirmation key to save the password.
  • Locking Parameters:
    1. Navigate to parameter H95 (Parameter Lock) in the function group 2.
    2. Press the confirmation key to enter the setting.
    3. Use the arrow keys to select the desired lock level (e.g., locking all parameters by setting H95 to 0xFFFF).
    4. Press the confirmation key to save the setting and lock the parameters.

II. Terminal Control and Potentiometer Speed Regulation

Terminal Forward/Reverse Control

To achieve forward/reverse control via terminal inputs, the following parameters need to be configured:

  • drv (Drive Mode): Set to 1 to enable terminal control.
  • drC (Motor Rotation Direction Selection): Select the desired rotation direction (F for forward, r for reverse).
  • I17-I18 (Multi-Function Input Terminal Definitions): Assign the FX (forward) and RX (reverse) commands to specific terminals (e.g., P1 for FX and P2 for RX).

Required Wiring:

  • FX Terminal: Connect to a normally open (NO) contact to start the motor in the forward direction.
  • RX Terminal: Connect to a normally open (NO) contact to start the motor in the reverse direction.
  • CM (Common) Terminal: Provide a common ground connection for all input terminals.

Potentiometer Speed Regulation

For speed regulation using a potentiometer, the following parameters need to be configured:

  • Frq (Frequency Mode): Set to 3 to enable potentiometer input for frequency control.
  • I6-I10 (V1 Input Parameters): Configure the voltage range and corresponding frequency for the potentiometer input.
    • I7 (V1 Input Minimum Voltage): Set to the minimum voltage output by the potentiometer.
    • I8 (V1 Input Minimum Frequency): Set the frequency corresponding to the minimum voltage.
    • I9 (V1 Input Maximum Voltage): Set to the maximum voltage output by the potentiometer.
    • I10 (V1 Input Maximum Frequency): Set the frequency corresponding to the maximum voltage.

Required Wiring:

  • V1 Terminal: Connect to the output of the potentiometer.
  • CM Terminal: Provide a common ground connection for the V1 terminal.
  • 10V Terminal (if applicable): Provide a 10V reference voltage for the potentiometer (not required for potentiometers with built-in reference voltage).

By configuring the above parameters and wiring the terminals correctly, the SV-iGxA series inverter can be easily controlled via external inputs for forward/reverse operation and speed regulation using a potentiometer.

Posted on Leave a comment

Operation Guide for BoPusen Inverter PER640 Series User Manual

I. Introduction to Operation Panel Functions and Password & Parameter Lock Settings

The BoPusen Inverter PER640 series boasts an intuitive operation panel that provides users with a clear interface. The panel primarily comprises a display screen, buttons (such as PRG, ENTER, WARNING, etc.), and status indicators. Users can utilize these buttons and the display screen to set various parameters, monitor operating status, and troubleshoot issues.

PER640 picture

Setting Passwords and Parameter Locks:

  • Password Setting: Function code F0.23 allows users to set a password within the range of 0~9999. Once set, unauthorized users will be unable to modify the inverter’s parameters.
  • Parameter Lock: Function code F8.05 is used for parameter initialization. Selecting “1” will restore the inverter to its factory settings, resetting all user parameters to their default values. This can also be considered a form of parameter lock, ensuring parameters are not changed arbitrarily.

Parameter Initialization:

  • Initialization Procedure: By selecting “1” in function code F8.05, users can restore the inverter’s parameters to their factory settings. Selecting “2” will clear fault records.

II. Terminal Forward/Reverse Control and External Potentiometer Speed Regulation

Terminal Forward/Reverse Control:

  • To achieve forward/reverse control of the inverter, users need to set function code F0.12 (Operation Direction Setting). This parameter has three options: 0 for forward rotation, 1 for reverse rotation, and 2 to prohibit reverse rotation.
  • For wiring, terminals X1 and X2 are typically used for forward/reverse control. Connect terminal X1 to the forward signal source and terminal X2 to the reverse signal source to enable forward/reverse control.

External Potentiometer Speed Regulation:

  • To achieve speed regulation via an external potentiometer, users must first set function code F0.03 (Frequency Setting Selection) to “3” (AI Analog Setting).
  • For wiring, connect the output terminal of the external potentiometer to the inverter’s AI terminal (typically the AVI terminal), ensuring the GND terminal is grounded. By adjusting the resistance of the external potentiometer, users can change the inverter’s output frequency, thereby achieving speed regulation.
PER640 standard wiring diagram

III. Fault Codes and Troubleshooting Methods

The BoPusen Inverter PER640 series provides a comprehensive list of fault codes to assist users in quickly locating and resolving issues. Below are some common fault codes, their meanings, and corresponding troubleshooting methods:

  1. EOC1 (Overcurrent During Acceleration):
    • Meaning: The inverter experiences an overcurrent during the acceleration process.
    • Troubleshooting: Extend the acceleration time (F0.10), check if the inverter power is too small, and adjust the V/F curve or torque boost.
  2. EOC2 (Overcurrent During Deceleration):
    • Meaning: The inverter experiences an overcurrent during the deceleration process.
    • Troubleshooting: Extend the deceleration time (F0.11), check if the inverter power is too small, and adjust the V/F curve or torque boost.
  3. EOL1 (Inverter Overload):
    • Meaning: The inverter’s output current exceeds the rated value, causing an overload.
    • Troubleshooting: Extend the acceleration time (F0.10), select a more powerful inverter, adjust the V/F curve and torque boost, and check if the grid voltage is too low.
  4. EHU1 (Overvoltage During Acceleration):
    • Meaning: The inverter experiences an overvoltage during the acceleration process.
    • Troubleshooting: Check if the input power supply is normal and set the starting mode to DC brake start for restarting rotating motors.
  5. ELUO (Undervoltage During Operation):
    • Meaning: The inverter’s input voltage falls below the allowable range.
    • Troubleshooting: Check if the power supply voltage is normal and seek assistance from the manufacturer.
  6. ESC1 (Power Module Fault):
    • Meaning: The inverter’s power module has failed.
    • Troubleshooting: Seek assistance from the manufacturer.

IV. Conclusion

The BoPusen Inverter PER640 series user manual provides users with a detailed operation guide, covering the introduction to operation panel functions, password and parameter lock settings, methods for achieving terminal forward/reverse control and external potentiometer speed regulation, as well as fault codes and troubleshooting methods. By carefully reading the manual and following the instructions, users can fully utilize the inverter’s capabilities, ensuring stable equipment operation. Additionally, the manual provides abundant technical parameters and wiring diagrams, offering users strong technical support.