Posted on Leave a comment

ADSEN Variable Frequency Drive ADS-V Series User Manual Operation Guide

I. Introduction to Operation Panel Functions

The operation panel of the ADSEN Variable Frequency Drive (VFD) ADS-V series serves as a crucial interface for user interaction with the device. The panel typically includes multiple function keys and a display screen, allowing users to perform operations such as start, stop, frequency setting, and parameter modification. The main function keys on the panel include:

  • Run Key: Starts the VFD operation.
  • Stop/Reset Key: Stops the VFD operation or resets it after a fault occurs.
  • Forward/Reverse Switch Key: Switches the running direction of the VFD.
  • Set Key: Enters the parameter setting mode.
  • Display/Shift Key: Cycles through different parameters such as output frequency, current, temperature, etc., in display mode.

1.1 Initializing Parameters (Restoring Factory Settings)

To restore all parameters of the VFD to factory settings, users can follow these steps:

  1. Press the “Set” key to display “Pr000”.
  2. Use the “Increase” or “Decrease” key to adjust to “Pr013” (parameter reset) and set the value to “01”.
  3. Press the “Confirm” key (usually the “Jog” key) to confirm the reset.
  4. At this point, the VFD will restore to factory settings, and all user-set parameters will be cleared.

1.2 Setting and Removing a Password

To protect the parameter security of the VFD, users can set a password to prevent unauthorized access. The specific steps are as follows:

  1. Enter the parameter setting mode and locate “Pr000” (parameter lock).
  2. Set the value to “1” to enable password protection.
  3. To remove the password, set it to “0”.

1.3 Setting Parameter Access Restrictions

After setting the parameter lock in “Pr000”, users can prevent others from modifying the parameters. A setting of “0” indicates invalid, while “1” indicates valid. Users must unlock before modifying parameters.

II. External Terminal Forward/Reverse Control and External Potentiometer Frequency Speed Adjustment

2.1 External Terminal Forward/Reverse Control

To achieve external terminal forward/reverse control, users need to wire the following terminals:

  • X1 Terminal: Run control signal.
  • X2 Terminal: Reverse control signal.
  • X3 Terminal: Stop control signal.

Parameter Settings:

  1. Set “Pr001” to “1” to select external terminal control.
  2. Set “Pr044” to “02” to assign X1 as run.
  3. Set “Pr045” to “03” to assign X2 as reverse.
  4. X3 terminal can be set as stop.

2.2 External Potentiometer Frequency Speed Adjustment

Connect the external potentiometer to the following terminals:

  • FV Terminal: Frequency setting input.
  • GND Terminal: Ground.

Parameter Settings:

  1. Set “Pr001” to “1” to select external terminal control.
  2. Set “Pr002” to “1” to select external potentiometer for frequency setting.
  3. Set “Pr072” to the desired maximum frequency (e.g., 50Hz).

With these settings, users can adjust the output frequency of the VFD using an external potentiometer.

III. Fault Codes and Troubleshooting

The ADSEN VFD ADS-V series provides multiple fault protection functions. Common fault codes and their troubleshooting methods are as follows:

3.1 Common Fault Codes

  • OU-1: Overvoltage during acceleration
    • Troubleshooting: Check the grid voltage and extend the acceleration/deceleration time.
  • OU-2: Overvoltage during deceleration
    • Troubleshooting: Extend the deceleration time or install a braking resistor.
  • FB: Fuse blown
    • Troubleshooting: Send for factory repair.
  • OH: VFD overheat
    • Troubleshooting: Check if the fan is blocked and ensure the ambient temperature is normal.
  • OL-1: VFD overcurrent or overload
    • Troubleshooting: Check if the load is too large and reset the parameters.
  • LV: Undervoltage
    • Troubleshooting: Check if the input voltage is normal.

3.2 Fault Handling

In the event of a fault, immediately press the stop key and record the fault code. Users should refer to the manual for corresponding checks and troubleshooting based on the fault code. If the fault cannot be resolved, contact professional technicians for repair.

IV. Summary

The user manual of the ADSEN VFD ADS-V series provides a detailed operation guide. Users should be familiar with the functions of the operation panel and fault troubleshooting methods during daily operations. By properly setting parameters and conducting effective maintenance checks, the normal operation of the VFD can be ensured, and its service life can be extended. In practical applications, if any issues are encountered, users should refer to the manual for resolution or contact professionals for support.

Posted on Leave a comment

Operation Guide for Ruishen Inverter RCP900 Series User Manual

I. Introduction to Operation Panel Functions and Parameter Initialization

The Ruishen Inverter RCP900 series is equipped with an intuitive and user-friendly operation panel, which integrates a data display area, command source indicators, forward/reverse indicators, and various other functions. Through this panel, users can easily perform parameter settings, working status monitoring, operation control, and other operations of the inverter.

RCP900正面图片

Parameter Initialization:

Before using the RCP900 series inverter, it is sometimes necessary to initialize the parameters to restore the factory settings. This can be achieved by setting the function code PP-01. Setting PP-01 to 1 will restore the inverter’s factory parameters (excluding motor parameters). This step is particularly important for resolving inverter faults caused by incorrect parameter settings.

Password Setting and Removal:

To protect the inverter settings from unauthorized changes, the RCP900 series inverter supports password protection. Users can set a password by configuring the function code PP-00. To remove the password, simply set PP-00 to 0. The password protection feature effectively prevents unauthorized operations and ensures the safety and stability of the inverter’s operation.

Parameter Access Restriction:

In addition to password protection, the RCP900 series inverter also supports parameter access restriction functionality. Users can select which parameter groups or specific parameters can be accessed and modified by configuring the function codes PP-03 and PP-04. This feature allows users to flexibly control access permissions to the inverter parameters based on actual needs, enhancing the security of device management.

RCP900 Side Image

II. Terminal Forward/Reverse Control and External Potentiometer Speed Regulation

Terminal Forward/Reverse Control:

The RCP900 series inverter supports forward/reverse control of the motor through terminals. The specific wiring method is as follows: Connect the forward control signal to the DI1 terminal, the reverse control signal to the DI2 terminal, and the common terminal to the COM terminal. In terms of parameter settings, it is necessary to set P0-02 (Run Command Selection) to 1 (Terminal Command), P4-00 (DI1 Terminal Function Selection) to 1 (Forward Run), and P4-01 (DI2 Terminal Function Selection) to 2 (Reverse Run). After completing these settings, the motor’s forward/reverse control can be achieved by controlling the electrical level status of the DI1 and DI2 terminals.

External Potentiometer Speed Regulation:

The RCP900 series inverter also supports speed regulation through an external potentiometer. The specific wiring method is as follows: Connect the output end of the external potentiometer to the AI1 terminal and the GND terminal to the inverter’s GND terminal. In terms of parameter settings, it is necessary to set P0-03 (Main Frequency Command Input Selection) to 4 (AI3 Panel Potentiometer). After completing these settings, the motor speed can be adjusted by adjusting the resistance value of the external potentiometer.

RCP900 Standard Wiring Diagram

III. Fault Code Meaning Analysis and Troubleshooting

During operation, the RCP900 series inverter may encounter various faults. When a fault occurs, the inverter will display the corresponding fault code. Below are some common fault codes, their meanings, and troubleshooting methods:

  • Err02: Acceleration Overcurrent. Possible causes include grounding or short circuit in the output circuit, incorrect motor parameter settings, etc. Solutions include troubleshooting peripheral issues, performing motor parameter identification, etc.
  • Err03: Deceleration Overcurrent. Possible causes are similar to those of acceleration overcurrent. Solutions also include troubleshooting peripheral issues, increasing deceleration time, etc.
  • Err05: Acceleration Overvoltage. Possible causes include high input voltage, short acceleration time, etc. Solutions include adjusting the input voltage, increasing the acceleration time, etc.
  • Err14: IGBT Overheat. Possible causes include high ambient temperature, fan failure, etc. Solutions include lowering the ambient temperature, replacing the fan, etc.

For the above fault codes, users can adopt corresponding solutions based on the inverter’s display information, combined with fault phenomena and possible causes. If the issue cannot be resolved, it is recommended to contact Ruishen Inverter’s technical support personnel or professional maintenance personnel for assistance.

IV. Conclusion

The Ruishen Inverter RCP900 series user manual provides a detailed operation guide, including operation panel function introduction, parameter initialization, password setting and removal, parameter access restriction, terminal forward/reverse control, external potentiometer speed regulation, fault code meaning analysis, troubleshooting methods, and other content. By carefully reading and understanding the user manual, users can better master the inverter’s usage methods and maintenance skills, ensuring the normal operation of the equipment and extending its service life. At the same time, users should flexibly utilize the inverter’s various functions based on actual needs to achieve more efficient and stable motor control.

Posted on Leave a comment

Operation Guide for Instar-Tech AE200H Series Frequency Converter User Manual

I. Introduction to Operation Panel Functions

The Instar-Tech AE200H series frequency converter features a concise and straightforward operation panel design, facilitating intuitive operation and monitoring. The main function keys and indicator lights on the operation panel include:

  • RUN Key: Press this key to start the frequency converter. In programming mode, this key can be used as a shift key.
  • JOG Key: Press this key to enter jogging mode and switch between forward and reverse rotation.
  • STOP Key: Press this key to stop the frequency converter. After a fault alarm, pressing this key can reset the system.
  • PROG Key: Press this key to enter the function setting mode. After modification, press it again to exit the setting mode.
  • DATA Key: In programming mode, press this key to confirm the function code and parameter content. After modification, press it again to save the data.
  • UP Key and DOWN Key: In programming mode, use these keys to adjust the numerical values of function codes and parameter data.
  • Shift Key (<< / REV): In programming mode, use this key to shift during parameter data modification.

Additionally, the operation panel has multiple indicator lights to display the operating status of the frequency converter, such as the RUN, STOP, FWD, and REV indicators.

Function diagram of AE200H operation panel

II. Password Setting and Parameter Access Restrictions

To protect the frequency converter’s settings from unauthorized modification, the AE200H series provides a password setting function. Users can set a password to restrict access and modification of frequency converter parameters. The specific steps are as follows:

  1. Set Password: Enter programming mode, locate the user password parameter (e.g., P.089), and set a non-zero value as the password.
  2. Enter Password: When modifying parameters, the system will prompt for a password. Only by entering the correct password can you access the parameter modification interface.
  3. Eliminate Password: To eliminate the password, simply reset the user password parameter value to 0.

Furthermore, the AE200H series frequency converter offers parameter access restriction functions. Users can set different access levels to restrict different users’ access to frequency converter parameters.

III. Parameter Initialization

If users need to restore the frequency converter to its factory settings, they can perform a parameter initialization operation. The specific steps are as follows:

  1. Enter programming mode.
  2. Locate the factory reset parameter (e.g., P.XXX, refer to the user manual for specific codes) and set its value to 1.
  3. Press the DATA key to save the setting and restart the frequency converter.

After restarting, the frequency converter will return to its factory settings, and all user-set parameters will be cleared.

IV. Terminal Forward/Reverse Control and External Potentiometer Speed Regulation

The AE200H series frequency converter supports motor forward/reverse control through external terminals and speed regulation through an external potentiometer. The specific settings and wiring methods are as follows:

  1. Terminal Forward/Reverse Control
    • Parameter Setting: No special setting is required; ensure correct wiring.
    • Wiring Method: Connect the forward control terminal (e.g., S1) and reverse control terminal (e.g., S2) to the corresponding contacts in the control circuit. By controlling the on/off status of these contacts, you can achieve motor forward/reverse rotation and stopping.
  2. External Potentiometer Speed Regulation
    • Parameter Setting: Locate the speed control mode selection parameter (e.g., P.XXX) and set its value to external given.
    • Wiring Method: Connect the output terminal of the external potentiometer to the speed regulation input terminal of the frequency converter (e.g., AI1 or AI2). By adjusting the resistance value of the potentiometer, you can change the output frequency of the frequency converter, thereby achieving motor speed regulation.

V. Fault Codes and Solutions

The AE200H series frequency converter features comprehensive fault diagnosis capabilities. When a fault occurs, the corresponding fault code will be displayed on the screen. Here are some common fault codes, their meanings, and solutions:

  1. OC1/OC2/OC3: Overcurrent during acceleration/deceleration/constant speed.
    • Meaning: The output current of the frequency converter exceeds the rated value.
    • Solution: Check if the motor load is excessive, check the power line connection for good contact, and check if the frequency converter parameter settings are reasonable (e.g., acceleration/deceleration time, overload protection).
  2. OU1/OU2/OU3: Overvoltage during acceleration/deceleration/constant speed.
    • Meaning: The input voltage of the frequency converter is too high or the braking resistor is damaged.
    • Solution: Check if the power supply voltage is stable and inspect the braking resistor for damage or poor connection.
  3. UV: Undervoltage on the bus.
    • Meaning: The input voltage of the frequency converter is lower than the rated voltage.
    • Solution: Check if the power supply voltage is normal and inspect the power line connection for good contact.
  4. OL1: Motor overload.
    • Meaning: The motor load is excessive or the motor parameter settings are incorrect.
    • Solution: Check if the motor load is excessive and verify the motor parameter settings (e.g., rated current, power).
  5. OH2: Frequency converter overheat.
    • Meaning: The internal temperature of the frequency converter is too high.
    • Solution: Check if the frequency converter installation environment is well-ventilated and inspect the cooling fan for normal operation.
AE200H standard wiring diagram

VI. Conclusion

This article provides a detailed operation guide for the Instar-Tech AE200H series frequency converter, covering the introduction to operation panel functions, password setting and parameter access restrictions, parameter initialization, terminal forward/reverse control, external potentiometer speed regulation, fault codes and solutions, and other related content. We hope this guide will help users better understand and utilize this series of frequency converters to ensure their efficient and stable operation.

Posted on Leave a comment

WEICHI Servo SD710 Series User Manual Operation Guide

I. Introduction to Servo Operation Panel Functions and Basic Settings

1.1 Panel Function Introduction

The WEICHI Servo SD710 series operation panel features a concise and clear design, including mode selection keys (MODE/SET), up/down adjustment keys (UP/DOWN), data shift keys (DATA/SHIFT), and some function keys. These keys allow users to easily switch modes, set parameters, display statuses, and more.

SD710 front

1.2 Setting Passwords and Parameter Access Restrictions

To ensure the security of the servo system, the SD710 series provides password protection functionality. Users can set the access permissions for function code parameters through parameter PnE1D’s system switch 3. The specific steps are as follows:

  1. Enter Auxiliary Functions: Press the MODE/SET key to select auxiliary functions and adjust to Fn010 using the UP/DOWN keys.
  2. Set Password: Press the DATA/SHIFT key for about one second to enter the parameter setting state, and adjust the parameter value using the UP/DOWN keys. Press the MODE/SET key to confirm after setting.

1.3 Realizing Jog Operation

Jog operation is a commonly used function in servo debugging. The SD710 series provides two modes: JOG (speed jog) and program JOG (position jog). The specific implementation steps are as follows:

  1. JOG Mode:
    • Press the MODE/SET key to select auxiliary functions and adjust to Fn005.
    • Set the jog speed (Pn500) using the UP/DOWN keys, and press the MODE/SET key to enter the servo ON state.
    • Press the UP key (forward rotation) or DOWN key (reverse rotation) to start jog operation.
  2. Program JOG Mode:
    • Press the MODE/SET key to select auxiliary functions and adjust to Fn006.
    • Set the relevant parameters for program JOG (such as Pn502 operation mode, Pn503 movement distance, etc.).
    • Press the MODE/SET key to enter the servo ON state and start program JOG operation.
SD710 Side

1.4 Setting Brake and Over-travel

Brake Setting:

  • Set the relevant delay times for brake activation through parameters Pn009 and Pn010 to ensure that the brake can actuate timely when the motor stops.

Over-travel Setting:

  • Connect external limit switches to the P-OT and N-OT pins of the CN1 terminal to achieve over-travel protection in positive and negative directions.
  • Alternatively, enable the soft limit function internally through parameter Pn00D.W and set the absolute position limit switch.

1.5 Regenerative Braking Setting

Regenerative braking is an important safety protection function in servo systems. The SD710 series provides options for both built-in and external regenerative braking resistors. Users can set the resistance and capacity of the built-in braking resistor through parameters PnE0B and PnE0C. For external braking resistors, correct connection according to the wiring diagram in the drive manual is required, and the corresponding resistance should be set through parameters.

II. External Pulse Position Mode Forward and Reverse Positioning Control

2.1 Terminal Connections

To realize external pulse position mode forward and reverse positioning control, the relevant pins of the CN1 terminal need to be connected correctly. The specific connections are as follows:

  • Pulse Input: Connect to the PUL+ and PUL- pins of CN1.
  • Direction Input: Connect to the DIR+ and DIR- pins of CN1.
  • Enable Input: Connect to the S-ON pin of CN1.

2.2 Parameter Settings

  1. Control Mode Selection: Set parameter Pn000.X to 0 to select position control mode.
  2. Position Command Source Selection: Set parameter Pn200 to 0 to select external pulse sequence as the position command source.
  3. Electronic Gear Ratio Setting: Set parameters Pn204 (numerator) and Pn206 (denominator) according to actual needs to determine the number of pulses per motor revolution.
  4. Jog Speed Setting (optional): Set parameter Pn500 for using the jog function during debugging.

After completing the above settings, pulse signals can be sent through an external pulse generator to realize forward and reverse positioning control of the servo motor.

SD710 Position Mode Standard Wiring Diagram

III. Fault Codes and Solutions

The WEICHI Servo SD710 series drive provides a wealth of fault codes to help users quickly locate problems. The following are some common fault codes and their solutions:

  • ER.020: User function code parameter and checksum error. Solution: Check if the parameter settings are correct and re-initialize the parameters after re-powering.
  • ER.100: Drive overcurrent. Solution: Check if the motor and drive are overloaded, and check if the motor power line connection is poor.
  • ER.320: Regenerative overload. Solution: Check if the regenerative braking resistor is connected correctly and if the resistance is appropriate; reduce the load or increase the braking resistor.
  • ER.400: Overvoltage. Solution: Check if the power supply voltage is stable and if it exceeds the rated voltage range of the drive.
  • ER.410: Undervoltage. Solution: Check if the power supply voltage is too low and ensure that the power supply voltage is within the allowable range of the drive.

For other fault codes, users can refer to the fault code table in the drive manual and perform corresponding checks and troubleshooting according to the prompts.

IV. Conclusion

The WEICHI Servo SD710 series user manual provides detailed operation guides and parameter setting instructions, helping users quickly get started and achieve efficient and stable servo control. By correctly setting panel parameters, connecting external terminals, and promptly handling fault codes, users can fully leverage the performance advantages of the SD710 series to meet the needs of various industrial applications.

Posted on Leave a comment

User Manual Guide for Zhengchuan ZC300 Series Frequency Converter

The Zhengchuan ZC300 series frequency converter is a high-performance frequency control device known for its high torque, high precision, wide speed range, and low noise. It is widely used in equipment manufacturing and end-user applications for speed control, energy saving, protection, and automatic control. To assist users in better understanding and utilizing this frequency converter, the following is a detailed user manual guide based on the Zhengchuan ZC300 series frequency converter manual.

I. Introduction to the Frequency Converter Operation Panel and Parameter Settings

1. Operation Panel Function Introduction

The operation panel of the Zhengchuan ZC300 series frequency converter mainly includes a display screen, function keys (MENU, ENT, UP/DOWN arrow keys, etc.), and status indicators. By operating these keys, users can access and modify various parameters of the frequency converter for precise control.

2. Parameter Locking and Password Setting

To ensure that the frequency converter parameters are not changed arbitrarily, the Zhengchuan frequency converter provides a parameter locking function. The specific operation steps are as follows:

  • First, enter the parameter setting interface through the operation panel.
  • Find the parameter that needs to be locked (such as P0.07) and set its value to 1.
  • Press the MENU key twice to exit the parameter setting interface. At this point, the parameter is locked.

To unlock the parameter, simultaneously press and hold the first function key and the red stop key for 8 seconds. The screen will display a prompt indicating successful unlocking.

Password setting typically involves modifying specific parameters, and the specific method may vary depending on the model. Please refer to the detailed instructions in the user manual.

3. Parameter Initialization

Parameter initialization is the process of restoring the frequency converter to its factory settings, which helps restore the device to normal operation when the parameter settings are confused. The method for initializing parameters is as follows:

  • Enter the parameter setting interface and find the function code related to initialization (such as P0.00).
  • According to the instructions in the user manual, set the value of the function code to the corresponding initialization option (e.g., 2 indicates restoring all user parameters to factory settings).
  • After confirming the setting, exit the parameter setting interface, and the frequency converter will automatically restore to its factory settings.

II. Terminal Forward/Reverse Control and External Potentiometer Speed Adjustment

1. Terminal Forward/Reverse Control

The Zhengchuan ZC300 series frequency converter supports forward/reverse control of the motor through terminals. The specific wiring and setting methods are as follows:

  • Wiring: Connect the three wires of the three-phase motor to the UVW terminals of the frequency converter. At the same time, connect the intermediate relays KA1 and KA2 controlling forward and reverse to the STF and STR terminals of the frequency converter, respectively. Additionally, short-circuit the SD terminal with the common terminal to achieve start control.
  • Setting: Enter the parameter setting interface, find the parameter related to forward/reverse control (such as the run command channel selection), and set it to the external terminal control mode.

2. External Potentiometer Speed Adjustment

An external potentiometer can be used to adjust the output frequency of the frequency converter, thereby achieving precise control of the motor speed. The specific wiring and setting methods are as follows:

  • Wiring: Connect the three terminals of the potentiometer to the 10V, V, and GND terminals of the frequency converter. Among them, the 10V terminal provides positive power for the potentiometer, the V terminal is the output terminal of the potentiometer, and the GND terminal is the grounding terminal.
  • Setting: Enter the parameter setting interface, find the frequency setting selection parameter, and set it to the external terminal mode. At this point, the output frequency of the frequency converter will change with the rotation angle of the potentiometer.

III. Fault Codes and Their Handling

The Zhengchuan ZC300 series frequency converter has a comprehensive fault detection and diagnosis function, capable of displaying fault codes in real-time and taking corresponding protective measures. The following are some common fault codes, their meanings, and handling methods:

1. OCF (Overcurrent Fault of the Frequency Converter)

  • Meaning: Incorrect input of motor nameplate data or excessive load causing excessive output current of the frequency converter.
  • Handling Method: Check whether the motor nameplate data entered in the settings and motor control menu is correct; check whether the frequency converter selection matches the motor and load; check whether the motor is locked or the machinery is jammed.

2. SCF (Motor Short-Circuit Fault)

  • Meaning: Insulation issues in the motor or the cable from the frequency converter to the motor causing a short circuit.
  • Handling Method: Check the insulation of the cable between the frequency converter and the motor; check the motor insulation; if the cable is too long, use a motor reactor or sine wave filter to reduce grounding leakage current.

3. OBF (Over-Braking Fault)

  • Meaning: Sudden increase in the internal DC bus voltage of the frequency converter due to excessive braking or excessive load inertia.
  • Handling Method: Increase the deceleration time of the frequency converter; activate the deceleration time adaptive function; add a braking resistor and calculate the resistance value and power of the braking resistor based on actual requirements.

4. OLF (Motor Overload Fault)

  • Meaning: Excessive current in the motor triggers the motor thermal protection inside the frequency converter.
  • Handling Method: Check the load condition of the motor; check the setting of the motor thermal protection parameter of the frequency converter; wait for the motor to cool down before starting it again.

5. OPF (Motor Phase Loss Fault)

  • Meaning: The frequency converter is not connected to the motor or the motor power does not match the frequency converter power, resulting in the inability to detect motor current.
  • Handling Method: Check the connection between the frequency converter and the motor; turn off the motor phase loss protection function of the frequency converter (e.g., for small motor testing); check whether the settings for the motor rated voltage, rated current, and IR stator voltage drop compensation parameters are correct.

In addition, there are other fault codes such as OSF (Overvoltage Fault of Input), SLF (Communication Fault of Frequency Converter), USF (Undervoltage Fault of Frequency Converter), and PHF (Input Phase Loss Fault of Frequency Converter), each with its specific meaning and handling method. Users should closely monitor the operating status of the frequency converter during use to detect and handle faults in a timely manner.

Conclusion

The Zhengchuan ZC300 series frequency converter, as a high-performance frequency control device, offers various practical functions to meet the needs of different users. This article provides a detailed introduction to the operation panel functions, parameter setting methods, wiring and setting methods for terminal forward/reverse control and external potentiometer speed adjustment, as well as the meanings and handling methods of common fault codes. We hope this user manual guide can help users better understand and utilize the Zhengchuan ZC300 series frequency converter.

Posted on Leave a comment

Operation Guide for C-LIN XLP6000 Series Inverter User Manual

The C-LIN XLP6000 series of inverters, as a high-performance general-purpose vector control inverter, is widely used in various industrial control applications due to its excellent motor control performance and flexible operation methods. This article aims to provide users with a comprehensive guide on operating the C-LIN XLP6000 series inverter based on its user manual.

1. Introduction to the Functionality of the Inverter Operation Panel

The operation panel of the C-LIN XLP6000 series inverter is equipped with various functions to facilitate user operation and monitoring. It includes:

  • Password Setting and Reset:
    • To set a password, users can modify the parameter P0.00 in the function parameter settings. Note that passwords with values of 0 to 9 do not require protection, while setting a password successfully requires a wait of 3 minutes before it takes effect.
    • To reset the password, users can set P0.00 back to its default value (0).
  • Parameter Locking:
    • Users can enable parameter locking by setting the parameter P0.09 to 2, which will prevent unauthorized modifications to parameters.
  • Parameter Initialization:
    • To initialize parameters, users can set P0.09 to 2. This will restore all user parameters to their factory default settings, except for motor parameters.

2. Terminal Control for Forward/Reverse Rotation and External Potentiometer Speed Regulation

To achieve forward/reverse rotation control and external potentiometer speed regulation, users need to properly wire the relevant terminals and configure the corresponding parameters.

  • Wiring Instructions:
    • Forward/Reverse Rotation Control:
      • Connect the forward and reverse control terminals (X1 and X2) to the corresponding switches or relays.
      • Ensure that the common terminal (COM) is properly grounded.
      • In the function parameter settings, set P0.21 to determine the default direction when using the operation panel.
    • External Potentiometer Speed Regulation:
      • Connect one end of the potentiometer to the power supply (e.g., +10V and GND).
      • Connect the other end of the potentiometer to the analog input terminal (AI1).
      • In the function parameter settings, ensure that AI1 is configured to receive analog voltage input and set the corresponding range.
  • Specific Terminals:
    • Forward/Reverse Control: X1 (forward), X2 (reverse), COM (common)
    • External Potentiometer: AI1 (analog input), +10V (power supply), GND (ground)
  • Parameters to Be Set:
    • P0.06: Run command channel selection (set to 0 for operation panel control, 1 for terminal control, etc.)
    • P0.07: Frequency setting channel selection (set to 1 for analog voltage input, etc.)
    • P6.00: AI1 input type selection (set to 0 for voltage input)
    • P6.01: AI1 input range setting

By following the above steps, users can effectively utilize the C-LIN XLP6000 series inverter for forward/reverse rotation control and external potentiometer speed regulation, enhancing the flexibility and efficiency of their industrial control systems.

Posted on Leave a comment

KEWO Inverter AD350/AD150 Series User Manual Operation Guide

I. Introduction to the Operation Panel Functions and Parameter Initialization Settings

The operation panel of the KEWO Inverter AD350/AD150 series provides an intuitive user interface for easy parameter setting and monitoring. The operation panel typically includes a display screen, direction keys, a confirmation key, a run key, and a stop key.

AD350 front image

Parameter Initialization Settings:
When initializing the inverter for the first time or restoring it to factory settings, the parameter initialization function can be used. The specific steps are as follows:

  1. Enter the functional parameter table (P group) and locate the P0.13 parameter (parameter initialization).
  2. Use the direction keys to select “01: Restore factory parameters, excluding motor parameters” or “12: Clear record information”, then press the confirmation key.
  3. The inverter will automatically perform the initialization settings and restart.

Password and Parameter Access Restrictions:
To prevent unauthorized parameter modifications, users can set passwords and parameter access restrictions to protect the inverter configuration.

  1. Enter the P7 group (keyboard and display group) and locate the P7.00 parameter (user password).
  2. Use the direction keys to set the desired password (0-65535), then press the confirmation key.
  3. Find the P7.03 parameter (parameter write protection) and select “1: Parameters not allowed to be modified” to enable parameter access restrictions.
Side image of AD350

II. Terminal Forward/Reverse Control and External Potentiometer Given Speed Regulation

Terminal Forward/Reverse Control:
The KEWO Inverter supports forward/reverse control through external terminals. Typically, the X1 and X2 terminals are used as forward/reverse control terminals.

Wiring Steps:

  1. Connect the forward control signal line to the X1 terminal and the reverse control signal line to the X2 terminal.
  2. Ensure that the other end of the signal line is connected to the correct control source (such as a PLC output).

Parameter Settings:

  1. Enter the P5 group (input terminal group) and locate the P5.00 parameter (X1 terminal function selection).
  2. Use the direction keys to select “1: Forward operation (FWD)”, then press the confirmation key.
  3. Find the P5.01 parameter (X2 terminal function selection) and select “2: Reverse operation (REV)”, then press the confirmation key.

External Potentiometer Given Speed Regulation:
An external potentiometer can conveniently adjust the output frequency of the inverter to achieve speed regulation.

Wiring Steps:

  1. Connect the output terminal of the external potentiometer to the AI1 terminal (analog input terminal 1) and the other end to the GND terminal (ground terminal).
  2. Ensure that the power supply and signal lines of the potentiometer are connected correctly.

Parameter Settings:

  1. Enter the P0 group (basic parameter group) and locate the P0.03 parameter (main frequency selection).
  2. Use the direction keys to select “4: Panel potentiometer”, then press the confirmation key.

III. Fault Codes and Troubleshooting Methods

The KEWO Inverter AD350/AD150 series provides a wealth of fault codes to help users quickly locate problems and take corresponding measures.

AD350-AD150 Standard Wiring Diagram

Common Fault Codes and Troubleshooting Methods:

  1. E001 (Acceleration Overcurrent):
    • Possible Causes: Too short acceleration time, output short circuit, improper motor parameter settings, etc.
    • Solution: Increase the acceleration time, check the insulation of the motor and cable, perform motor parameter identification, etc.
  2. E002 (Deceleration Overcurrent):
    • Possible Causes: Too short deceleration time, output short circuit, sudden load changes, etc.
    • Solution: Increase the deceleration time, check the insulation of the motor and cable, check the load, etc.
  3. E007 (Control Power Supply Fault):
    • Possible Causes: Abnormal input voltage, relay failure, etc.
    • Solution: Adjust the input voltage to the normal range, check the relay status, etc.
  4. E015 (Motor Overload):
    • Possible Causes: Excessive load, improper motor parameter settings, undersized inverter selection, etc.
    • Solution: Check the load and mechanical condition, correctly set the motor parameters, replace the inverter with a higher power rating, etc.
  5. E024 (Communication Fault):
    • Possible Causes: Upper computer fault, abnormal communication line, incorrect communication parameter settings, etc.
    • Solution: Check the upper computer and connection line, check the communication line, correctly set the communication parameters, etc.

The KEWO Inverter AD350/AD150 series user manual provides detailed operation guides and fault diagnosis methods to help users quickly get started and resolve issues encountered during use. Through reasonable parameter settings and wiring, users can fully utilize the performance of the inverter to achieve efficient and stable motor control.

Posted on Leave a comment

User Manual Operation Guide for SenDao Inverter SD5000 Series

I. Introduction to the Operation Panel

The SenDao Inverter SD5000 series features an intuitive operation panel, facilitating easy operation and monitoring for users. The operation panel includes a display screen, function selection keys, shift keys, confirm keys, run/stop keys, and more.

Function diagram of SD5000 operation panel

Setting and Releasing the Password

To ensure secure operation, the inverter supports password protection. To set a password:

  1. Enter the Password Setting Menu: Press the PRG key to enter the function parameter menu. Navigate to the password setting function code (typically BP-00).
  2. Set the Password: Use the  and  keys to set the desired password value (ranging from 0 to 65535). Press the ENTER key to confirm.

To release the password:

  1. Enter the Password Setting Menu: Press the PRG key and navigate to the password setting function code (BP-00).
  2. Set the Password to Zero: Use the  and  keys to set the password value to 0. Press the ENTER key to confirm.

Setting Parameter Access Restrictions

To restrict access to certain parameters, you can set the parameter modification attribute. To do this:

  1. Enter the Parameter Attribute Setting Menu: Press the PRG key and navigate to the function code for parameter modification attribute (typically BP-04).
  2. Set the Attribute: Use the  and  keys to set the attribute to “unmodifiable” (value 1). Press the ENTER key to confirm.
SD5000 standard wiring diagram

II. Using the Multi-speed Function

The multi-speed function allows the inverter to operate at different preset speeds. To set up a 5-speed configuration, follow these steps:

Terminal Wiring

  1. Connect the Multi-speed Terminals: Connect the required digital input terminals (DI1 to DI5) to the external control signals that will trigger the different speeds.

Parameter Settings

  1. Enter the Multi-speed Setting Menu: Press the PRG key and navigate to the multi-speed setting function codes (typically BC-00 to BC-15).
  2. Set the Speed Values: Use the  and  keys to set the desired speed values for each multi-speed segment (BC-00 to BC-04 for the first 5 speeds). These values are relative to the maximum frequency set in BO-10.
  3. Configure Terminal Function: Navigate to the input terminal function setting function codes (typically B4-00 to B4-09). Set the desired function for the terminals used for multi-speed control (e.g., DI1 to DI5 as multi-speed terminals 1 to 5).

III. Fault Codes and Troubleshooting

The SenDao Inverter SD5000 series provides fault codes to help users quickly identify and troubleshoot issues. Common fault codes include:

  • E-02: Acceleration overcurrent
  • E-03: Deceleration overcurrent
  • E-04: Constant speed overcurrent
  • E-05: Acceleration overvoltage
  • E-06: Deceleration overvoltage
  • E-07: Constant speed overvoltage
  • E-09: Undervoltage fault
  • E-10: Inverter overload
  • E-11: Motor overload
  • E-12: Input phase loss
  • E-13: Output phase loss
  • E-15: External fault
  • E-16: Communication fault

When a fault occurs, the inverter will stop output, and the fault code will be displayed on the operation panel. To troubleshoot, refer to the fault code and the corresponding troubleshooting steps in the user manual.

By following this operation guide, users can effectively utilize the SenDao Inverter SD5000 series for their control needs, ensuring efficient and reliable operation.

Posted on Leave a comment

Communication Setup Method for Prolet Controller and Yuanxin Inverter YX3000

In modern industrial automation systems, the communication setup between controllers and inverters is crucial for achieving efficient and stable operation. This article will combine the “Prolet Air Compressor Controller and Inverter Communication Setup Manual” and the “Yuanxin Inverter YX3000 Manual” to provide a comprehensive guide on setting up the communication between the Prolet controller and the Yuanxin Inverter YX3000.

Actual working status of Pulet

1. Communication Protocol Description of Prolet Controller

The Prolet controller adopts a communication protocol that is compatible with industry standards, such as MODBUS RTU. This protocol ensures reliable data transmission between the controller and various devices, including inverters. The key features of the Prolet controller’s communication protocol include:

  • Baud Rate: Typically set at 9600 bps, which is a common baud rate for industrial communication.
  • Parity: No parity bit is used to simplify the communication process and reduce errors.
  • Data Bits: 8 data bits are used to ensure sufficient data transmission capacity.
  • Stop Bits: 1 stop bit is employed to mark the end of each data frame.

To establish communication with the Yuanxin Inverter YX3000, the Prolet controller needs to be configured with the appropriate communication parameters, such as the address of the inverter, baud rate, and data format.

2. Communication Protocol Description of Yuanxin Inverter YX3000

The Yuanxin Inverter YX3000 also supports the MODBUS RTU communication protocol, making it compatible with the Prolet controller. The YX3000 offers a wide range of communication settings to meet different application requirements:

  • Communication Interface: Equipped with standard RS485 communication interfaces, the YX3000 can be easily connected to the Prolet controller using shielded twisted-pair cables.
  • Communication Address: Users can set a unique address for each inverter on the network to facilitate multi-inverter communication.
  • Baud Rate and Data Format: The YX3000 supports various baud rates (e.g., 1200, 2400, 4800, 9600, 19200, 38400 bps) and data formats (e.g., 8N1, 8N2).

To establish communication with the Prolet controller, the YX3000 needs to be configured with the same baud rate, data format, and communication address as the controller.

Yuanxin YX3000 physical product

3. Detailed Parameters Required for Communication Between Prolet Controller and YX3000

To set up communication between the Prolet controller and the Yuanxin Inverter YX3000, users need to configure the following detailed parameters on both devices:

  • Communication Address:
    • Prolet Controller: Set the communication address of the YX3000 in the controller’s communication parameters. This address should be unique on the network.
    • YX3000 Inverter: Set the communication address of the inverter to match the address configured in the controller.
  • Baud Rate:
    • Prolet Controller: Set the baud rate to 9600 bps (or other compatible baud rates) in the controller’s communication parameters.
    • YX3000 Inverter: Set the baud rate to 9600 bps (or the same baud rate as the controller) in the inverter’s communication parameters.
  • Data Format:
    • Prolet Controller: Set the data format to 8N1 (8 data bits, no parity, 1 stop bit) in the controller’s communication parameters.
    • YX3000 Inverter: Set the data format to 8N1 (or the same data format as the controller) in the inverter’s communication parameters.
  • Additional Parameters:
    • Prolet Controller: Depending on the specific model and functionality, the controller may require additional communication-related parameters to be configured, such as communication timeout settings, retry intervals, etc.
    • YX3000 Inverter: Similarly, the inverter may also have additional communication parameters that need to be configured, such as communication port settings, communication protocol selection, etc.

After configuring the above parameters, users can test the communication between the Prolet controller and the Yuanxin Inverter YX3000 by sending test commands from the controller and observing the responses from the inverter. If the communication is successful, users can proceed with the integration of the two devices into their industrial automation system.

Posted on Leave a comment

Operation Guide for EURA Inverter E2000 Series User Manual

I. Introduction to Operation Panel Functions and Initialization Settings

The EURA Inverter E2000 series comes equipped with an intuitive and user-friendly operation panel, enabling users to easily set parameters and monitor the inverter’s status. The operation panel typically includes a display screen, direction keys, function keys, and operation control keys.

Restoring Parameter Initialization Settings:

To restore the inverter’s parameters to their factory settings, users need to enter the programming menu and locate function code F160. The specific steps are as follows:

  1. Press the “Mode” key to display the function codes.
  2. Use the “Up” or “Down” key to select function code F160.
  3. Press the “Set” key to enter the setting value interface for F160.
  4. Change the setting value of F160 to 1 and press the “Set” key again to confirm.

At this point, the inverter will begin the initialization process, restoring all parameters to their factory default values.

Setting Passwords and Parameter Locking:

To ensure the security of parameter settings, the E2000 series inverter supports password protection and parameter locking functions. Users can enable or disable password protection by setting function code F107 and set the user password through F100. Once password protection is enabled, users must enter the correct password before modifying parameters.

Setting Reserved Parameter Areas:

The reserved parameter area allows users to save a set of parameters as a macro for quick recall. Users can select the saved macro by setting function code F135 and restore the user macro through F160.

II. Terminal Control and External Input

Terminal Forward/Reverse Control and External Potentiometer Given:

The E2000 series inverter supports forward/reverse control via terminals and frequency given by an external potentiometer. The specific settings are as follows:

  • Forward/Reverse Control: It is necessary to set function codes F200 and F201 to select terminals as the source of start and stop commands. Simultaneously, set F202 to determine the direction of operation.
  • External Potentiometer Given: It is necessary to set function code F203 to select the main frequency source X and choose analog input AI3 (i.e., external potentiometer) as the given source. Additionally, set F422 to select between panel potentiometer and remote panel potentiometer.

For wiring, users need to connect the output terminal of the external potentiometer to the AI3 terminal of the inverter and ensure proper grounding.

Pulse Input/Output Control:

The E2000 series inverter also supports pulse input/output control, suitable for applications requiring high-precision speed control. Users need to set function codes F440 to F449 to configure pulse input parameters such as minimum frequency, maximum frequency, filter constant, etc. Simultaneously, set F450 to F453 to configure pulse output parameters.

For wiring, users need to connect the output terminal of the pulse generator to the FI terminal of the inverter and connect the FO terminal of the inverter to the device receiving the pulse.

III. Fault Code Analysis and Solutions

The EURA Inverter E2000 series is equipped with a comprehensive fault protection mechanism, capable of real-time monitoring and reporting of various faults. Common fault codes include:

  • OC: Overcurrent protection. Possible causes include motor jam, excessive load, etc. Solutions include checking the motor and load, extending acceleration time, etc.
  • OE: DC overvoltage protection. Possible causes include excessive power supply voltage, brake unit failure, etc. Solutions include checking the power supply voltage, inspecting the brake unit, etc.
  • OL1: Inverter overload protection. Possible causes include excessive load, poor heat dissipation, etc. Solutions include reducing the load, improving heat dissipation conditions, etc.
  • OH: Inverter overheat protection. Possible causes include high ambient temperature, fan failure, etc. Solutions include improving ventilation conditions, replacing the fan, etc.

Users can view fault codes through the operation panel and follow the guidance in the manual for troubleshooting and resolution.

IV. Conclusion

The EURA Inverter E2000 series user manual provides a detailed operation guide covering operation panel function introduction, parameter setting, terminal control, fault troubleshooting, and other aspects. By carefully reading the manual and following the guidance, users can easily achieve the installation, commissioning, and maintenance of the inverter. At the same time, the fault code analysis and solutions in the manual also provide strong support for users, helping them quickly resolve issues that may arise during the operation of the inverter.