Posted on

MIKOM MV Series Inverter User Manual Guide


The MIKOM MV series inverter is a crucial device in the field of industrial automation, and its user manual elaborates on key aspects such as equipment operation, parameter settings, and troubleshooting. This article provides systematic guidance on four core modules: operation panel functions, parameter settings, external control, and fault handling, based on the content of the manual.

MV10G front

1. Operation Panel Function Analysis

The operation panel is the direct interface for users to interact with the inverter, designed with both functionality and ease of use in mind. The panel’s main components include an LED display, function keys, and status indicators. The LED display shows real-time operating parameters such as output frequency, current, and voltage, and indicates operational status (e.g., RUN/STOP) and fault codes (e.g., Er.XX) through symbols. The function keys are clearly arranged, including:

  • MENU/ESC Key: Used to enter the parameter settings menu or exit the current operation interface.
  • ENTER Key: Confirms parameter modifications or enters submenus.
  • RUN/STOP Key: Controls the inverter’s start and stop; pressing and holding it initiates emergency stop.
  • MK Key: A multifunctional key whose function is defined by parameter P50.03 (e.g., inching control, free stop).
  • Increment/Decrement Keys (>, <): Adjust parameter values or switch display pages.
  • Shift Key (>>): Selects operation bits during parameter modification or cycles through display interfaces.

By using these keys in combination, users can perform operations such as parameter browsing, modification, and device control. For example, pressing and holding the MENU key for 3 seconds enters the password verification interface, where entering the correct password grants access to protected parameters.

2. Parameter Settings and Security Protection

1. Restoring Factory Default Parameters
To restore the device to its initial state, you can select the restoration range through parameter P50.20:

  • P50.20=0: Restores basic menu parameters (P00-P19 groups).
  • P50.20=1: Restores advanced menu parameters (P20-P49 groups).
  • P50.20=2: Restores user-defined menu parameters (P50-P99 groups).

Operation steps: Enter the menu → select P50.20 → press ENTER to confirm → use the increment/decrement keys to choose the restoration range → press ENTER again to execute.

2. Password Setting and Removal
To prevent accidental operations, a user password can be set via parameter P50.00:

  • Setting the password: Enter P50.00 → input a 4-digit password → press ENTER to confirm → the password takes effect after 1 minute of inactivity.
  • Password verification: The system prompts for password entry when modifying protected parameters.
  • Password removal: Power cycle the device or enter the correct password and press ENTER to lift protection.

3. Parameter Access Restrictions
Three levels of protection can be set via parameter P50.02:

  • P50.02=0: No protection; all parameters can be modified.
  • P50.02=1: Partial parameters locked (e.g., P00 group basic parameters are accessible, P20 group advanced parameters are locked).
  • P50.02=2: All parameters locked; modifications require a password.

Additionally, the thousand’s place of parameter P50.03 can lock operation panel keys (e.g., disabling RUN/STOP operations), further enhancing security.

MV10G Side

3. External Control Function Implementation

1. External Terminal Forward/Reverse Control
Configure terminal functions via parameter P10 group:

  • Forward control: Set P10.01=1 (DI1 terminal as forward command).
  • Reverse control: Set P10.02=2 (DI2 terminal as reverse command).
  • Combined logic: Set multi-terminal combined logic via P10.03-P10.06 (e.g., DI1+DI3 for forward inching).

Wiring example: Connect the forward button to the DI1 terminal and COM terminal, and the reverse button to the DI2 terminal and COM terminal.

2. External Potentiometer Frequency Adjustment
Implementation steps:

  • Parameter settings: Enter the P12 group → set P12.01=1 (AI1 as frequency reference source) → P12.03=0 (0-10V corresponds to 0-50Hz).
  • Hardware wiring: Connect an external potentiometer (10kΩ) to AI1 (terminal 10) and GND (terminal 11).
  • Debugging tips: Rotate the potentiometer and observe if the frequency value displayed on the LED changes linearly. Adjust P12.04 (filter time) if fluctuations occur.

4. Fault Codes and Handling Procedures

The manual lists over 20 fault codes and solutions. Below is a guide to common fault handling:

Fault CodeFault DescriptionPossible CausesHandling Steps
Er.01Acceleration overcurrentSudden load change, short acceleration timeExtend acceleration time (P01.01), check load
Er.02Deceleration overcurrentBraking resistor failure, short deceleration timeCheck braking unit, extend deceleration time (P01.02)
Er.07Input phase lossPoor power line contactCheck input voltage and wiring
Er.11Motor overloadExcessive load, motor faultReduce load, check motor insulation
Er.15Communication faultLoose communication cable, protocol mismatchCheck wiring, verify communication parameters (P30 group)

Fault troubleshooting process:

  1. Record the fault code (displayed on the LED or query historical records via P34 group).
  2. Identify the cause using the fault list in the manual.
  3. Follow the recommended steps (e.g., check power supply, adjust parameters, replace components).
  4. Clear the fault record (P34.01=1) and restart the device.

5. Maintenance and Extended Functions

1. Communication Function
The device supports the Modbus RTU protocol (P30 group) and can be monitored via PLC or a host computer through an RS485 interface. Parameter settings example:

  • P30.01=1 (Enable Modbus)
  • P30.02=9600 (Baud rate)
  • P30.03=2 (8 data bits, 1 stop bit, no parity)

2. Maintenance Recommendations

  • Clean the cooling fan and filter regularly (every 6 months).
  • Check the electrolyte capacitor capacity (every 2 years; replace if below 80%).
  • Back up parameters (export to external storage via P50.21).

6. Conclusion

This article systematically summarizes the operation logic and advanced functions of the MIKOM MV series inverter based on the user manual. By mastering panel operations, parameter management, external control, and fault handling skills, users can significantly enhance equipment efficiency and safety. It is recommended to deepen understanding through practical operations and the manual’s diagrams, and to regularly attend manufacturer training to stay updated on technical advancements.

Posted on

User Manual Guide for CHRH-G Series Inverter by RiHong


I. Panel Function Introduction and Parameter Management Operations

1. Panel Function Introduction

The operation panel of the RiHong CHRH-G series inverter includes the following core buttons and indicators:

  • RUN Key: Starts the inverter operation, defaulting to forward rotation.
  • STOP/RESET Key: Stops the machine or resets faults.
  • PRG Key: Enters parameter setting mode.
  • ENTER Key: Saves parameter modifications.
  • ▲/▼ Keys: Adjusts parameter values or switches monitoring items.
  • ◄/► Keys: Modifies parameter digits or switches function groups.
  • Analog Potentiometer: Manually adjusts frequency (requires setting the frequency reference channel to potentiometer mode).

LED Indicator Descriptions:

  • Hz: Displays frequency unit.
  • A/V: Displays current or voltage unit (green for current, red for voltage).
  • ALM: Fault alarm indicator (red constantly lit or flashing).
  • F/R: Rotation direction indicator (red for forward, green for reverse).

CHRH front

2. Parameter Factory Default Settings

Steps:

  1. Enter function code F0.13 (Parameter Initialization).
  2. Set to 1 (Restore factory settings, retaining motor parameters) or 2 (Restore all parameters).
  3. Press the ENTER key to confirm; the system will automatically exit after completion.

3. Parameter Encryption and Decryption

Encryption Setup:

  1. Enter function code FC.05 (User Password) and set a password (range: 10~65535).
  2. Set function code F0.14 (Parameter Write Protection) to 2 (Prohibit modification of all parameters).

Decryption Operation:

  1. After entering the correct password, set F0.14 to 0 or 1 to lift the protection.

4. Parameter Access Restrictions

Set access permissions via F0.14:

  • 0: Allows modification of all parameters (in stop state).
  • 1: Only allows modification of frequency-related parameters (F0.02~F0.08).
  • 2: Completely prohibits modification of parameters.

II. External Terminal Forward/Reverse Control and Potentiometer Speed Regulation

1. External Terminal Forward/Reverse Control

Wiring Terminals:

  • X1/X2/X3: Multi-function input terminals (default functions need redefinition).
  • COM: Common terminal.

Parameter Settings:

  1. Set F0.01 (Operation Command Channel) to 1 (Terminal Control).
  2. Set F5.00 (X1 Function) to 12 (Forward Control) and F5.01 (X2 Function) to 13 (Reverse Control).
  3. The corresponding direction starts when the terminal is closed and stops when disconnected.

2. External Potentiometer Speed Regulation

Wiring Terminals:

  • AI1: Analog Input 1 (0~10V/0~20mA).
  • GND: Signal ground.

Parameter Settings:

  1. Set F0.02 (Frequency Reference Channel) to 4 (AI1 Analog Reference).
  2. Calibrate the AI1 input range via F6.00~F6.03 (default: 0~10V corresponds to 0~maximum frequency).
  3. Adjust the potentiometer to regulate the output frequency in real-time.

III. Fault Code Analysis and Solutions

Fault CodeMeaningPossible CausesSolutions
E001Acceleration OvercurrentAcceleration time too short, sudden load changeExtend acceleration time, check load
E005Deceleration OvervoltageDeceleration time too short, inertial loadExtend deceleration time, install braking resistor
E009Power Module FaultOutput short circuit, poor heat dissipationCheck motor wiring, clean air ducts
E010Heatsink OverheatingHigh ambient temperature, fan failureImprove ventilation, replace fan
E013External Device FaultExternal fault signal inputCheck external device wiring
E021Operation Time Limit ReachedCumulative operation timeoutContact dealer to lift restriction
E022Output Phase LossLoose or broken motor wiringCheck U/V/W terminal connections

General Fault Handling Steps:

  1. Press the STOP/RESET key to reset.
  2. Check monitoring parameters (d-21~d-28) to record the operating state during the fault.
  3. Adjust relevant parameters or check hardware connections according to the manual.

CHRH Side

IV. Maintenance and Precautions

Daily Maintenance:

  • Regularly clean the heat dissipation air ducts to ensure proper fan operation.
  • Check terminal screws for looseness to avoid poor contact.

Insulation Testing:

  • Disconnect all wiring, short-circuit the main circuit terminals, and test with a 500V megohmmeter.
  • Do not perform insulation tests on control terminals.

Long-Term Storage:

  • Store in a dry environment and power on every six months to activate electrolytic capacitors.

Conclusion

The RiHong CHRH-G series inverter meets diverse industrial scenario demands through flexible terminal control, parameterized configuration, and multiple protection functions. Users must master panel operations, parameter logic, and fault troubleshooting methods to ensure efficient and stable operation of the equipment. For complex issues, it is recommended to contact the manufacturer’s technical support for professional guidance.

Posted on

Rhymedbus Inverter RM6 Series User Manual Usage Guide

I. Introduction to the Operation Panel Functions and Parameter Settings

1.1 Overview of Operation Panel Functions

The Rhymedbus Inverter RM6 series comes equipped with an intuitive and user-friendly operation panel, which includes the following key functions:

  • Power Indicator: Displays the power status of the inverter.
  • Frequency Unit Indicator: Shows the current set or actual frequency unit (Hz).
  • Voltage Unit Indicator: Displays the current voltage unit (V).
  • Current Unit Indicator: Displays the current current unit (A).
  • Program Key (PROG): Used to switch between parameter setting mode and monitoring mode.
  • Function/Data Key (FUNC DATA): Enters parameter setting mode, returns to the set item, and switches monitoring screens.
  • Set Knob: Adjusts frequency commands or other parameter settings.
  • Run Key (RUN): Starts the inverter.
  • Stop/Reset Key (STOP RESET): Stops the inverter or clears abnormal states.
  • Increase/Decrease Keys: Used to change set items and parameter values.
RM6 physical picture

1.2 Restoring Parameters to Factory Defaults

To restore the inverter parameters to their factory default settings, follow these steps:

  1. Enter Parameter Setting Mode: Press the “PROG” key to enter parameter setting mode.
  2. Select Factory Default Setting: Use the Increase/Decrease keys to select the F_000 (Inverter Information) parameter item.
  3. Choose Factory Default Restoration: Continue using the Increase/Decrease keys to select the corresponding factory default restoration option (e.g., dEF60 for 60Hz general-purpose factory defaults).
  4. Confirm Restoration: Press the “FUNC DATA” key to confirm restoring the factory defaults.

1.3 Password Setting and Removal

The RM6 series inverter supports parameter locking to prevent unauthorized parameter modifications.

  • Setting a Password: Enter the F_213 (Parameter Lock Password Input) parameter item, use the Set Knob to enter the password value (0-9999), and press the “FUNC DATA” key to confirm.
  • Removing a Password: Enter the F_214 (Parameter Lock Decoding Input) parameter item, enter the password value, and press the “FUNC DATA” key to confirm, thereby removing the password lock.

1.4 Setting Parameter Access Display

Users can set the access level and display content of parameters according to their needs:

  • Parameter Access Level: Set through the F_212 (Parameter Lock Parameter Display Selection) parameter item, which can choose whether to display locked parameters.
  • Monitoring Screen Selection: In monitoring mode, use the “FUNC DATA” key to switch between different monitoring screens, such as output frequency, voltage, current, etc.

II. External Terminal Control and Speed Regulation Function Implementation

2.1 External Terminal Forward and Reverse Control

The RM6 series inverter supports forward and reverse control of the motor through external terminals, requiring the following wiring and settings:

  • Wiring:
    • Connect the external control signals (such as buttons or relay contacts) to the inverter’s forward terminal (FWD) and reverse terminal (REV) respectively.
    • Ensure the common terminal (COM) is connected correctly.
  • Parameter Settings:
    • Enter the F_001 (Start Control Selection) parameter item and set it to 0 or 1 (depending on the specific control mode).
    • Ensure the F_003 (Operator STOP Key Priority) parameter item is set to allow external terminal control (e.g., set to 0).

2.2 External Potentiometer Speed Regulation Function

Speed regulation of the inverter can be achieved through an external potentiometer, requiring the following wiring and settings:

  • Wiring:
    • Connect the output terminal of the external potentiometer to the inverter’s Vin (analog input voltage) terminal.
    • Ensure the potentiometer’s common terminal and the other output terminal are connected to the inverter’s GND (ground) and Vin+ terminals respectively.
  • Parameter Settings:
    • Enter the F_002 (Main Frequency Command Selection) parameter item and set it to 1 (controlled by analog signal).
    • Enter the F_124 (Analog Input Selection (Vin)) parameter item and ensure it is set to 1 (enable Vin input).

III. Fault Codes and Troubleshooting Methods

The RM6 series inverter features comprehensive fault diagnosis functionality. When a fault occurs, the corresponding fault code will be displayed on the operation panel. Here are some common fault codes, their meanings, and troubleshooting methods:

  • EEr: EEPROM error protection. Possible causes include EEPROM data write errors or EEPROM component failures. The troubleshooting method is to restore all parameter settings to factory defaults and reboot. If the error persists, send it for repair.
  • AdEr: A/D converter error protection. Possible cause is A/D converter failure. The troubleshooting method is to contact customer service for repair.
  • GF: Ground fault protection. Possible causes include grounding of the inverter output or poor insulation of the motor and motor wires. The troubleshooting method is to check the insulation of the motor and motor wires, and replace them if necessary.
  • OE: Overvoltage protection. Possible cause is excessively high DC bus voltage inside the inverter. Troubleshooting methods include increasing the deceleration time setting, installing a dynamic brake unit, checking if the power supply voltage is within the rated input range of the inverter, etc.
  • OL: Motor overload protection. Possible cause is long-term overload operation of the motor. The troubleshooting method is to check the usage of the mechanical equipment and ensure the load is within the motor’s rated range.

When a fault occurs in the inverter, first check the fault code displayed on the operation panel and follow the troubleshooting guide in the user manual for corresponding actions. If the issue cannot be resolved by the user, professional maintenance personnel or customer support should be contacted promptly.

RM6 Control Circuit Standard Wiring Diagram

IV. Conclusion

The Rhymedbus Inverter RM6 series user manual provides detailed operation guidelines and fault handling information, helping users better understand and utilize the inverter. By familiarizing themselves with the operation panel functions, mastering parameter setting methods, understanding the implementation of external terminal control and speed regulation functions, and being familiar with fault codes and troubleshooting methods, users can operate and maintain the inverter equipment more efficiently. In practical applications, users should flexibly configure inverter parameters and functional options according to specific needs and site conditions to achieve optimal control effects and operational efficiency.

Posted on

VEIHI Inverter AC310 Series User Manual Guide

I. Detailed Explanation of Operation Panel Functions

1. Overview of Operation Panel Functions
The VEIHI Inverter AC310 series operation panel integrates multiple functions, supporting parameter settings, operational control, and fault diagnosis. Key functions include:

  • Display Screen: Displays operational status, parameter values, and fault codes.
  • Run Key: Starts/stops the inverter.
  • Up/Down Keys: Adjust parameter values or select menu items.
  • Confirm/Shift Key: Confirms settings or switches operation positions.
  • Menu Key: Enters the function menu interface.
  • Stop/Reset Key: Stops operation or resets faults.

2. Factory Parameter Settings

  • Enter Parameter Settings: Press the “Menu Key” → Select “Parameter Settings”.
  • Select Parameter Group: Use the up/down keys to choose a parameter group (e.g., F00, F01).
  • Modify Parameter Values: After selecting a parameter, adjust its value with the up/down keys and press “Confirm/Shift Key” to save.
  • Restore Factory Defaults: Press the “Menu Key” → Select “Restore Factory Defaults” → Confirm.

3. Password Setting and Removal

  • Set Password:
    • Press the “Menu Key” → Select “Password Settings”.
    • Enter the default password (0000) → Press “Confirm/Shift Key” to save.
  • Remove Password:
    • Press the “Menu Key” → Select “Password Settings”.
    • Enter the current password → Press “Confirm/Shift Key” → Reset the password to 0000.

4. Parameter Access Restrictions

  • Enter Restriction Settings: Press the “Menu Key” → Select “Parameter Access Restrictions”.
  • Set Permissions: Choose a parameter group and set access permissions (e.g., read-only, writable).
  • Save Settings: Press “Confirm/Shift Key” to save.

Front image of AC310

II. External Terminal Control and Speed Regulation Methods

1. External Terminal Forward/Reverse Control

  • Wiring: Connect external signals to digital input terminals (e.g., X1, X2) and set terminal functions (Parameter F05.00).
  • Parameter Settings:
    • F01.01=1 (External Terminal Control).
    • Set the corresponding terminal in F05.00 for forward/reverse control.

2. External Potentiometer Frequency Control

  • Wiring: Connect the potentiometer output to analog input terminals (e.g., AI1, AI2) and set terminal functions (Parameter F05.04).
  • Parameter Settings:
    • F01.02=2 (Frequency Reference Source Channel A = Terminal AI1 Reference).
    • Set the potentiometer output range in F05.50 and F05.53 (e.g., 0V~10V).

III. Fault Codes and Troubleshooting Methods

1. Common Fault Codes

  • E.SC1 (01): System fault during acceleration (short circuit, interference, overload).
  • E.oC1 (05): Overcurrent during acceleration (overload, motor damage, too short acceleration time).
  • E.Lu (13): Undervoltage during operation (unstable power supply, loose cables).
  • E.oH1 (30): Rectifier module overtemperature (poor ventilation, high ambient temperature).

2. Fault Troubleshooting Methods

  • System Fault (E.SC1):
    • Check the main circuit and eliminate short circuits.
    • Shorten the output cable or add an output reactor.
    • Reduce the load or replace with a higher-capacity inverter.
  • Overcurrent Fault (E.oC1):
    • Reduce the load or replace with a higher-capacity inverter.
    • Increase the acceleration time (Parameter F01.22).
  • Undervoltage Fault (E.Lu):
    • Check the stability of the power supply voltage.
    • Ensure the cable connections are secure.
  • Overtemperature Fault (E.oH1):
    • Ensure proper ventilation.
    • Lower the ambient temperature or add cooling equipment.

Side image of AC310

IV. Conclusion and Recommendations

The VEIHI Inverter AC310 series is a powerful and user-friendly variable frequency drive. By properly setting parameters, correctly wiring, and promptly addressing faults, users can fully leverage its performance and ensure stable equipment operation. This guide provides detailed information on operation panel functions, parameter settings, external control and speed regulation methods, and fault troubleshooting steps, offering valuable references for users. If issues arise during use, please contact our technical support team for professional assistance.

Posted on

User Manual Guide for Wisen Inverter FE550 Series

I. Introduction to the Operation Panel Functions

1.1 Overview of the Operation Panel

The operation panel of the Wisen Inverter FE550 integrates multiple functions, allowing users to set parameters, control operations, and diagnose faults through the buttons and display screen on the panel. The operation panel mainly includes the following parts:

  • Display Screen: Used to display operating status, parameter values, and fault codes.
  • Function Buttons: Including start, stop, frequency adjustment, and setting buttons.
  • Navigation Buttons: Used to navigate through menus and select parameters.
Front image of FE550

1.2 How to Restore Factory Settings

In some cases, users may need to restore the inverter to its factory settings. Here are the steps to restore factory settings:

  1. Press the PROG button to enter the parameter setting mode.
  2. Use the  or  buttons to select parameter F0.50 (Parameter Restoration).
  3. Set F0.50 to 30 (Restore all factory parameters).
  4. Press the ENTER button to confirm, and the inverter will automatically restore to factory settings.

1.3 How to Encrypt and Unlock the Password

To prevent unauthorized parameter modifications, the FE550 series inverter supports parameter encryption. Here are the steps to encrypt and unlock the password:

Setting the Password:

  1. Enter the parameter setting mode and select parameter F0.36 (User Password).
  2. Enter a four-digit password (e.g., 1234) and press the ENTER button to confirm.

Unlocking the Password:

  1. When modifying parameters, the system will prompt for a password.
  2. Enter the correct password and press the ENTER button to unlock the password protection.

1.4 How to Set Parameter Access Restrictions

To further protect the inverter’s parameter settings, users can set parameter access restrictions:

  1. Enter the parameter setting mode and select parameter F0.36 (User Password).
  2. Set F0.36 to a non-zero value (e.g., 65555), indicating that the parameters are encrypted.
  3. In the parameter modification mode, only by entering the correct password can parameters be accessed and modified.
FE550 side image

II. External Terminal Control and Speed Regulation Settings

2.1 External Terminal Forward/Reverse Control

The FE550 series inverter supports forward/reverse control via external terminals. Here are the specific wiring and parameter setting steps:

Wiring Instructions:

  • Forward Signal: Connect the external forward signal to the inverter’s X1 terminal.
  • Reverse Signal: Connect the external reverse signal to the inverter’s X2 terminal.
  • Common Terminal (GND): Connect the common terminal of the forward and reverse signals to the inverter’s GND terminal.

Parameter Settings:

  1. Enter the parameter setting mode, select parameter F4.01 (X1 Terminal Function Selection), and set it to 1 (Forward Operation).
  2. Select parameter F4.02 (X2 Terminal Function Selection) and set it to 2 (Reverse Operation).
  3. Save the settings, and the inverter will implement forward/reverse control based on the external terminal signals.

2.2 External Potentiometer Speed Regulation

The FE550 series inverter supports speed regulation via an external potentiometer. Here are the specific wiring and parameter setting steps:

Wiring Instructions:

  • Potentiometer Signal: Connect the output signal of the external potentiometer to the inverter’s A15 terminal.
  • Potentiometer Power Supply: Connect the positive pole of the external potentiometer’s power supply to the inverter’s +10V terminal and the negative pole to the GND terminal.

Parameter Settings:

  1. Enter the parameter setting mode, select parameter F0.02 (Main Frequency Command Selection), and set it to 5 (A15 Analog Input).
  2. Select parameter F5.14 (Maximum Input of Attached Potentiometer) and set it to the actual output voltage range of the potentiometer (e.g., 10V).
  3. Select parameter F5.15 (Maximum Input Corresponding Setting of Attached Potentiometer) and set it to 100.0% (indicating that the maximum input of the potentiometer corresponds to the inverter’s maximum frequency).
  4. Select parameter F5.16 (Filtering Time of Attached Potentiometer) and set it to 0.10s (adjust according to actual needs).

With the above settings, the inverter will adjust the output frequency based on the input signal from the external potentiometer, achieving speed regulation.

FE550 standard wiring diagram

III. Fault Codes and Solutions

During operation, the FE550 series inverter may encounter various faults, which will be displayed as fault codes on the screen. Here are common fault codes and their solutions:

3.1 Common Fault Codes

Fault CodeFault DescriptionPossible CausesSolutions
1002Acceleration OvercurrentToo short acceleration time, excessive loadIncrease acceleration time, reduce load
1003Deceleration OvercurrentToo short deceleration time, excessive loadIncrease deceleration time, reduce load
1004Operating OvercurrentExcessive load, motor faultCheck motor and load, reduce load
1008Power UndervoltageInput voltage too lowCheck power supply voltage, ensure it is within the allowable range
1010Inverter OverheatingHigh ambient temperature, poor heat dissipationImprove heat dissipation conditions, reduce ambient temperature
1016Communication FaultCommunication line or parameter errorCheck communication line and parameter settings

3.2 Fault Handling Steps

  1. Identify the Fault Code: View the fault code on the display screen to determine the fault type.
  2. Analyze the Cause: Analyze possible causes based on the fault code and description.
  3. Take Measures: Operate according to the solution to eliminate the fault.
  4. Verify Recovery: After troubleshooting, restart the inverter to confirm its normal operation.

IV. Conclusion

The Wisen Inverter FE550 series is a powerful and easy-to-operate inverter control device. Through proper wiring and parameter settings, users can achieve external terminal control, speed regulation functions, and efficient fault diagnosis. During use, it is recommended that users read the user manual carefully, follow the correct operation steps, and ensure the stable operation and long-term reliability of the device. If you encounter problems that cannot be solved, you can contact our technical support team for professional help and guidance.

Posted on

User Manual Guide for ANYHZ Inverter FST-650 Series

I. Introduction

The ANYHZ Inverter FST-650 Series stands out as a leader among general-purpose frequency converters, thanks to its high performance and extensive parameter features. This document aims to provide users with a comprehensive operational guide, covering aspects such as the operation panel functions, parameter settings, external control, and fault handling, to assist users in efficiently utilizing and maintaining this inverter.

II. Detailed Explanation of Operation Panel Functions

(I) Basic Functions of the Operation Panel

The operation panel of the FST-650 Series inverter is intuitively designed and comprehensive in functionality, including:

  • Program Key: Used to enter or exit menus.
  • Confirm Key: Navigates through menus step-by-step, sets, and confirms parameters.
  • Up/Down Keys: Adjust data and function codes.
  • Right Shift Key: Shifts right to select parameters when the inverter is stopped or in the operation interface; selects the digit to modify when changing parameters.
  • Run Key: Starts the inverter in keyboard operation mode.
  • Stop/Reset Key: Stops the operation in the running state; resets the inverter during a fault alarm.

(II) Restoring Factory Parameter Settings

  1. Enter the parameter setting interface and locate F0.00.
  2. Set F0.00 to the default value (usually 0).
  3. Confirm the setting, and the inverter will restore to factory default settings.

(III) Password Setting and Removal

  1. Enter the parameter setting interface and find FP.00.
  2. Enter a new password and confirm.
  3. To remove the password, set FP.00 to the default value (usually 0).

(IV) Parameter Access Restriction

  1. Enter the parameter setting interface and locate FP.01.
  2. Set the parameter access restriction level and confirm.
  3. Users with different levels will have different access and modification permissions for parameters.
FST-650 Operation Panel Function Diagram

III. External Terminal Control and Potentiometer Speed Regulation

(I) External Terminal Forward/Reverse Control

  • Terminal Connections: X1 (Forward Run FWD), X2 (Reverse Run REV).
  • Parameter Settings:
    1. Enter the parameter setting interface and find F4.00 and F4.01.
    2. Set F4.00 to 1 (Forward) and F4.01 to 2 (Reverse).
    3. Confirm the settings, and the inverter will control forward/reverse based on the external terminal status.

(II) External Potentiometer Speed Regulation

  • Terminal Connections: AI1 (Analog Input Terminal, connected to the potentiometer).
  • Parameter Settings:
    1. Enter the parameter setting interface and find F0.03.
    2. Set F0.03 to 2 (Analog VCI Setting).
    3. Confirm the setting, and the inverter will regulate speed based on the potentiometer input signal.
FST-650 standard wiring diagram

IV. Fault Codes and Handling Methods

(I) Common Fault Codes

  • Err01: Overcurrent Fault
  • Err02: Overvoltage Fault
  • Err03: Undervoltage Fault
  • Err04: Overheat Fault
  • Err05: Phase Sequence Fault
  • Err06: Ground Fault

(II) Fault Handling Methods

  • Err01: Check the load and cable connections to ensure the load is within the allowable range.
  • Err02: Check the input voltage and cable connections to ensure the voltage is within the allowable range.
  • Err03: Check the input voltage and cable connections to ensure the voltage does not fall below the set value.
  • Err04: Check the inverter’s cooling conditions to ensure proper ventilation and that the heat sink is functioning correctly.
  • Err05: Check the input power phase sequence and cable connections to ensure the phase sequence is correct.
  • Err06: Check the ground connection and cable connections to ensure the ground is properly connected.

V. Conclusion

The ANYHZ Inverter FST-650 Series offers users a highly efficient and stable frequency conversion solution with its powerful features and flexible control methods. By mastering the operation panel functions, parameter settings, external control, and fault handling methods, users can fully leverage the performance advantages of this inverter and ensure its long-term stable operation. It is hoped that this document will provide strong support for users in using and maintaining the FST-650 Series inverter.

Posted on

Detailed Operation Guide for LS Servo APD-VS Series User Manual

I. Introduction to Control Panel Functions

The control panel of the LS Servo APD-VS series is designed to be intuitive, comprising the following key components:

Operation Keys:

  • Left/Right Keys: Used to switch between menu items for easy navigation.
  • Up Key: Selects submenus or adjusts parameter values.
  • Enter Key: Confirms selections or enters edit mode, executing commands such as tests or alarm resets.
    Display Screen: Displays real-time system operating status, including key parameters such as current speed, position, torque, and load, facilitating user monitoring and diagnostics.
    Menu Structure:
  • Status Menu (Pd-001 to Pd-020): Displays real-time data such as operating status, speed, torque, and load.
  • Alarm Menu (PA-101 to PA-120): Records historical alarms for fault tracing.
  • System Menu (PE-201 to PE-220): Configures system parameters, such as motor ID, encoder type, and communication speed.
  • Control Menu (PE-301 to PE-320): Adjusts control parameters, such as inertia ratio, position/speed gain, and resonance suppression.
  • Analog Menu (PE-401 to PE-420): Sets analog inputs/outputs, such as speed and torque commands.
  • Input/Output Menu (PE-501 to PE-520): Manages I/O settings, including position error limits and brake control.
  • Speed Operation Menu (PE-601 to PE-620): Configures speed-related operations and test runs.
  • Pulse Operation Menu (PE-701 to PE-720): Handles position control settings, including pulse logic and electronic gear ratio.
  • Command Menu (PC-801 to PC-820): Executes operations such as alarm reset, test run, and gain adjustment.
    Connectors:
  • CN1 (Control Signal): Used to connect external control signals, supporting communication with a host computer or PLC.
  • CN2 (Encoder): Connects to the encoder, providing motor position and speed feedback.
  • CN3 (Communication): Supports RS232 or other communication protocols for interaction with a PC or host controller.
APD-VS110L1A50

II. Setting Passwords and Access Restrictions

The LS Servo APD-VS series user manual does not explicitly mention a traditional password system but provides a “Menu Data Lock” function to restrict unauthorized parameter modifications:

Menu Data Lock Function:

  • Enable or disable the lock function through menu [PC-810].
  • In the locked state, attempting to modify menu data will display an “Err3” error, indicating that the menu is locked.
  • Unlocking Operation: Return to [PC-810] and press the Enter key to switch to the “unLock” state, allowing parameter modifications.

III. Jog Operation

Jog operation (also known as manual test operation) is an important function for testing motor response or debugging. Below are the detailed steps:

Starting Jog:

  • Enter command menu [PC-803] and press the Enter key to initiate the manual test.
  • The system will cancel existing alarms, display the test operation speed, and start the motor.
    Controlling Speed and Direction:
  • Use the Up key to switch between different test speeds set in [PE-602] to [PE-608].
  • Press the Right key for forward rotation (counterclockwise) and the Left key for reverse rotation (clockwise).
    Ending Operation:
  • Press the Enter key to stop the test and return to the menu.

IV. Position Mode and External Pulse Forward/Reverse Control

Position mode is suitable for applications requiring precise positioning, such as CNC machine tools or robotic arms. Below are the steps to configure external pulse forward/reverse control:

Setting Position Mode:

  • Set the operation mode to “2” (position mode) in menu [PE-601].
    Pulse Input:
  • External pulse signals are input through pins 9 (PF+), 10 (PF-), 11 (PR+), and 12 (PR-) of CN1.
  • Two input methods are supported: line-driven 5V or open-drain 24V, to be selected based on the host controller.
    Electronic Gear Ratio:
  • Use [PE-702] to [PE-709] to set the electronic gear ratio, defining the ratio between input pulses and encoder pulses.
    Pulse Logic:
  • Set the pulse logic to N logic or P logic in [PE-701], determining the pulse direction interpretation for forward/reverse rotation.
Standard Wiring Diagram for APD-VS Position and Speed Modes

V. Speed Mode and Forward/Reverse Control

Speed mode is used to control motor speed and is suitable for applications requiring stable speed. Below are the configuration steps:

Setting Speed Mode:

  • Set the operation mode to “1” (speed mode) in menu [PE-601].
    Speed Command:
  • Analog Command: Input through SPDCOM (pin 27), with a range of -10V to +10V, where positive and negative values correspond to forward and reverse directions, respectively.
  • Digital Command: Select digital speed commands 1 to 7 through combinations of SPD1 (pin 23), SPD2 (pin 22), and SPD3 (pin 21).
    Direction Control:
  • Use DIR (pin 46) and STOP (pin 48) inputs to control direction, configured through [PE-514].

VI. Fault Code Analysis and Solutions

The LS Servo APD-VS series provides a detailed list of fault codes to help users quickly diagnose and resolve issues. Below are common fault codes and their solutions:

Fault CodeMeaningSolution
Nor-offNormal (servo off)No action required
Nor-onNormal (servo on)No action required
L1.01RS232 communication error/control operation errorReplace the drive
AL-01Emergency stopCheck external DC24V power supply
AL-02Power failureCheck main power lines
AL-03Line faultCheck settings, CN2, U/V/W lines
AL-04Motor output faultCheck U/V/W lines and IPM module
AL-05Encoder pulse errorCheck [PE-204] settings and CN2 lines
AL-06Following errorCheck [PE-502] settings, lines, limit switches, gain
AL-08OvercurrentCheck output lines, motor/encoder settings, gain; replace the drive if necessary
AL-09OverloadCheck load, brake operation, lines, motor/encoder settings
AL-10OvervoltageCheck input voltage, brake resistor, regenerative operation
AL-11OverspeedCheck encoder settings, lines, gain
AL-14~17Absolute encoder errorCheck initial reset [PC-811], battery, encoder lines
AL-20~22Flash/initialization errorReplace the drive
AL-23Hardware errorCheck [PE-203] settings
Err1Parameter modification during servo onAdjust parameters after turning off the servo
Err2Data out of rangeInput values within the valid range
Err3Menu lockedUnlock through [PC-810]

General Solutions:

  • Use [PC-801] or ALMRST (pin 17) to reset alarms.
  • View alarm history [PA-101] to [PA-120] and use [PC-802] to clear history records to track new faults.
  • Ensure all lines are connected correctly and parameters are set reasonably. If the problem persists, contact technical support.

Through this operation guide, users can better understand and use the LS Servo APD-VS series drive to ensure efficient and stable system operation.

Posted on

KINGDA Electric Inverter A800 Series User Guide and Analysis of EC.34 Fault Code Meaning

The KINGDA Electric Inverter A800 series is a powerful and flexible industrial automation device widely used in motor control and speed regulation. This article, based on its user manual and the provided fault code image (showing “EC.34 0.00”), details the operation panel functions, parameter initialization methods, password setting and removal, parameter access restriction settings, and the implementation of external terminal forward/reverse control and external potentiometer speed regulation. Additionally, for the situation where the EC.34 fault code is not explained in the manual, combined with feedback from the manufacturer’s technical staff, it analyzes its potential meaning and possible commercial operation background, and proposes solutions. The article is clearly structured and comprehensive, aiming to provide practical guidance for users.


I. Introduction to Operation Panel Functions and Parameter Management

Operation Panel Functions

The operation panel of the KINGDA Electric A800 series inverter is the core component for user interaction with the device. As seen from the fault image, the panel is equipped with a red LED display, currently showing “EC.34 0.00”, indicating the device is in a fault state. The functions of the buttons and knobs on the panel are as follows:

  • ESC (Exit): Exit the current menu or cancel the operation.
  • PROG (Programming): Enter parameter programming mode.
  • ENTER (Confirm): Confirm selection or enter the next level menu.
  • Direction Keys (Up, Down, Left, Right): Navigate menus or adjust parameter values.
  • STOP/RESET (Stop/Reset): Stop operation or reset faults.
  • RUN (Run): Start the inverter.
  • Knob: The central black knob is used to manually adjust parameters or scroll through menus.

These controls are intuitively designed for easy user operation. The user manual on page 24 (“Operation Panel and Status Parameters”) provides a detailed description.

Parameter Initialization Method

Parameter initialization is used to restore the inverter to factory settings, typically performed during first use or troubleshooting. The specific steps are as follows:

  1. Press the PROG key to enter the main menu.
  2. Use the direction keys to navigate to the “Parameter Initialization” option (see “Function Parameter Table” on page 28 of the manual).
  3. Press ENTER to confirm; if a password is set, enter the password to unlock.
  4. Select “Yes” and press ENTER to perform initialization; the device will automatically restart upon completion.

After initialization, all parameters are restored to default values, and the user needs to reconfigure them according to the application.

Password Setting and Removal

The password function protects parameters from unauthorized modification:

  • Setting a Password:
  1. Enter the “Programmable Management Parameter Array” (page 90 of the manual).
  2. Find the password setting item (usually parameter P10.XX).
  3. Enter a 4-digit password and press ENTER to save.
  • Removing the Password:
  • If the password is remembered, it can be cleared by entering the correct password in the same menu.
  • If the password is forgotten, contact the manufacturer’s technical support and provide the serial number (e.g., “A800-250007G-AB00-250040G” on page 7 of the manual) to unlock.
  • Alternatively, clear the password through parameter initialization, but this will reset all settings.
Parameter Access Restriction Setting

Parameter access restrictions further enhance security:

  1. Enter the “Programmable Management Parameter Array” (page 90).
  2. Find the “Parameter Lock” or “Access Level” option (e.g., P10.01).
  3. Set to “Lock Mode”, with options for “Read-Only” or “Fully Locked”.
  4. After saving the settings, unlocked users cannot modify parameters.

These features ensure the security and stability of the device parameters.


II. External Terminal Forward/Reverse Control and External Potentiometer Speed Regulation

External Terminal Forward/Reverse Control

Controlling the inverter’s forward and reverse operation through external switches requires wiring and parameter settings:

  • Wiring:
  • Two-Wire Control (page 101 of the manual, “Two-Wire Switch Control for Inverter Forward and Reverse”):
    • Terminal FWD (Forward) connected to one end of the switch.
    • Terminal REV (Reverse) connected to the other switch.
    • COM terminal is the common ground.
  • Three-Wire Control (page 101, “Three-Wire Self-Resetting Switch Control”):
    • SB1 (Start), SB2 (Stop), SB3 (Forward/Reverse Switch) connected to switches respectively.
    • COM terminal is the common ground.
  • Parameter Settings:
  • P02.01 (Start/Stop Control Source) set to “External Terminal Control”.
  • P02.02 (Direction Control Source) set to “Terminal FWD/REV” or “Three-Wire Control”.
  • P05.00 (Input Terminal Function Selection) assign functions to FWD, REV, or SB1/SB2/SB3.
External Potentiometer Speed Regulation

Adjusting the output frequency through an external potentiometer to achieve motor speed regulation:

  • Wiring (page 100 of the manual, “External Potentiometer Connection to Inverter”):
  • One end of the potentiometer connected to +10V (power), the other end to GND (ground).
  • The middle tap connected to VI (analog input).
  • Parameter Settings:
  • P00.06 (Main Frequency Reference Source) set to “VI Analog Input”.
  • P03.00 (Analog Input Range) set to 0-10V, corresponding to 0 to maximum frequency (P00.03).
  • Calibrate P03.01 (Minimum Input Voltage) and P03.02 (Maximum Input Voltage) to match the potentiometer.

After correct configuration, users can flexibly control the inverter through switches or the potentiometer.


III. Analysis of EC.34 Fault Code

Fault Phenomenon and Missing Manual Information

The inverter displays “EC.34 0.00” and cannot operate normally. Upon checking pages 92-121 of the user manual (“Fault Diagnosis and Solutions” to “Common EMC Interference Problem Rectification Suggestions”), no explanation for EC.34 is found. After consulting the manufacturer’s technical staff, the response was “need to contact the dealer to solve”, suggesting that EC.34 is not a standard fault code.

Speculation on Fault Meaning

Combining the feedback from technical staff and the fact that it is not mentioned in the manual, EC.34 may be a black-box operation code set by the dealer. The analysis is as follows:

  • Clock Function Association: The A800 series may have a built-in operation time limit mechanism (parameters may be hidden in the “Management Parameter Array” on pages 49-90), such as setting a 3-month operation cycle.
  • Artificial Shutdown: After the cycle ends, EC.34 is triggered, displaying a fault and shutting down, but the hardware is actually undamaged.
  • Commercial Purpose: This design may be set by the dealer to recover outstanding payments, promote services, or force users to pay additional fees, which is a malicious commercial practice.

This practice exists in certain market environments but lacks transparency and may harm user rights.

Solution Methods
  1. Contact the Dealer:
  • Provide the serial number and purchase certificate, and request to lift the restriction.
  1. Technical Unlocking:
  • Try parameter initialization (see Part One), which may reset the time limit but will clear all settings.
  1. Legal Rights Protection:
  • If confirmed as malicious setting, keep evidence (manual, pictures, communication records) and complain to consumer protection agencies.

IV. Summary and Suggestions

The KINGDA Electric A800 series inverter has an intuitive operation panel, rich functions, supports parameter initialization, password protection, and external control, suitable for various industrial scenarios. However, the EC.34 fault reveals potential commercial traps. Users should:

  • Familiarize with the Manual: Master parameter settings and operation methods.
  • Backup Parameters: Prevent loss of configuration during initialization.
  • Choose Suppliers: Prioritize cooperation with reputable dealers.
  • Keep Certificates: Ensure after-sales rights.

When facing unclear faults like EC.34, prioritize negotiating with the dealer; if unsuccessful, seek technical support or legal channels. This case reminds users to be vigilant against technical black-box operations and calls for the industry to standardize commercial behavior to protect user interests.


Posted on

User Guide for HYPERMIZER-M RT4 Series Inverter

Introduction to the Operation Panel

The operation panel of the HYPERMIZER-M RT4 series inverter provides various functions for parameter settings, status monitoring, and operational control. Below is an overview of the main functions of the operation panel:

Function Indicator Lights

  • RUN: Indicates the running status. The light is off when the inverter is stopped and on when it is running.
  • FWD/REV: Indicates forward or reverse operation. The light is off for forward operation and on for reverse operation.
  • LOCAL/REMOT: Indicates the control mode. The light is off for keypad control, on for terminal control, and flashing for remote communication control.
  • TUNE/TRIP: Indicates overload warning. The light is on for torque control mode, flashes slowly during self-learning, and flashes quickly during a fault.

Unit Indicator Lights

  • Hz: Frequency unit.
  • A: Current unit.
  • V: Voltage unit.
  • RPM: Speed unit.
  • %: Percentage.

Display Area

The 5-digit LED display shows the set frequency, output frequency, and other monitoring data, as well as alarm codes.

Keypad Buttons

  • PRG/ESC: Program key for entering or exiting the first-level menu.
  • DATA/ENTER: Confirmation key for entering the next menu level and confirming parameter settings.
  • : Increment key for increasing data or function codes.
  • : Decrement key for decreasing data or function codes.
  • : Shift key for cycling through display parameters in stop or run mode and selecting the modification position for parameters.
  • RUN: Run key for starting operation in keypad mode.
  • STOP/RST: Stop/Reset key for stopping operation or resetting from a fault.
  • QUICK/JOG: Multifunction key for switching functions based on P7-01 settings.
HYPERMIZER-M

Setting and Removing Passwords

Setting a Password

  1. Enter the function parameter mode and locate PP-00 (User Password).
  2. Set a non-zero value as the user password.
  3. Exit the function parameter mode; the password protection will be activated.

Removing a Password

  1. Enter the function parameter mode and input the correct user password.
  2. Locate PP-00 (User Password) and set it to 0.
  3. Exit the function parameter mode; the password protection will be deactivated.

Setting Parameter Access Restrictions

  1. Enter the function parameter mode and locate PP-04 (Function Code Modification Attribute).
  2. Set to 0 for modifiable or 1 for non-modifiable.

Restoring Factory Default Settings

  1. Enter the function parameter mode and locate PP-01 (Parameter Initialization).
  2. Set to 01 to restore default values, excluding motor parameters.
  3. Set to 02 to clear recorded information.

Forward/Reverse Control via Terminals and External Potentiometer Speed Control

Forward/Reverse Control via Terminals

  1. Terminals: FWD (Forward), REV (Reverse).
  2. Parameter Settings: Set P4-00 (D1 Terminal Function Selection) to 1 (Forward Operation) or 2 (Reverse Operation).

External Potentiometer Speed Control

  1. Terminals: AI1 (Analog Input Terminal 1).
  2. Parameter Settings: Set P0-03 (Main Frequency Source A Selection) to 4 (Panel Potentiometer Setting).

Fault Codes and Handling

Fault Codes

  • 01: Overcurrent fault.
  • 02: Undervoltage fault.
  • 03: Overvoltage fault.
  • 04: Overheating fault.
  • 05: Phase loss fault.
  • 06: Overload fault.
  • 07: Short circuit fault.
  • 08: Communication fault.
  • 09: Encoder fault.
  • 10: Parameter read/write fault.

Fault Handling

  1. Overcurrent Fault: Check if the motor and load are normal; ensure the motor is not overloaded.
  2. Undervoltage Fault: Check if the input voltage is normal; ensure the voltage is within the allowed range.
  3. Overvoltage Fault: Check if the input voltage is too high; ensure the voltage is within the allowed range.
  4. Overheating Fault: Check if the inverter’s cooling is normal; ensure the cooling fan is working properly.
  5. Phase Loss Fault: Check if the input power supply has a phase loss; ensure the power supply is normal.
  6. Overload Fault: Check if the motor and load are overloaded; ensure the load is within the allowed range.
  7. Short Circuit Fault: Check if the motor and load are short-circuited; ensure the circuit is normal.
  8. Communication Fault: Check if the communication lines are normal; ensure the communication equipment is working properly.
  9. Encoder Fault: Check if the encoder is working properly; ensure the encoder signal is normal.
  10. Parameter Read/Write Fault: Check if the parameter settings are correct; ensure the parameters are within the allowed range.
HYPERMIZER-M standard wiring diagram

Conclusion

The user manual for the HYPERMIZER-M RT4 series inverter provides detailed operational guidance and fault handling methods, helping users correctly operate and maintain the inverter. By understanding the operation panel functions, setting passwords and parameter access restrictions, restoring factory default settings, implementing forward/reverse control via terminals, and external potentiometer speed control, as well as identifying and handling common faults, users can better utilize the inverter’s capabilities, improving work efficiency and extending the equipment’s lifespan.

Posted on

User Guide for the Chuanken SCKR1 Series Soft Starter Manual

The Chuanken SCKR1 series soft starter is a powerful digital soft-start solution designed for motors ranging from 11 kW to 850 kW. This guide provides a detailed explanation of the operation panel functions, parameter initialization, parameter copying to another soft starter, password setup and removal, external terminal start mode, bypass control implementation, wiring methods for main and control circuits (including schematic diagrams, with real images preferred if available), key parameters, and fault codes with their meanings and troubleshooting steps. This will help users operate the device efficiently and safely.


SCR1 physical image

1. Functions of the Operation Panel (Keyboard, HMI)

The operation panel (HMI) of the SCKR1 series soft starter is the core interface for user interaction, offering parameter configuration, status monitoring, and fault diagnosis. Below are its main functions (refer to PAGE16, 6.1 Operation Panel):

  1. Display Screen:
  • Shows real-time status (e.g., current, power, motor temperature) and programming details.
  • Parameter 8D allows selection between real-time current or motor power display.
  • The bottom half of the screen can switch between options like soft starter status, motor temperature, current, and power using the “▲” and “▼” buttons.
  1. Button Functions:
  • Menu Navigation Keys (▲/▼): Switch between menu options, parameters, or adjust parameter values.
  • MENU Key: Enter menu or parameter editing mode, save parameter changes (includes STORE function).
  • EXIT Key: Exit menu or parameter editing, cancel unsaved changes.
  • ALT Key: Used with F1/F2 to access function logs or debugging tools.
  • F1/F2 Shortcut Keys: Quick access to common tasks (functions defined by parameters 8B and 8C).
  • L/R Key: Switch between Local and Remote control modes.
  1. Status LED Indicators:
  • Ready: Steady on indicates motor stopped and starter ready; blinking indicates waiting for restart delay or temperature check.
  • Run: Steady on indicates motor running at full voltage; blinking indicates starting or stopping.
  • Trip: Steady on indicates starter tripped; blinking indicates warning state.
  • Local: Steady on indicates local control mode; off indicates remote control mode.
  • If all LEDs are off, it indicates no control voltage.
  1. Synchronization Function:
  • The operation panel syncs with the soft starter’s parameters. If a different panel is inserted, a confirmation message appears, allowing the user to copy parameters from the panel to the starter or vice versa.

2. How to Initialize Parameters

Initializing parameters ensures the soft starter matches the motor (refer to PAGE7, 3.1 Setting Procedure Summary):

  1. Preparation:
  • Ensure no power voltage is applied before connecting cables.
  • Complete physical installation and control cable connections (see wiring section).
  1. Initialization Steps:
  • Step 1: Apply control voltage (A1, A2 terminals, 220-440 VAC).
  • Step 2: Set date and time:
    1. Press “ALT” + “TOOL” to enter the “Tool” menu.
    2. Use “▲/▼” to navigate to the “Date/Time” screen.
    3. Press “ENTER” to enter edit mode.
    4. Use “▲/▼” to adjust date and time values, press “ENTER” to save.
  • Step 3: Quick setup (for common applications):
    1. Press “MENU” to enter the main menu.
    2. Use “▲/▼” to select “Fast Setting,” press “ENTER” to access.
    3. Find your application in the list, press “ENTER” to start setup.
  • Step 4: If no matching application, use the standard menu:
    1. Return to the main menu, select “Standard Menu.”
    2. Navigate to “Motor Data 1,” edit parameter 1A (motor rated current) to match the motor nameplate.
  • Step 5: Press “EXIT” multiple times to exit the menu.
  1. Notes:
  • For advanced applications, refer to “Extended Menu” (PAGE31) and parameter descriptions (PAGE35).
  • Use the built-in simulation tool (3.3 Simulation Tool) to verify wiring and control logic.

3. How to Copy Parameters to Another Soft Starter

The operation panel supports parameter copying for easy configuration of multiple devices (refer to PAGE16, 6.1 Operation Panel):

  1. Steps:
  • Step 1: Save parameters to the operation panel on the source soft starter:
    1. Press “MENU,” enter “Load/Save Settings” (PAGE35).
    2. Select “Save to Display,” press “ENTER” to save.
  • Step 2: Remove the panel and insert it into the target soft starter.
  • Step 3: When the target device detects the new panel, it displays “New Display Detected”:
    1. Use “▲/▼” to select “Display to Starter.”
    2. Press “MENU” to confirm; parameters will be copied to the target starter.
  1. Notes:
  • If parameters don’t take effect, the target device loads default values; check compatibility.
  • Ensure both devices are of the same model to avoid parameter conflicts.

4. How to Set and Remove a Password

Password protection restricts parameter modifications (refer to PAGE28-29, 9.2 Parameter Write Protection & 9.3 Access Password):

  1. Set a Password:
  • Step 1: Press “MENU,” enter “Programming Menu.”
  • Step 2: Navigate to “Access Password” (parameter 15A).
  • Step 3: Enter a new password (default is 0000), press “ENTER” to save.
  • Step 4: Set “Parameter Write Protection” (parameter 15B) to “Read Only” to restrict changes.
  1. Remove a Password:
  • Step 1: Enter the “Access Password” menu.
  • Step 2: Input the current password, press “ENTER” to verify.
  • Step 3: Change the password to “0000,” set parameter 15B to “Read/Write” to remove protection.
  1. Notes:
  • If the password is forgotten, contact the supplier for a reset, which may require a factory reset.

SCKR1-7000 standard wiring diagram

5. How to Use External Terminal Start Mode

External terminal start is achieved via remote control inputs (refer to PAGE9, 4.4 Control Cable):

  1. Configuration:
  • The soft starter has 3 fixed remote inputs (e.g., C53, C54), supporting low-voltage, low-current control.
  • Press “L/R” to switch to remote mode (Local LED off).
  1. Wiring:
  • Start: Short C53-C54 (start input).
  • Stop: Open C53-C54.
  • Reset: Short another input pair (configurable, see parameter 6M).
  1. Parameter Settings:
  • In the “Input” menu (PAGE74, 6 Input), configure parameters 6A/6F (input functions) to “Start/Stop/Reset.”
  1. Notes:
  • Ensure correct wiring; test by observing the corresponding LED activation.

6. How to Implement Bypass Control

Bypass control bypasses the soft starter once the motor reaches full speed (refer to PAGE15, 5.2 Bypass Contactor):

  1. Built-in Bypass:
  • Models from 5.5 kW to 500 kW have built-in bypass, requiring no external contactor.
  • Automatically switches; no additional operation needed during runtime.
  1. External Bypass:
  • Models without built-in bypass require an external bypass contactor.
  • Contactor AC1 rating ≥ motor current.
  • Wiring: Connect the bypass contactor in parallel with the soft starter outputs (2/T1, 4/T2, 6/T3).
  1. Control:
  • Configure relay outputs (parameters 7A-7L) to “Bypass,” which close when the motor reaches full voltage, activating the bypass contactor.

7. Wiring (Main Circuit and Control Circuit)

Main Circuit Wiring (refer to PAGE10-11, 4.8-4.9)
  • Input Terminals: 1/L1, 3/L2, 5/L3 connect to three-phase power.
  • Output Terminals: 2/T1, 4/T2, 6/T3 connect to the motor.
  • Grounding: 5.5-55 kW models have 1 ground terminal at the input; 75-500 kW models have 2 (one at input, one at output).
  • Schematic (simplified text representation; refer to the manual for actual diagrams):
  [Power L1]---[1/L1]   [2/T1]---[Motor U]
  [Power L2]---[3/L2]   [4/T2]---[Motor V]
  [Power L3]---[5/L3]   [6/T3]---[Motor W]
  [Ground]------[Earth]
Control Circuit Wiring (refer to PAGE8-9, 4.2-4.4)
  • Control Voltage: A1, A2 terminals connect to 220-440 VAC.
  • Remote Inputs: C53-C54, etc., connect to external switches.
  • Schematic:
  [220-440V]---[A1]   [C53]---[Start Switch]---[C54]
               [A2]   [Other Inputs]---[Stop/Reset Switch]

8. Key Parameters

Below are critical parameters (refer to PAGE73-76, 12.2 Parameter Value):

  • 1A: Motor rated current, matches the motor nameplate.
  • 2A-2D: Start mode, ramp time, initial current, current limit; affect start performance.
  • 4A-4F: Protection settings, e.g., start timeout, undercurrent, instantaneous overcurrent.
  • 6A-6F: Input functions, define external terminal roles.
  • 7A-7L: Relay output functions, e.g., bypass control.
  • 15A-15B: Access password and write protection.

9. Fault Codes, Meanings, and Solutions

Below are common fault codes (refer to PAGE81-82, 13.5 Trip Code):

  1. 1 – Starting Time Limit:
  • Meaning: Start time exceeded.
  • Solution: Check parameter 4A, extend start time, or adjust load.
  1. 2 – Motor Overload:
  • Meaning: Motor overloaded.
  • Solution: Check motor load, adjust parameters 1B-1D, cool down and restart.
  1. 8 – Power Down/Power Circuit:
  • Meaning: Power failure or circuit not energized.
  • Solution: Check main contactor and fuses.
  1. 15 – Starter Communication:
  • Meaning: Communication failure.
  • Solution: Check interface connections, contact supplier.

For more faults, refer to PAGE81-82. Disconnect power before troubleshooting.