Posted on Leave a comment

User Guide for Shihlin SE2 Series Frequency Inverter

The Shihlin SE2 series frequency inverter is a high-performance device widely used in various industrial control systems. This article provides a detailed user guide for the Shihlin SE2 series frequency inverter, including an introduction to the operating panel functions, parameter settings, external terminal control, fault codes, and their resolution methods.

Front image of Shilin inverter SE2 series

Introduction to Operating Panel Functions

Password Setting and Removal

The Shihlin SE2 series frequency inverter offers password protection to prevent unauthorized operation. The following are the steps to set and remove the password:

  1. Setting the Password:
  • Enter the parameter setting mode and locate the password setting option (usually P.294 and P.295).
  • Input the desired password and save the settings.
  1. Removing the Password:
  • Enter the parameter setting mode and locate the password setting option.
  • Set the password to the default value (usually 0000) and save the settings.

Parameter Access Restriction

To prevent unauthorized parameter modifications, you can set parameter access restrictions:

  1. Setting Parameter Access Restrictions:
  • Enter the parameter setting mode and locate the parameter access restriction option (usually P.77).
  • Set the parameter access restriction to “Read-only” or “Access Denied” and save the settings.

Parameter Initialization

In some cases, you may need to reset all parameters to their factory settings. The following are the steps for parameter initialization:

  1. Parameter Initialization:
  • Enter the parameter setting mode and locate the parameter initialization option (usually P.998).
  • Select “Restore Factory Settings” and save the settings.

External Terminal Forward/Reverse Start/Stop and External Potentiometer Speed Control

The Shihlin SE2 series supports forward/reverse start/stop and speed control via an external potentiometer. The following are the specific setup steps and wiring methods:

External Terminal Forward/Reverse Start/Stop

  1. Setting Parameters:
  • Enter the parameter setting mode and locate the operation mode selection parameter (usually P.79).
  • Set the operation mode to “External Mode” (usually P.79=2).
  • Set the start terminal function (usually P.78) and select the external forward/reverse terminal.
  1. Wiring:
  • Connect the external start terminal (STF) and stop terminal (STR) to the corresponding terminals on the inverter.

External Potentiometer Speed Control

  1. Setting Parameters:
  • Enter the parameter setting mode and locate the operation mode selection parameter (usually P.79).
  • Set the operation mode to “External Mode” (usually P.79=2).
  • Set the target frequency source to external voltage/current signal (usually P.39).
  1. Wiring:
  • Connect the output terminal of the external potentiometer to the 4-5 terminal of the inverter.
Shilin inverter SE2 series standard wiring diagram

Fault Codes and Their Resolution

The Shihlin SE2 series provides a detailed list of fault codes to help users quickly identify and resolve issues. The following are some common fault codes, their meanings, and resolution methods:

Common Fault Codes

  1. Overcurrent Fault (OC0):
  • Meaning: The inverter detects a current exceeding the set value.
  • Resolution: Check if the motor and load are normal, and ensure the motor is not operating under overload.
  1. Overvoltage Fault (OV0):
  • Meaning: The inverter detects a voltage exceeding the set value.
  • Resolution: Check if the power supply voltage is stable, and ensure the power supply voltage is within the allowed range.
  1. Overheating Fault (OT0):
  • Meaning: The internal temperature of the inverter exceeds the set value.
  • Resolution: Check the heat dissipation of the inverter, ensure good ventilation, and add heat dissipation measures if necessary.
  1. Communication Fault (CM0):
  • Meaning: There is a communication anomaly between the inverter and the upper computer.
  • Resolution: Check if the communication cables are correctly connected, and ensure the communication parameters are set correctly.
  1. Earth Fault (ERR):
  • Meaning: The inverter detects an earth fault.
  • Resolution: Check the grounding of the inverter and ensure it is properly grounded.
  1. Phase Loss Fault (PHL):
  • Meaning: The inverter detects a phase loss in the power supply.
  • Resolution: Check the power supply for any phase loss and ensure all phases are properly connected.

Fault Resolution Steps

  1. Confirm the Fault Code:
  • View the fault code on the inverter’s display to determine the type of fault.
  1. Consult the User Manual:
  • Look up the fault code in the user manual to find the corresponding fault description and resolution method.
  1. Execute the Resolution Method:
  • Follow the instructions in the user manual to resolve the fault and restore the inverter to normal operation.

Conclusion

The Shihlin SE2 series user manual provides detailed operating instructions and fault resolution methods to help users quickly get started and resolve issues during operation. By correctly setting passwords, parameter access restrictions, parameter initialization, external terminal control, and handling fault codes, users can efficiently use and maintain Shihlin SE2 series products. This article aims to provide valuable references to help users better utilize Shihlin SE2 series products.

Posted on Leave a comment

TECO GS510 Series Inverter User Manual Operation Guide

The TECO GS510 series inverter is a high-performance variable frequency drive widely used in industrial automation, ventilation systems, pump equipment, and other fields. This article provides a detailed introduction to the operation panel functions of the GS510 series inverter, parameter initialization, encryption and decryption, parameter access restrictions, external terminal forward and reverse control, external potentiometer speed regulation, fault codes, and their meanings and solutions. Through this article, users can better understand the operation methods of the GS510 inverter, improve equipment utilization efficiency, and reliability.


GS510 working status

I. Operation Panel Function Introduction

1. Operation Panel Overview

The operation panel of the GS510 inverter mainly includes a digital operator and multifunctional terminals. The digital operator comes in two types: LCD display (JNEP-34) and LED display (JNEP-33). Users can choose according to their needs. The main functions of the operation panel include parameter setting, operation control, and fault display.

2. Parameter Initialization

  • Implementation Method:
    By setting the parameter Sn-03 to 1110 or 1111, most parameters of the inverter can be restored to the factory default settings.
  • Steps:
    1. Enter PRGM mode.
    2. Select the parameter Sn-03 and set the value to 1110 or 1111.
    3. After confirmation, the inverter will automatically initialize the parameters.
  • Note: After initialization, the parameters Sn-01, Sn-02, Sn-13, and Sn-23 will not be reset.

3. Encryption and Decryption

  • Encryption Function:
    The GS510 inverter supports parameter encryption to prevent unauthorized personnel from arbitrarily modifying parameters.
  • Encryption Method:
    1. Enter PRGM mode.
    2. Set the parameter Sn-00 to the password value (e.g., 1234).
    3. After confirmation, the inverter enters the encrypted state.
  • Decryption Method:
    1. Enter PRGM mode.
    2. Enter the password value (e.g., 1234).
    3. After confirmation, the inverter exits the encrypted state.

4. Parameter Access Restriction Settings

  • Access Restrictions:
    By setting the parameter Sn-03, the access rights of parameters in different modes can be restricted.
  • DRIVE Mode:
    • Sn-03 = 0000: An, bn parameters can be set, Sn, Cn parameters can only be viewed.
    • Sn-03 = 0101: Only An parameters can be set, other parameters can only be viewed.
  • PRGM Mode:
    • Sn-03 = 0000: All parameters can be set.
    • Sn-03 = 0101: Only An parameters can be set, other parameters can only be viewed.

TECO G510 Label Wiring Diagram

II. External Terminal Control

1. External Terminal Forward and Reverse Control

  • Terminal Connection:
    External forward and reverse control requires the use of control circuit terminals 1 (forward) and 2 (reverse).
  • Wiring Method:
    1. Connect the forward control signal to terminal 1.
    2. Connect the reverse control signal to terminal 2.
  • Parameter Settings:
    1. Set the second bit of parameter Sn-05 to 0, indicating acceptance of external terminal control.
    2. Set the first bit of parameter Sn-03 to 0, indicating that the frequency command comes from the control circuit terminal.

2. External Potentiometer Speed Regulation

  • Terminal Connection:
    External potentiometer speed regulation requires the use of control circuit terminals 13 (voltage type) or 14 (current type).
  • Wiring Method:
    1. Connect the output signal of the potentiometer to terminal 13 (voltage type) or 14 (current type).
    2. Ensure that the output range of the potentiometer matches the input range of the inverter.
  • Parameter Settings:
    1. Set the first bit of parameter Sn-03 to 0, indicating that the frequency command comes from the control circuit terminal.
    2. Set parameter bn-05 to the gain value of the potentiometer, and bn-06 to the offset value of the potentiometer.

III. Fault Codes and Solutions

1. Meaning of Fault Codes

The GS510 inverter displays fault codes through the digital operator to help users quickly identify problems. The following are common fault codes and their meanings:

Fault CodeMeaning
OVOvervoltage fault, main circuit DC voltage exceeds 820V (440V level).
UVUndervoltage fault, main circuit DC voltage below 380V (440V level).
OL1Overload fault, output current exceeds 150% of the rated current.
OCOvercurrent fault, output current exceeds 200% of the rated current.
OHOverheating fault, internal temperature of the inverter is too high.
GFGround fault, electronic circuit detects ground current.

2. Fault Handling Methods

  • Overvoltage (OV) / Undervoltage (UV):
    Check if the input voltage is normal and ensure the stability of the power supply.
  • Overload (OL1) / Overcurrent (OC):
    Check if the load exceeds the rated capacity of the inverter. Reduce the load or replace it with a suitable inverter if necessary.
  • Overheating (OH):
    Check the heat dissipation conditions of the inverter and ensure good ventilation. Install a cooling fan if necessary.
  • Ground Fault (GF):
    Check if the ground wire is correctly connected and ensure that the inverter and motor are grounded separately.

IV. Conclusion

The TECO GS510 series inverter is a powerful and flexible variable frequency drive. By reasonably setting parameters and correctly wiring, various control methods can be realized to meet the needs of different application scenarios. This article provides a detailed introduction to the operation panel functions, parameter initialization, encryption and decryption, parameter access restriction settings, external terminal control, and fault handling methods of the GS510 inverter. It aims to help users better understand the operation methods of the GS510 inverter, improve equipment operation efficiency and reliability. It is hoped that this article will provide valuable reference for users and contribute to the efficient operation of the equipment.

Posted on Leave a comment

RB5000 Series Inverter User Manual Operation Guide

I. Introduction to Operation Panel Functions and Password & Parameter Settings

The operation panel of the Ribbo Inverter RB5000 series is designed to be intuitive and user-friendly, facilitating various operations and settings. The panel mainly includes keys such as PRG/DRIVE, ▲▼, SET, RUN, STOP, JOG, MENU, and multiple indicator display windows.

RB50000 front

Password Setting and Cancellation: The RB5000 series inverter does not directly mention a password setting function, but certain parameters in the High-level Parameter Group (HP) may involve access restrictions. To set similar password-like access restrictions, the HP-03 parameter can be modified to set the parameter group modification permissions. For example, setting HP-03 to a non-zero value will restrict access and modification to the AP, LP, HP, and PP parameter groups.

Parameter Access Restriction: By setting the HP-03 parameter, users can restrict access and modification permissions to the inverter parameters. For instance, when HP-03=0, all parameter groups can be viewed and modified; when HP-03=1, only the AP parameter group can be viewed and modified, while the other parameter groups can only be viewed.

Restoring Factory Default Settings: To restore the inverter parameters to their factory settings, the HP-03 parameter can be set to 07 or 08, which will not only restore all parameters to their factory defaults but also set the inverter to two-wire or three-wire start/stop control mode.

II. Terminal Forward/Reverse Control and External Potentiometer Speed Regulation

Terminal Forward/Reverse Control: The RB5000 series inverter supports motor forward/reverse control through external terminals. First, the control mode needs to be set to terminal control by setting the HP-04 parameter to 1. Then, depending on the requirements, the HP-03 parameter can be set to select two-wire or three-wire control mode. In two-wire control mode, terminal X1 is the forward start/stop command, and terminal X2 is the reverse start/stop command. In three-wire control mode, terminal X1 is the forward start command, terminal X2 is the reverse start command, and terminal X5 is the stop command.

External Potentiometer Speed Regulation: To regulate speed using an external potentiometer, the frequency command source needs to be set to external analog input by setting the HP-05 parameter to 1. Then, connect the external potentiometer to the VS terminal (voltage input, 0-10V) and GND terminal (common ground). Depending on the output characteristics of the potentiometer, the LP-05 (analog voltage frequency command gain) and LP-06 (analog voltage frequency command offset) parameters may also need to be adjusted to ensure that the speed regulation range matches the potentiometer output range.

RB5000 standard wiring diagram for Ribo Paint frequency converter

III. Fault Codes and Troubleshooting

The RB5000 series inverter features comprehensive fault protection and alarm functions. When a fault occurs, the inverter will display a fault code through the LED to help users quickly locate the problem. Below are some common fault codes, their meanings, and troubleshooting methods:

  • UE1 (UE): Under-voltage on the DC side of the main circuit. Possible causes include insufficient power supply capacity, excessive voltage drop in power supply lines, and power contactor failure. Solutions include checking the power supply voltage, power supply lines, and contactor.
  • OE: Over-voltage on the DC side of the main circuit. Possible causes include too short a deceleration time, excessively high input voltage, or voltage spikes. Solutions include increasing the deceleration time, checking the input voltage, and ensuring power supply stability.
  • OH: Internal overheating of the inverter. Possible causes include a malfunctioning cooling fan, poor ventilation, and blocked heat dissipation channels. Solutions include checking the cooling fan, improving ventilation, and clearing heat dissipation channels.
  • OC: Output current of the inverter exceeds 200% of the rated value. Possible causes include too short an acceleration time, excessively large motor capacity, output short circuit or grounding. Solutions include increasing the acceleration time, checking the motor and output lines.
  • OL1: Motor output overload. Possible causes include improper setting of the rated current and long-term motor overload. Solutions include adjusting the rated current setting and checking the motor load.

When a fault occurs, users should refer to the fault code and fault phenomenon, combined with the fault analysis and troubleshooting methods in the user manual, to troubleshoot and resolve the issue step-by-step. If the problem cannot be resolved independently, users can contact Ribbo Electric’s customer service center or distributor for assistance.

IV. Conclusion

The Ribbo Inverter RB5000 series user manual provides a detailed operation guide and troubleshooting methods, helping users better understand and use the inverter. Through this guide, users should be able to master the basic functions of the operation panel, parameter setting methods, terminal control and external speed regulation implementation, as well as fault code interpretation and troubleshooting. In practical applications, users should strictly follow the operating instructions and safety precautions in the user manual to ensure the normal operation and safe use of the inverter.

Posted on Leave a comment

Operation Guide for the Tai’an Inverter N2 Series User Manual

I. Introduction to the Operation Panel Functions

The operation panel of the Tai’an Inverter N2 series is designed to be intuitive and feature-rich, facilitating various settings and monitoring for users. The panel primarily includes the following function keys and indicator lights:

  • FREQ.SET: Used to set the output frequency.
  • ▲▼: Increase or decrease the set value.
  • READ: Read the current display content.
  • ENTER: Confirm the settings.
  • RUN: Start the inverter.
  • STOP: Stop the inverter.
  • DSP: Switch between display contents, such as frequency, speed, linear velocity, etc.
  • FUN: Enter the function setting mode.
  • FWD/REV: Forward/Reverse indicator lights, showing the current operating direction.
  • Hz/RPM/VOLT/AMP: Indicate frequency, speed, voltage, and current, respectively.
N2 standard wiring diagram

II. Password Setting and Parameter Access Restrictions

To ensure the security of the inverter settings, the N2 series provides a password protection function. Users can follow these steps to set and remove passwords:

  1. Setting a Password:
    • Enter the function setting mode (FUN).
    • Use the ▲▼ keys to select the password setting option.
    • Enter the password value using the FREQ.SET key.
    • Press the ENTER key to confirm.
  2. Removing a Password:
    • Enter the function setting mode (FUN).
    • Select the password setting option.
    • Set the password value to 0 and press the ENTER key to confirm.
  3. Parameter Access Restrictions:
    • Users can restrict access to frequency parameters by setting parameter F_004. When F_004 is set to XXX1, frequency parameters are locked and cannot be modified.
  4. Parameter Initialization:
    • Users can initialize the inverter parameters by setting parameter F_123. Setting F_123 to 1111 or 1110 will restore the inverter to its factory settings.
N2 front

III. External Terminal Forward/Reverse Control and External Potentiometer Speed Regulation

The N2 series inverter supports forward/reverse control and external potentiometer speed regulation through external terminals. Specific settings and wiring are as follows:

  1. Forward/Reverse Control:
    • Parameter Setting: Set F_003 to XX01 (forward/reverse mode).
    • Terminal Wiring: Connect the forward control signal to terminal 3 of TM2, the reverse control signal to terminal 4, and the common terminal to terminal 5.
  2. External Potentiometer Speed Regulation:
    • Parameter Setting: Set F_011 to 1 (frequency instruction set by the potentiometer on the panel) or 2 (frequency instruction set by the potentiometer or analog signal on the TM2 multifunction terminal).
    • Terminal Wiring: Connect the output terminal of the external potentiometer to terminal 13 of TM2 (analog input point), and the common point of the analog signal to terminal 14.
N2 side

IV. Fault Codes and Solutions

During operation, the N2 series inverter may display various fault codes. Users need to take corresponding measures based on the code meanings:

  1. OC (Overcurrent):
    • Meaning: The output current of the motor or inverter exceeds the rated value.
    • Solution: Check if the motor is overloaded, adjust the acceleration time or V/F curve, and ensure that the motor matches the inverter capacity.
  2. OL1 (Motor Overload):
    • Meaning: The motor overload protection has activated.
    • Solution: Check if the load is too heavy, adjust the motor protection parameters F_069 and F_070, and ensure that the motor operates within the rated load.
  3. OL2 (Inverter Overload):
    • Meaning: The output current of the inverter exceeds the rated value for an extended period.
    • Solution: Check if the load is too heavy, adjust the acceleration time, or increase the inverter capacity.
  4. OV (Overvoltage):
    • Meaning: The DC bus voltage of the inverter is too high.
    • Solution: Check if the power supply voltage is too high, adjust the deceleration time, or install a braking resistor.
  5. LV (Low Voltage):
    • Meaning: The input power supply voltage is too low.
    • Solution: Check if the power supply voltage is normal and adjust the allowable instantaneous stop time parameter F_031.
  6. OH (Heat Sink Overheat):
    • Meaning: The temperature of the inverter heat sink is too high.
    • Solution: Check if the ventilation conditions are good, clean the heat sink dust, reduce the load, or increase the inverter capacity.

Through this operation guide, users can better understand and use the Tai’an Inverter N2 series, ensuring the normal operation and efficient energy saving of the inverter. In practical applications, users should also reasonably set the inverter parameters according to specific loads and process requirements to achieve the best control effect.

Posted on Leave a comment

Burmagor Inverter TD300 Series User Manual Guide

I. Introduction to Operation Panel Functions

The Burmagor Inverter TD300 series is equipped with an intuitive and user-friendly operation panel, facilitating various settings and operations for users. The following is an introduction to the main functions of the operation panel:

TD300 front

1.1 Setting and Eliminating a Password

To ensure the security of inverter settings, the TD300 series inverter provides a password protection function. Users can restrict access to the inverter by setting a password. The method for setting a password is as follows:

  1. Enter the parameter setting interface.
  2. Locate the parameter related to password setting (please refer to the user manual for the specific parameter number).
  3. Input the desired password value.

To eliminate an already set password, simply reset the password parameter to its default value.

1.2 Setting Parameter Access Restrictions

In addition to password protection, the TD300 series inverter also supports restricting access to parameters. Users can lock specific parameters as needed to prevent unauthorized modifications. The method for setting parameter access restrictions is as follows:

  1. Enter the parameter setting interface.
  2. Locate the parameter related to parameter locking (such as F1.18).
  3. Set this parameter to the locked state.
TD300 series standard wiring diagram

1.3 Parameter Initialization Setting

When it is necessary to restore factory settings or resolve certain parameter setting errors, users can use the parameter initialization function. The specific operation steps are as follows:

  1. Enter the parameter setting interface.
  2. Locate the parameter related to parameter initialization (such as F1.17).
  3. Set this parameter to the initialization value (usually 8), and the inverter will return to its factory settings.

II. Terminal Forward/Reverse Start/Stop and External Potentiometer Speed Control

The TD300 series inverter supports terminal forward/reverse start/stop and external potentiometer speed control functions. The following are the steps and parameters required to implement these functions:

2.1 Terminal Forward/Reverse Start/Stop

To implement the terminal forward/reverse start/stop function, the following parameters need to be set:

  • F1.02: Operation setting selection. Set to 1 (IO terminal), indicating that the operation command is given by the IO port.
  • F3.15-F3.16: Multi-function input terminal settings. Define the FWD terminal as forward (e.g., F3.15=6) and the REV terminal as reverse (e.g., F3.16=7).

In terms of wiring, external control signals need to be connected to the FWD and REV terminals, and the forward/reverse start/stop is achieved by controlling the on/off state of these two terminals.

2.2 External Potentiometer Speed Control

To implement the external potentiometer speed control function, the following parameter needs to be set:

  • F1.01: Frequency setting selection. Set to 3 (keypad potentiometer setting mode), indicating that the operating frequency of the inverter is controlled by the potentiometer on the operator.

In terms of wiring, the output terminal of the external potentiometer needs to be connected between the +10V and FIV terminals of the inverter. By adjusting the knob of the potentiometer, the output frequency of the inverter can be changed, thereby achieving speed control.

TD300 Side

III. Fault Codes and Their Handling

The TD300 series inverter has a comprehensive protection function. When a fault occurs, it displays the corresponding fault code. The following are some common fault codes, their meanings, and handling methods:

3.1 OC1/OC3 (Overcurrent during acceleration/operation)

  • Meaning: There is an overcurrent phenomenon in the motor or output circuit.
  • Handling methods:
    1. Check if the motor and output circuit are short-circuited or grounded.
    2. Extend the acceleration time (F1.07).
    3. Reduce the torque boost setting value (F2.08).
    4. Check if the grid voltage is stable.

3.2 OU1/OU3 (Overvoltage during acceleration/operation)

  • Meaning: The output voltage of the inverter is too high.
  • Handling methods:
    1. Extend the deceleration time (F1.08).
    2. Install a braking unit and braking resistor.
    3. Check if the power supply voltage is too high.

3.3 LU0/LU1/LU2/LU3 (Low voltage during standby/acceleration/deceleration/operation)

  • Meaning: The power supply voltage is too low.
  • Handling methods:
    1. Check if the power supply voltage is normal.
    2. Check if the power supply circuit has poor contact or is open-circuited.

3.4 OL0/OL1/OL2/OL3 (Overload during no operation/acceleration/deceleration/operation)

  • Meaning: The motor load is too heavy.
  • Handling methods:
    1. Reduce the load or increase the inverter capacity.
    2. Extend the acceleration time (F1.07).
    3. Check if the motor is stalled or seized.

IV. Conclusion

This article provides a detailed introduction to the operation panel functions of the Burmagor Inverter TD300 series, the setting methods for terminal forward/reverse start/stop and external potentiometer speed control, as well as common fault codes and their handling methods. By reasonably using these functions and settings, users can better control and maintain the inverter, ensuring stable operation of the equipment. At the same time, in the event of a fault, users can quickly resolve the issue based on the provided handling methods, reducing downtime and improving production efficiency.

Posted on Leave a comment

COTRUST CTF220 Series User Manual Operation Guide

1. COTRUST CTF220 Frequency Inverter Operation Panel Functions

The operation panel of the COTRUST CTF220 frequency inverter is designed to be intuitive and feature-rich, making it easy for users to perform device debugging and control operations. The panel consists of a display screen and various function buttons. The main functional areas include:

  1. Display Screen: Displays important parameters such as operating status, frequency, speed, voltage, and current.
  2. Control Buttons: Includes buttons like “RUN,” “STOP,” and “REV” for controlling the inverter’s start, stop, and running direction.
  3. Function Keys: Used to enter menu modes for setting various parameters.
  4. Adjustment Knob: Used to adjust the inverter’s operating frequency, speed, and more.
  5. Indicator Lights: Indicate the inverter’s operational status, such as running, fault, and remote control.
Front image of CTF220

Setting and Clearing Passwords

  1. Setting the Password: The inverter allows you to set a password to prevent unauthorized personnel from changing critical parameters. The steps to set the password are:
    • Enter the settings menu and choose the “Password Protection” option (e.g., F0.36).
    • Input the desired password (e.g., set the password as “1234”) and save it.
  2. Clearing the Password: If you need to remove the password protection, you can find the “Password Protection” setting on the operation panel and set the password value to zero (F0.36 set to “0”). This will disable the password.

Setting Parameter Access Restrictions

To prevent unauthorized modifications, you can set parameter access restrictions. After entering the menu, select the “Access Restrictions” option and define which parameters need protection and which can be freely adjusted. Once the settings are complete, the protected parameters can only be modified by entering the correct password.

Restoring Factory Settings

If issues arise with the inverter or you wish to reset it to its initial state, you can restore the inverter to its factory settings. Use function code F0.50 to choose the option “Restore Factory Settings.” After restoring, the inverter will revert to the default parameters, including both user settings and factory defaults.

2. COTRUST CTF220 Frequency Inverter Terminal Forward and Reverse Control and External Potentiometer Speed Regulation

Terminal Forward and Reverse Control

Forward and reverse control is an essential feature of the inverter, allowing users to control the inverter’s direction via terminals. The wiring method for achieving terminal forward and reverse control is as follows:

  1. Wiring Terminals:
    • Terminal X1: Used for forward rotation control (connect to external switch or relay to control forward operation).
    • Terminal X2: Used for reverse rotation control (connect to external switch or relay to control reverse operation).
    • Terminal COM: Common terminal connected to control terminals.
  2. Setting Parameters:
    • By configuring function code F4.01, you can set Terminal X1 for forward rotation and Terminal X2 for reverse rotation.
CTF220

External Potentiometer Speed Regulation

External potentiometer speed regulation allows the frequency inverter to adjust its output frequency by using an external potentiometer. To achieve this functionality, follow these steps:

  1. Wiring Terminals:
    • Terminal AI1: External potentiometer input terminal, connected to the output of the potentiometer.
    • Terminal GND: Ground terminal for the potentiometer.
  2. Setting Parameters:
    • Enter the settings menu and select function code F0.02, setting the main frequency command to “AI1” input (i.e., choose the external potentiometer as the frequency set point).
    • Ensure that the potentiometer’s adjustment range matches the required frequency range.

3. COTRUST CTF220 Frequency Inverter Fault Codes and Solutions

During the operation of the inverter, fault codes help users quickly diagnose issues. Below are the common fault codes for the COTRUST CTF220 frequency inverter, along with their meanings and solutions:

  1. E01: Overload Protection Fault
    • Meaning: The output current of the inverter exceeds the set overload protection value, causing the device to stop automatically.
    • Solution: Check if the motor and load are functioning normally. Reduce the load or increase the overload protection value. If it happens frequently, check the motor for issues or reset the operating parameters.
  2. E02: Overheating Fault
    • Meaning: The internal temperature of the inverter exceeds the allowable range.
    • Solution: Check if the cooling system is functioning correctly, clean the heat sinks and fans, and ensure proper ventilation. You may need to reduce the load or add additional cooling equipment.
  3. E03: Input Voltage Fault
    • Meaning: The input voltage is either too low or too high, exceeding the inverter’s rated range.
    • Solution: Check the power supply voltage and ensure it is within the inverter’s rated range. If the voltage is abnormal, contact the power supply company for repairs.
  4. E04: Communication Fault
    • Meaning: There is a communication issue between the inverter and the external control system.
    • Solution: Check the communication wiring for loose or disconnected cables and ensure the communication protocol is set up correctly.
  5. E05: Short Circuit Fault
    • Meaning: A short circuit occurs between the inverter’s output terminals and the motor.
    • Solution: Check the wiring between the inverter’s output terminals and the motor to ensure no short circuit. Inspect the motor cables for insulation damage.

4. Conclusion

The COTRUST CTF220 frequency inverter is a versatile control device with an intuitive operation panel, allowing users to efficiently manage settings, perform troubleshooting, and control operations. By configuring the password settings, terminal controls, and external potentiometer speed regulation, users can enhance the performance and stability of the inverter. Additionally, understanding the common fault codes and their solutions will help users diagnose and address issues quickly, ensuring the device operates smoothly for an extended period.

Posted on Leave a comment

Operation Guide for Colran Inverter CV800 Series User Manual

I. Introduction to the Operation Panel Functions and Initialization Settings

The Colran Inverter CV800 series features an intuitive operation panel with clear buttons and a display screen, facilitating various settings and monitoring tasks for users. The operation panel primarily includes run/stop keys, frequency adjustment keys (▲/▼), function keys, and a display screen.

EPOF Fault

Parameter Initialization:

  • Press the function key to enter the parameter setting interface.
  • Use the ▲/▼ keys to select the F8.03 parameter (Parameter Initialization).
  • Press the run/stop key to set F8.03 to 1, which will restore the factory settings, and all user parameters will be reset to their factory defaults.

Setting and Removing Password:

  • Password Setting: Set through the F0.23 parameter (User Password). Set any non-zero number, which will take effect after waiting for 3 minutes or a power cycle.
  • Password Removal: Set the F0.23 parameter value to 0 to remove the password.

Setting Parameter Access Restrictions:

  • The CV800 series inverters provide parameter access restriction functions, but the specific implementation method is not explicitly mentioned in the manual. Generally speaking, parameter access restrictions can be indirectly achieved by setting a password, allowing only users who know the password to modify critical parameters.

II. Terminal Forward/Reverse Control and External Potentiometer Given Frequency Speed Regulation

Terminal Forward/Reverse Control:

  • Wiring:
    • Connect the forward control signal to the X1 terminal (Forward Control, FWD).
    • Connect the reverse control signal to the X2 terminal (Reverse Control, REV).
    • Ensure the common terminal (COM) is correctly connected.
  • Parameter Setting:
    • Set F0.02 parameter (Operation Command Channel Selection) to 1 (Terminal Operation Command Channel).
    • Set F2.13 parameter (Input Terminal X1 Function) to 3 (Forward Control).
    • Set F2.14 parameter (Input Terminal X2 Function) to 4 (Reverse Control).

External Potentiometer Given Frequency Speed Regulation:

  • Wiring:
    • Connect the output terminal of the external potentiometer to the AI terminal (Analog Input).
    • Ensure the common terminal (COM) is correctly connected.
  • Parameter Setting:
    • Set F0.03 parameter (Frequency Given Selection) to 0 (Panel Potentiometer) or 3 (AI Analog Given).
    • Set F2.00 (AI Input Lower Limit Voltage) and F2.01 (AI Input Upper Limit Voltage) as needed.
    • F2.02 (AI Lower Limit Correspondence Setting) and F2.03 (AI Upper Limit Correspondence Setting) are used to set the correspondence between AI input and output frequency.
CV800 Terminal Wiring Diagram

III. Fault Codes and Solutions

The CV800 series inverters provide a wealth of fault codes to help users quickly locate and resolve issues. Below are some common fault codes, their meanings, and solutions:

  • E0C1: Overcurrent During Acceleration.
    • Meaning: The current during acceleration exceeds the allowable limit.
    • Solution: Extend the acceleration time, check if the load is too heavy, or select an inverter with higher power.
  • E0C2: Overcurrent During Deceleration.
    • Meaning: The current during deceleration exceeds the allowable limit.
    • Solution: Extend the deceleration time and check for sudden load changes.
  • EHU1: Overvoltage During Acceleration.
    • Meaning: The voltage during acceleration exceeds the allowable limit.
    • Solution: Check for abnormal input power or set the DC braking function.
  • EPOF: Dual CPU Communication Fault.
    • Meaning: Internal CPU communication within the inverter is abnormal.
    • Solution: Restart the inverter. If the problem persists, contact the manufacturer for repair.
  • E-OH: Heatsink Overheated.
    • Meaning: The temperature of the inverter’s heatsink is too high.
    • Solution: Check if the ambient temperature is too high, clean the air duct, or replace the fan.

IV. Conclusion

The Colran Inverter CV800 series, with its rich functionality and stable performance, has found widespread application in the industrial automation field. This operation guide enables users to easily master the basic operation, parameter settings, terminal wiring, and troubleshooting methods of the inverter, ensuring its normal operation and efficient use. Meanwhile, users should regularly check the working status of the inverter, promptly detect and resolve issues to guarantee the continuous and stable operation of the production line. In practical applications, users should also perform personalized settings based on specific needs to fully leverage the performance advantages of the inverter.

Posted on Leave a comment

ADSEN Variable Frequency Drive ADS-V Series User Manual Operation Guide

I. Introduction to Operation Panel Functions

The operation panel of the ADSEN Variable Frequency Drive (VFD) ADS-V series serves as a crucial interface for user interaction with the device. The panel typically includes multiple function keys and a display screen, allowing users to perform operations such as start, stop, frequency setting, and parameter modification. The main function keys on the panel include:

  • Run Key: Starts the VFD operation.
  • Stop/Reset Key: Stops the VFD operation or resets it after a fault occurs.
  • Forward/Reverse Switch Key: Switches the running direction of the VFD.
  • Set Key: Enters the parameter setting mode.
  • Display/Shift Key: Cycles through different parameters such as output frequency, current, temperature, etc., in display mode.
Front image of ADSEN VFD

1.1 Initializing Parameters (Restoring Factory Settings)

To restore all parameters of the VFD to factory settings, users can follow these steps:

  1. Press the “Set” key to display “Pr000”.
  2. Use the “Increase” or “Decrease” key to adjust to “Pr013” (parameter reset) and set the value to “01”.
  3. Press the “Confirm” key (usually the “Jog” key) to confirm the reset.
  4. At this point, the VFD will restore to factory settings, and all user-set parameters will be cleared.

1.2 Setting and Removing a Password

To protect the parameter security of the VFD, users can set a password to prevent unauthorized access. The specific steps are as follows:

  1. Enter the parameter setting mode and locate “Pr000” (parameter lock).
  2. Set the value to “1” to enable password protection.
  3. To remove the password, set it to “0”.

1.3 Setting Parameter Access Restrictions

After setting the parameter lock in “Pr000”, users can prevent others from modifying the parameters. A setting of “0” indicates invalid, while “1” indicates valid. Users must unlock before modifying parameters.

II. External Terminal Forward/Reverse Control and External Potentiometer Frequency Speed Adjustment

2.1 External Terminal Forward/Reverse Control

To achieve external terminal forward/reverse control, users need to wire the following terminals:

  • X1 Terminal: Run control signal.
  • X2 Terminal: Reverse control signal.
  • X3 Terminal: Stop control signal.

Parameter Settings:

  1. Set “Pr001” to “1” to select external terminal control.
  2. Set “Pr044” to “02” to assign X1 as run.
  3. Set “Pr045” to “03” to assign X2 as reverse.
  4. X3 terminal can be set as stop.

2.2 External Potentiometer Frequency Speed Adjustment

Connect the external potentiometer to the following terminals:

  • FV Terminal: Frequency setting input.
  • GND Terminal: Ground.

Parameter Settings:

  1. Set “Pr001” to “1” to select external terminal control.
  2. Set “Pr002” to “1” to select external potentiometer for frequency setting.
  3. Set “Pr072” to the desired maximum frequency (e.g., 50Hz).

With these settings, users can adjust the output frequency of the VFD using an external potentiometer.

ADSEN VFD physical image

III. Fault Codes and Troubleshooting

The ADSEN VFD ADS-V series provides multiple fault protection functions. Common fault codes and their troubleshooting methods are as follows:

3.1 Common Fault Codes

  • OU-1: Overvoltage during acceleration
    • Troubleshooting: Check the grid voltage and extend the acceleration/deceleration time.
  • OU-2: Overvoltage during deceleration
    • Troubleshooting: Extend the deceleration time or install a braking resistor.
  • FB: Fuse blown
    • Troubleshooting: Send for factory repair.
  • OH: VFD overheat
    • Troubleshooting: Check if the fan is blocked and ensure the ambient temperature is normal.
  • OL-1: VFD overcurrent or overload
    • Troubleshooting: Check if the load is too large and reset the parameters.
  • LV: Undervoltage
    • Troubleshooting: Check if the input voltage is normal.

3.2 Fault Handling

In the event of a fault, immediately press the stop key and record the fault code. Users should refer to the manual for corresponding checks and troubleshooting based on the fault code. If the fault cannot be resolved, contact professional technicians for repair.

IV. Summary

The user manual of the ADSEN VFD ADS-V series provides a detailed operation guide. Users should be familiar with the functions of the operation panel and fault troubleshooting methods during daily operations. By properly setting parameters and conducting effective maintenance checks, the normal operation of the VFD can be ensured, and its service life can be extended. In practical applications, if any issues are encountered, users should refer to the manual for resolution or contact professionals for support.

Posted on Leave a comment

Operation Guide for Ruishen Inverter RCP900 Series User Manual

I. Introduction to Operation Panel Functions and Parameter Initialization

The Ruishen Inverter RCP900 series is equipped with an intuitive and user-friendly operation panel, which integrates a data display area, command source indicators, forward/reverse indicators, and various other functions. Through this panel, users can easily perform parameter settings, working status monitoring, operation control, and other operations of the inverter.

RCP900正面图片

Parameter Initialization:

Before using the RCP900 series inverter, it is sometimes necessary to initialize the parameters to restore the factory settings. This can be achieved by setting the function code PP-01. Setting PP-01 to 1 will restore the inverter’s factory parameters (excluding motor parameters). This step is particularly important for resolving inverter faults caused by incorrect parameter settings.

Password Setting and Removal:

To protect the inverter settings from unauthorized changes, the RCP900 series inverter supports password protection. Users can set a password by configuring the function code PP-00. To remove the password, simply set PP-00 to 0. The password protection feature effectively prevents unauthorized operations and ensures the safety and stability of the inverter’s operation.

Parameter Access Restriction:

In addition to password protection, the RCP900 series inverter also supports parameter access restriction functionality. Users can select which parameter groups or specific parameters can be accessed and modified by configuring the function codes PP-03 and PP-04. This feature allows users to flexibly control access permissions to the inverter parameters based on actual needs, enhancing the security of device management.

RCP900 Side Image

II. Terminal Forward/Reverse Control and External Potentiometer Speed Regulation

Terminal Forward/Reverse Control:

The RCP900 series inverter supports forward/reverse control of the motor through terminals. The specific wiring method is as follows: Connect the forward control signal to the DI1 terminal, the reverse control signal to the DI2 terminal, and the common terminal to the COM terminal. In terms of parameter settings, it is necessary to set P0-02 (Run Command Selection) to 1 (Terminal Command), P4-00 (DI1 Terminal Function Selection) to 1 (Forward Run), and P4-01 (DI2 Terminal Function Selection) to 2 (Reverse Run). After completing these settings, the motor’s forward/reverse control can be achieved by controlling the electrical level status of the DI1 and DI2 terminals.

External Potentiometer Speed Regulation:

The RCP900 series inverter also supports speed regulation through an external potentiometer. The specific wiring method is as follows: Connect the output end of the external potentiometer to the AI1 terminal and the GND terminal to the inverter’s GND terminal. In terms of parameter settings, it is necessary to set P0-03 (Main Frequency Command Input Selection) to 4 (AI3 Panel Potentiometer). After completing these settings, the motor speed can be adjusted by adjusting the resistance value of the external potentiometer.

RCP900 Standard Wiring Diagram

III. Fault Code Meaning Analysis and Troubleshooting

During operation, the RCP900 series inverter may encounter various faults. When a fault occurs, the inverter will display the corresponding fault code. Below are some common fault codes, their meanings, and troubleshooting methods:

  • Err02: Acceleration Overcurrent. Possible causes include grounding or short circuit in the output circuit, incorrect motor parameter settings, etc. Solutions include troubleshooting peripheral issues, performing motor parameter identification, etc.
  • Err03: Deceleration Overcurrent. Possible causes are similar to those of acceleration overcurrent. Solutions also include troubleshooting peripheral issues, increasing deceleration time, etc.
  • Err05: Acceleration Overvoltage. Possible causes include high input voltage, short acceleration time, etc. Solutions include adjusting the input voltage, increasing the acceleration time, etc.
  • Err14: IGBT Overheat. Possible causes include high ambient temperature, fan failure, etc. Solutions include lowering the ambient temperature, replacing the fan, etc.

For the above fault codes, users can adopt corresponding solutions based on the inverter’s display information, combined with fault phenomena and possible causes. If the issue cannot be resolved, it is recommended to contact Ruishen Inverter’s technical support personnel or professional maintenance personnel for assistance.

IV. Conclusion

The Ruishen Inverter RCP900 series user manual provides a detailed operation guide, including operation panel function introduction, parameter initialization, password setting and removal, parameter access restriction, terminal forward/reverse control, external potentiometer speed regulation, fault code meaning analysis, troubleshooting methods, and other content. By carefully reading and understanding the user manual, users can better master the inverter’s usage methods and maintenance skills, ensuring the normal operation of the equipment and extending its service life. At the same time, users should flexibly utilize the inverter’s various functions based on actual needs to achieve more efficient and stable motor control.

Posted on Leave a comment

Operation Guide for Instar-Tech AE200H Series Frequency Converter User Manual

I. Introduction to Operation Panel Functions

The Instar-Tech AE200H series frequency converter features a concise and straightforward operation panel design, facilitating intuitive operation and monitoring. The main function keys and indicator lights on the operation panel include:

  • RUN Key: Press this key to start the frequency converter. In programming mode, this key can be used as a shift key.
  • JOG Key: Press this key to enter jogging mode and switch between forward and reverse rotation.
  • STOP Key: Press this key to stop the frequency converter. After a fault alarm, pressing this key can reset the system.
  • PROG Key: Press this key to enter the function setting mode. After modification, press it again to exit the setting mode.
  • DATA Key: In programming mode, press this key to confirm the function code and parameter content. After modification, press it again to save the data.
  • UP Key and DOWN Key: In programming mode, use these keys to adjust the numerical values of function codes and parameter data.
  • Shift Key (<< / REV): In programming mode, use this key to shift during parameter data modification.

Additionally, the operation panel has multiple indicator lights to display the operating status of the frequency converter, such as the RUN, STOP, FWD, and REV indicators.

Function diagram of AE200H operation panel

II. Password Setting and Parameter Access Restrictions

To protect the frequency converter’s settings from unauthorized modification, the AE200H series provides a password setting function. Users can set a password to restrict access and modification of frequency converter parameters. The specific steps are as follows:

  1. Set Password: Enter programming mode, locate the user password parameter (e.g., P.089), and set a non-zero value as the password.
  2. Enter Password: When modifying parameters, the system will prompt for a password. Only by entering the correct password can you access the parameter modification interface.
  3. Eliminate Password: To eliminate the password, simply reset the user password parameter value to 0.

Furthermore, the AE200H series frequency converter offers parameter access restriction functions. Users can set different access levels to restrict different users’ access to frequency converter parameters.

III. Parameter Initialization

If users need to restore the frequency converter to its factory settings, they can perform a parameter initialization operation. The specific steps are as follows:

  1. Enter programming mode.
  2. Locate the factory reset parameter (e.g., P.XXX, refer to the user manual for specific codes) and set its value to 1.
  3. Press the DATA key to save the setting and restart the frequency converter.

After restarting, the frequency converter will return to its factory settings, and all user-set parameters will be cleared.

IV. Terminal Forward/Reverse Control and External Potentiometer Speed Regulation

The AE200H series frequency converter supports motor forward/reverse control through external terminals and speed regulation through an external potentiometer. The specific settings and wiring methods are as follows:

  1. Terminal Forward/Reverse Control
    • Parameter Setting: No special setting is required; ensure correct wiring.
    • Wiring Method: Connect the forward control terminal (e.g., S1) and reverse control terminal (e.g., S2) to the corresponding contacts in the control circuit. By controlling the on/off status of these contacts, you can achieve motor forward/reverse rotation and stopping.
  2. External Potentiometer Speed Regulation
    • Parameter Setting: Locate the speed control mode selection parameter (e.g., P.XXX) and set its value to external given.
    • Wiring Method: Connect the output terminal of the external potentiometer to the speed regulation input terminal of the frequency converter (e.g., AI1 or AI2). By adjusting the resistance value of the potentiometer, you can change the output frequency of the frequency converter, thereby achieving motor speed regulation.

V. Fault Codes and Solutions

The AE200H series frequency converter features comprehensive fault diagnosis capabilities. When a fault occurs, the corresponding fault code will be displayed on the screen. Here are some common fault codes, their meanings, and solutions:

  1. OC1/OC2/OC3: Overcurrent during acceleration/deceleration/constant speed.
    • Meaning: The output current of the frequency converter exceeds the rated value.
    • Solution: Check if the motor load is excessive, check the power line connection for good contact, and check if the frequency converter parameter settings are reasonable (e.g., acceleration/deceleration time, overload protection).
  2. OU1/OU2/OU3: Overvoltage during acceleration/deceleration/constant speed.
    • Meaning: The input voltage of the frequency converter is too high or the braking resistor is damaged.
    • Solution: Check if the power supply voltage is stable and inspect the braking resistor for damage or poor connection.
  3. UV: Undervoltage on the bus.
    • Meaning: The input voltage of the frequency converter is lower than the rated voltage.
    • Solution: Check if the power supply voltage is normal and inspect the power line connection for good contact.
  4. OL1: Motor overload.
    • Meaning: The motor load is excessive or the motor parameter settings are incorrect.
    • Solution: Check if the motor load is excessive and verify the motor parameter settings (e.g., rated current, power).
  5. OH2: Frequency converter overheat.
    • Meaning: The internal temperature of the frequency converter is too high.
    • Solution: Check if the frequency converter installation environment is well-ventilated and inspect the cooling fan for normal operation.
AE200H standard wiring diagram

VI. Conclusion

This article provides a detailed operation guide for the Instar-Tech AE200H series frequency converter, covering the introduction to operation panel functions, password setting and parameter access restrictions, parameter initialization, terminal forward/reverse control, external potentiometer speed regulation, fault codes and solutions, and other related content. We hope this guide will help users better understand and utilize this series of frequency converters to ensure their efficient and stable operation.