Posted on Leave a comment

Cause Analysis and Troubleshooting of ACS580 Inverter Warnings A581 and FAULT 5080

Cause Analysis

The ACS580 inverter may encounter warnings such as A581 (AUX code 0000 0001 Coolingyou fan stuck or disconnected) or FAULT 5080 (fan failure) during operation. These errors are closely related to the inverter’s cooling fan system.

Warning A581: This warning indicates that the auxiliary cooling fan of the inverter may be stuck or disconnected. When the fan speed is insufficient or has completely stopped, the system fails to receive normal tachometer pulse feedback, triggering this warning. Although the inverter may temporarily continue to operate in warning mode, prolonged operation can potentially cause further damage to the equipment.

FAULT 5080: This is a more severe error, indicating that the cooling fan has completely stopped working and is not outputting any tachometer pulse signals. This typically implies that the fan motor is damaged, the power line is disconnected, or the control signal is lost, causing the inverter to be unable to cool effectively. This can lead to overheating and direct shutdown to protect the equipment from further damage.

Troubleshooting

To address the A581 and FAULT 5080 issues with the ACS580 inverter, follow these troubleshooting steps:

  1. Check Auxiliary Codes:
    • Begin by identifying the affected fan based on the auxiliary code in the alarm message (e.g., AUX code 0000 0001 for A581). Code 0 usually indicates the main fan 1, while XYZ-formatted codes can further indicate the fan’s status and index.
  2. Inspect Fan Operation:
    • Visually inspect the fan’s physical operation to confirm whether it is spinning. If the fan is not rotating, check the power lines for secure connections, absence of shorts or breaks.
  3. Measure Tachometer Pulses:
    • Use an oscilloscope or tachometer to measure the fan’s tachometer pulse signal. Under normal conditions, the signal should be stable and at an appropriate frequency. Weak or unstable signals may indicate issues with the fan motor or sensor.
  4. Verify Power and Control Wiring:
    • Ensure the fan’s power and control wiring are connected correctly, without damage or poor contact. Check fuses and relays for proper functioning and stable power supply.
  5. Replace Faulty Fan:
    • If the fan is confirmed faulty, promptly replace it with a new one. During replacement, ensure the fan’s model and specifications match the original equipment, and install and wire it correctly.
  6. Cleaning and Maintenance:
    • Regularly clean and maintain the inverter and its cooling system, removing dust and debris to keep air passages clear and enhance cooling efficiency.
  7. Software Settings Review:
    • Access the inverter’s setup interface to review settings related to fan control. Ensure all control logic and alarm thresholds are configured correctly, avoiding unnecessary shutdowns due to false alarms.
  8. Contact Technical Support:
    • If the above steps fail to resolve the issue, promptly contact Longi’s technical support team or professional service personnel for specialized assistance and solutions.

In conclusion, by methodically troubleshooting and diligently maintaining the ACS580 inverter, potential issues causing warnings A581 and FAULT 5080 can be effectively identified and resolved, ensuring the stable operation of the inverter.

Posted on Leave a comment

ACS850 Inverter User’s Manual Overview

I. Introduction to ACS850 Inverter Features

The ABB ACS850 series inverter is a high-performance, multi-functional drive device designed specifically for industrial applications, supporting various motor types. Its key features include:

  • Extensive Power Range: Covering from 0.37 kW to 560 kW, catering to the needs of small to large-scale industrial applications.
  • High-Precision Control: Utilizing advanced control algorithms to provide precise motor control, including Direct Torque Control (DTC).
  • Modular Design: Easy to configure and expand, supporting multiple communication protocols and fieldbus interfaces.
  • Comprehensive Protection: Built-in multiple protection mechanisms to ensure stable system operation, including overcurrent, overload, and short-circuit protection.
  • User-Friendly Interface: Equipped with an intuitive control panel for easy operation and monitoring.
ACS850 inverter control framework diagram

II. Operating Instructions for ACS850 Inverter Control Panel

The control panel of the ACS850 inverter typically includes an LCD display, multiple function keys, and directional keys. While the specific key names may vary depending on the model or version of the control panel, the basic operation logic remains similar. The following are general instructions:

  • Menu Navigation: Use directional keys to move up, down, left, or right in the menu to select the desired function or parameter.
  • Parameter Setting: Enter the parameter setting menu, use directional keys to select specific parameters, and then adjust them using data increase/decrease keys.
  • Operation Control: The panel usually has clear control keys for start, stop, forward, reverse, etc., for direct control of the inverter’s operating status.
  • Display Switching: Some control panels may be equipped with dedicated keys to switch between different display modes or view alarm information.
Default control connection for ACS850 inverter factory macro

III. Configuration Guide for Terminal Control Mode

When using terminal control mode, it is necessary to select the appropriate macro configuration and set relevant parameters based on application requirements. The following are general steps:

  • Select Macro Configuration: Based on the application type (e.g., fan/pump, compressor, etc.), select the suitable macro configuration in the inverter’s parameter settings. This typically involves presetting a series of related parameters to suit specific application needs.
  • Configure Input/Output Terminals:
    • Connect external control signals (e.g., start, stop, speed setting, etc.) to the corresponding input terminals.
    • Configure output terminals as needed (e.g., fault output, operating status output, etc.).
  • Set Control Parameters:
    • Adjust relevant control parameters according to the selected macro configuration, such as acceleration time, deceleration time, PID controller parameters, etc.
    • Ensure that AI1 (or other analog input terminals) is correctly configured as the speed setting input, and set appropriate scaling factors and offsets.
  • Save Settings and Test:
    • After saving all settings, test the inverter to ensure that all control signals are working as expected.
    • Check and eliminate any potential wiring errors or incorrect parameter configurations.

IV. Fault Code Analysis and Troubleshooting

The ACS850 inverter features a fault diagnosis function that displays corresponding fault codes when a fault occurs. Based on the fault code table (usually located in a specific chapter of the manual), users can quickly identify the problem and take appropriate measures. The following are some common fault codes and their troubleshooting suggestions:

  • 0001: Overcurrent fault. Check the motor, cables, and inverter output for normality; adjust the load or increase overload protection settings.
  • 0002: DC link overvoltage fault. Check the stability of the power supply voltage; consider increasing deceleration time or installing a braking resistor.
  • 0004: Motor short-circuit fault. Check the motor windings for short-circuits; replace the motor if necessary.

Note: The above steps and suggestions are based on a general description of the ACS850 series inverter. When performing specific operations, please refer to the ACS850 firmware manual and follow the official guidance provided by ABB. For any questions or issues, it is recommended to contact Longi Electromechanical Support for professional assistance.


Posted on Leave a comment

MotiFlex e180 Servo Drive Wiring, Debugging,manual,and Fault Handling Guide

I. Main Circuit Wiring Instructions

  1. Power Supply Wiring
    • The MotiFlex e180 servo drive supports three-phase AC power input, typically ranging from 200V to 480V AC, depending on the selected model.Before wiring, ensure the power supply is switched off and disconnected to avoid the risk of electric shock.
  2. Wiring Steps:
    • Verify that the power supply voltage and frequency meet the drive requirements.
    • Connect the three phases (L1, L2, L3) and ground wire (PE) of the power supply to the drive’s input terminals using appropriately sized cables.
    • Ensure secure cable connections and check that the cable shielding is properly grounded.
  3. Motor Wiring
    • Connect the motor cable to the drive’s motor output terminals (U, V, W), ensuring the motor ground wire (PE) is also properly connected.
    Wiring Steps:
    • Check that the motor model and rated parameters match the drive.
    • Use appropriately sized motor cables to connect the three-phase wires (U, V, W) and ground wire (PE) to the corresponding output terminals of the drive.
    • Tighten the cable connectors to ensure a reliable connection.
MotiFlex e180 servo main circuit wiring diagram

II. Control Circuit Wiring Instructions

  1. I/O Interface Description
    • The MotiFlex e180 provides a rich set of I/O interfaces, including Digital Input (DI), Digital Output (DO), Analog Input (AI), and Analog Output (AO) for communication and control with external devices or controllers.
    • DIs receive switching signals from external devices, such as start, stop, and emergency stop.
    • DOs send control signals to external devices, such as alarm output and motor running status indication.
    • AIs receive analog signals, such as speed setting and position feedback.
    • AOs output analog signals, such as drive current and voltage feedback.
  2. Control Circuit Wiring
    Wiring Steps:
    • Prepare suitable control cables, ensuring that the cable specifications and length meet the requirements.
    • Connect the control cables to the corresponding I/O interfaces according to the drive wiring diagram. Pay attention to distinguishing between inputs and outputs, as well as positive and negative polarity.
    • For digital outputs requiring external power (e.g., relay outputs), ensure that the external power specifications meet the requirements and are correctly wired.
IO Function Description and Control Circuit Wiring Diagram of ABB Server MotiFlex e180

III. Debugging MotiFlex e180 Servo Drive with Mint WorkBench

  1. Installing and Configuring Mint WorkBench
    • Download and install Mint WorkBench software: Obtain the latest version of Mint WorkBench from the ABB official website and follow the installation guide to complete the installation.
    • Connect the drive: Use an Ethernet cable to connect the computer to the MotiFlex e180’s E3 port, and configure the computer’s network adapter to ensure it is in the same subnet as the drive’s IP address.
  2. Starting and Debugging
    • Launch Mint WorkBench, create a new project, and select to connect to the MotiFlex e180 servo drive.
    • Run the debugging wizard: In Mint WorkBench, start the debugging wizard, follow the prompts to input motor and drive parameters, and proceed with automatic adjustment and performance testing.
    • Monitoring and Adjustment: Use the monitoring window to view the drive status in real-time and make manual adjustments as needed to optimize drive performance.
ABB server MotiFlex e180 status display

IV. Fault Code Analysis and Solutions

  • Error Code 10033 (ecSTO_ACTIVE): Indicates that the STO (Safe Torque Off) function is active.
    • Cause: The STO input signal is not energized.
    • Solution: Check the wiring and power supply of the STO input signal to ensure normal operation.
  • Error Code 10015 (Overcurrent Protection): Indicates that the drive has detected an overcurrent condition.
    • Cause: Excessive motor load, motor or cable short circuit, etc.
    • Solution: Inspect motor and cable connections, ensure no short circuits or overloads; adjust the load or reduce the operating speed.
  • Error Code 20006 (Axis Alarm): Indicates abnormal encoder feedback data.
    • Cause: Incorrect encoder wiring, encoder failure, or interference with the feedback signal.
    • Solution: Check encoder wiring, replace faulty encoders, or increase signal shielding measures.

By following these steps, you can effectively debug the MotiFlex e180 servo drive using Mint WorkBench and resolve common fault issues. For further questions, please contact us for a detailed manual or free technical support.

Posted on Leave a comment

Cause Analysis and Solution for FF89 Alarm on ABB VFD ACS800

The ABB ACS800 VFD (Variable Frequency Drive) plays a pivotal role in industrial automation, finding extensive applications across various industrial control systems. However, during operation, it may encounter various alarm messages.

ACS800 VFD panel display fault

Alarm Message: FF89 – MOD CHOKE T (FF89) 09.11 AW 3 bit 13

Cause:

  • Overheating of Reactor in Liquid-Cooled R8i Inverter Module
    The reactor in the liquid-cooled R8i inverter module has exceeded its temperature threshold.

Resolution Steps:

  1. Check the Inverter Fan:
    • Ensure the inverter fan is operating properly and providing sufficient cooling to the reactor.
    • Inspect for any blockages or dirt accumulation that may impede airflow.
  2. Inspect Ambient Temperature:
    • Verify that the ambient temperature surrounding the VFD is within the recommended range.
    • Ensure there are no heat sources in close proximity that could contribute to overheating.
  3. Examine the Liquid Cooling System:
    • Thoroughly check the condition of the liquid cooling system, including pipes, pumps, and radiators.
    • Confirm that the coolant flow rate and temperature are within normal operating parameters.
    • Inspect for leaks or corrosion that could indicate a need for maintenance or replacement.
  4. Review VFD Operation and Configuration:
    • Ensure the VFD is not operating under excessive load conditions that could lead to overheating.
    • Check the VFD’s settings and parameters to verify they are appropriate for the application and load requirements.
  5. Check for Alarms or Warnings in the VFD’s Diagnostic System:
    • Use the VFD’s diagnostic tools or software (such as DriveWindow) to check for any additional alarms or warnings that may provide further insight into the issue.
  6. Service and Maintenance:
    • If the above steps do not resolve the issue, consider scheduling preventive maintenance or contacting ABB support for further assistance.
ACS800 Fault Code Table

By following these resolution steps, you can effectively diagnose and address the FF89 alarm on your ABB ACS800 VFD, ensuring reliable and efficient operation of your industrial automation system.

Posted on Leave a comment

Modifying Power Ratings for ABB ACS800 Series VFD Control Boards

Modifying the power ratings on ABB ACS800 series VFD (Variable Frequency Drive) control boards can be performed following a set of detailed steps, depending on the firmware version of the RDCU (Remote Digital Control Unit) board. This guide outlines the processes for both pre-version 7200 and post-version 7200 RDCU boards.

Pre-Version 7200 RDCU Power Rating Modification Steps

  1. Enter 9903 and set to YES:
    • Access the control panel and navigate to parameter 9903.
    • Set the value to YES to enable modification mode.
  2. Enter 1603 and set to 564:
    • Navigate to parameter 1603 and enter the passcode 564.
    • This unlocks access to parameter groups 112 and 190.
  3. Select XXNONE in 11206:
    • Navigate to parameter 11206 and select XXNONE.
    • This prepares the board for power cycle.
  4. Power Cycle:
    • Turn off the power to the RDCU board.
    • Wait a few seconds and then turn the power back on.
  5. Re-enter 1603 and set to 564 (again):
    • Repeat step 2 to ensure the passcode is active.
  6. Select the Desired Power Rating in 11206:
    • Navigate to parameter 11206 again and select the desired power rating (e.g., 170-3).
  7. Initialize Parameters:
    • Perform any necessary parameter initialization steps as recommended by the manufacturer’s guidelines.
  8. Final Power Cycle:
    • Repeat the power cycle process to ensure the new settings take effect.

Post-Version 7200 RDCU Power Rating Modification Steps

  1. Enter 9903 and set to YES:
    • Same as the pre-version 7200 steps.
  2. Enter 1603 and set to 564:
    • Same as the pre-version 7200 steps.
  3. Select the Desired Power Rating Directly in 11221:
    • Instead of using 11206, navigate to parameter 11221 and directly select the desired power rating (e.g., 11221 = sr170_3).
  4. Re-enter 9903 and set to YES (optional):
    • Depending on the specific firmware, this step may be optional but recommended for confirmation.
  5. Power Cycle:
    • Turn off the power to the RDCU board and then turn it back on.

Notes and Cautions

  • Parameter Ranges: Note that parameters 11219 to 11223 represent different power ratings. Ensure you select the correct one for your application.
  • Normal Usage Caution: Do not modify the settings on a normally operating VFD unless absolutely necessary, as it may result in the loss of important operational parameters.
  • Firmware Differences: Always refer to the latest ABB documentation for your specific firmware version, as steps may vary slightly between versions.
  • Parameter Unlocking: Remember that entering 564 in parameter 1603 unlocks advanced parameters, allowing for the modification of power ratings and other settings.

By following these steps carefully, you can safely modify the power ratings of ABB ACS800 series VFD control boards, ensuring optimal performance and compatibility

Posted on Leave a comment

ACS530 VFD 5098 Alarm Fault Analysis and Troubleshooting

ACS530 VFD 5098 Alarm Fault Analysis and Troubleshooting

When working with ABB’s ACS530 series VFDs (Variable Frequency Drives), encountering specific fault alarms such as the 5098 alarm can be a concern. While the ACS530 series manual may not directly mention this alarm code, by referencing the manual of its similar ACS580 series VFDs, also from ABB, we can gain insight into the 5098 alarm and apply that knowledge to troubleshooting the ACS530 series.

Physical picture of ACS530 with fault number 5098

I. Understanding the 5098 Alarm

In the ACS580 series, the 5098 alarm indicates “I/O Communication Lost,” signifying a failure in communication with the standard I/O (Input/Output) devices. This usually occurs when there is an issue with the communication link between the VFD’s I/O terminal board (where analog inputs like AI1 reside) and the main board. Similarly, in the ACS530 series, the 5098 alarm likely indicates a communication issue as well.

II. Possible Causes of the Fault

  1. Power Issues:
    • The 10V or 24V power supply on the I/O terminal board may be abnormal, leading to unstable or failed communication.
    • There may be short circuits, open circuits, or poor connections in the power lines.
  2. Hardware Connection Problems:
    • Connections between the I/O terminal board and the main board may be loose, have cold solder joints, or be corroded.
    • Terminals may have aged due to prolonged use, resulting in poor contact.
  3. Communication Module Failure:
    • The VFD’s I/O communication module may be damaged, preventing proper communication with the I/O terminal board.
  4. Software or Configuration Issues:
    • The VFD’s software configuration may have errors, affecting communication protocols or parameter settings.
    • Despite similarities in design and software between the ACS530 and ACS580 series, subtle differences in configuration may lead to unexpected alarms in the ACS530 under certain conditions.
Physical picture of ABB inverter ACS530

III. Fault Troubleshooting Steps

To address the 5098 alarm in the ACS530 VFD, follow these troubleshooting steps:

  1. Check Power Supplies:
    • Use a multimeter to verify the 10V and 24V power supplies on the I/O terminal board are functioning correctly.
    • Inspect power lines for completeness, shorts, or open circuits.
  2. Inspect Hardware Connections:
    • Disconnect all connections related to the I/O terminal board, reconnect them securely, and ensure they are tight.
    • Examine the connections between the I/O terminal board and the main board for looseness, cold solder joints, or corrosion, and make necessary repairs.
  3. Assess Communication Module:
    • If possible, test replacing the I/O communication module with an identical one to determine if it’s faulty.
  4. Reset and Restart:
    • Attempt to reset the VFD to clear the alarm.
    • If resetting fails, power off the VFD, wait for a while, and then power it back on to eliminate any software-related communication issues.
  5. Contact Technical Support:
    • If none of the above steps resolve the issue, contact ABB’s technical support team or a professional service provider for further diagnosis and repair.

IV. Conclusion

Despite the ACS530 series VFD manual’s lack of direct mention of the 5098 alarm, referencing similar ACS580 series documentation and contextual analysis enables understanding the likely fault type and appropriate troubleshooting methods. In practice, consider all potential causes

Posted on Leave a comment

ACH550 Inverter User Manual: Comprehensive Guide for Installation, Operation, and Maintenance


I. Operating Panel (Control Pad) Usage

1. Overview of Control Pad

The operating panel (control pad) of the ACH550 inverter serves as the primary interface between the user and the inverter, enabling status display, parameter setting, and operation control.

2. Basic Operations

  • Starting and Stopping:
    • Press “HAND” Button: Enters manual mode, allowing adjustment of inverter output frequency via the up and down arrow keys.
    • Press “AUTO” Button: Switches to automatic mode, where inverter operation is controlled by external signals (such as terminal signals or communication signals).
  • Display Mode Switching:
    • Access different display modes (e.g., output mode, parameter mode, assistant mode) through the menu button (MENU) on the control pad.
  • Parameter Setting:
    • In parameter mode, use the up and down arrow keys to select the parameter to modify. Press the edit button (EDIT) to enter the parameter settings, input new values using the numeric keys, and save changes with the save button (SAVE).

3. Assistant Mode

The assistant mode provides guided steps for starting and configuring the inverter, ideal for first-time users or those requiring quick setup.

II. Terminal Starting and Potentiometer Speed Control

1. Terminal Starting Wiring

  1. Connect Main Power: Wire the inverter’s input power to the corresponding terminals (U1, V1, W1).
  2. Connect Motor: Connect motor wires to the inverter’s output terminals (U2, V2, W2).
  3. Control Signal Wiring:
    • Connect the start signal (e.g., DI1) to the inverter’s digital input terminal.
    • If direction control is required, connect the direction signal to the corresponding terminal (e.g., DI2).

2. Potentiometer Speed Control Wiring

  1. Potentiometer Selection: Choose an appropriate rotary or slide potentiometer.
  2. Wiring:
    • Connect the three pins of the potentiometer to the inverter’s analog input terminals (e.g., positive, negative, and signal terminals of AI1).
    • Adjust the potentiometer knob to vary the voltage or current signal input to AI1, thereby controlling the inverter’s output frequency.

3. Parameter Setting

  • Enter parameter mode and select an appropriate macro (e.g., fan macro or general PID macro) that presets parameters suitable for specific applications.
  • Adjust parameters related to start/stop, direction control, and analog inputs based on actual wiring configurations.
Default macro HVAC wiring diagram for ACH550

III. Inverter Fault Code Analysis and Troubleshooting

1. Fault Code Inquiry

Display recent fault codes through the control pad, which correspond to different fault types.

2. Common Fault Codes and Troubleshooting Methods

  • Overcurrent Fault:
    • Cause: Motor overload, motor short circuit, improper parameter settings, etc.
    • Solution: Check motor and load conditions, adjust overload protection parameters, and confirm inverter and motor parameter compatibility.
  • Undervoltage Fault:
    • Cause: Low or fluctuating input power voltage.
    • Solution: Verify power supply voltage stability, increase input filter capacitors, or adjust undervoltage protection thresholds.
  • Overheat Fault:
    • Cause: Poor inverter cooling, high ambient temperature.
    • Solution: Improve inverter cooling conditions, such as installing additional cooling fans or reducing ambient temperature.
  • Communication Fault:
    • Cause: Communication line issues, incorrect communication parameter settings.
    • Solution: Check communication line connections, ensure communication parameter settings match the device configuration.

IV. Precautions

  • Always disconnect inverter power before performing any wiring or parameter adjustments.
  • Observe control pad status indicators and fault codes during operation, promptly addressing potential issues.
  • For complex faults or unsolvable problems, contact ABB technical support or a qualified service
Posted on Leave a comment

ACS510 Variable Frequency Drive (VFD) User Guide: Operating Panel Usage, Terminal Mode Startup and Speed Adjustment Methods, Fault Analysis and Solution Methods

ACS510 Variable Frequency Drive (VFD) User Guide

I. Operating Panel Usage

  1. Power On/Off
    Before powering on, ensure all connections are correct and the surrounding environment meets safety standards.
    Use the power switch on the operating panel to turn the power on or off.
  2. Mode Switching
    LOC/REM Button: Used to switch the control mode of the VFD. Press and hold this button for 2 seconds to toggle between Local Control (LOC) and Remote Control (REM) modes.
    In Remote Control mode, the VFD can be controlled via external terminals or communication interfaces.
  3. Display and Operation
    Display: The LCD screen on the operating panel displays various status information of the VFD, such as motor speed, current, voltage, etc.
    Button Operation: Use the Up/Down arrow buttons to navigate through menus and parameters. The MENU/ENTER button is used to enter and exit menus, while the EXIT/RESET button exits to the previous menu level or resets settings.
  4. Parameter Modification
    Enter the parameter mode, select the parameter group to be modified, adjust the parameter value using the Up/Down arrow buttons, and save the settings with the SAVE button.
ACS510 drive operation panel basic function diagram

II. VFD Terminal Start-up and Potentiometer Speed Control Wiring Methods

  1. Terminal Start-up Wiring
    External Start Signal: Typically, connect the external start signal (e.g., a push-button switch) to the DI1 (Digital Input 1) terminal of the VFD and connect the common terminal to DI COM (Digital Input Common).
    Direction Control: If direction control is required, connect the direction signal to the DI2 terminal.
    Run Enable: Some applications may require an additional run enable signal, which can be connected to the appropriate DI terminal.
  2. Potentiometer Speed Control Wiring
    Analog Input Wiring: When using a potentiometer for speed control, connect the output terminal of the potentiometer to the AI1 (Analog Input 1) terminal of the VFD and connect AI COM (Analog Input Common) to the common terminal.
    Parameter Setting: In parameter group 11, set Reference 1 Select (REF1 SELECT) to AI1 to ensure the VFD receives the speed reference signal from AI1.
standard macro of ACS510 drive function diagram

III. Parameter Settings

  1. Selecting Standard Macros
    Enter parameter group 99, find parameter 9902 (APPLIC MACRO), set it to 1, and select the ABB standard macro. This will automatically set a predefined set of parameters suitable for most general applications.
  2. Motor Parameter Settings
    Input the motor’s rated voltage (9905 MOTOR NOM VOLT), rated current (9906 MOTOR NOM CURR), rated frequency (9907 MOTOR NOM FREQ), rated speed (9908 MOTOR NOM SPEED), and rated power (9909 MOTOR NOM POWER), ensuring these parameters match the data on the motor’s nameplate.
  3. Other Important Parameters
    Acceleration Time (2202 ACCELER TIME 1): Sets the time required for the motor to accelerate from rest to maximum frequency.
    Deceleration Time (2203 DECELER TIME 1): Sets the time required for the motor to decelerate from maximum frequency to rest.
    Maximum Output Frequency (2008 MAXIMUM FREQ): Sets the maximum frequency output of the VFD.

IV. VFD Fault Code Analysis and Resolution Methods

  1. Overcurrent Fault (Code 1: OVERCURRENT)
    Cause: Motor overload, excessively short acceleration time, motor fault, etc.
    Solution: Check if the motor is overloaded, increase the acceleration time, inspect motor and cable connections.
  2. DC Overvoltage (Code 2: DC OVERVOLT)
    Cause: Excessively high input voltage, excessively short deceleration time, improper braking resistor, etc.
    Solution: Check the input voltage, increase the deceleration time, inspect the braking resistor configuration.
  3. Overtemperature Fault (Code 3: DEV OVERTEMP)
    Cause: Excessively high ambient temperature, faulty cooling fan, dust accumulation, etc.
    Solution: Lower the ambient temperature, clean dust, replace faulty fan.
  4. Motor Stall (Code 12: MOTOR STALL)
    Cause: Motor or load stall, improper motor selection, etc.
    Solution: Inspect the motor and load, ensure correct motor selection.
  5. Panel Loss (Code 10: PANEL LOSS)
    Cause: Communication fault between the control panel and the VFD.
    Solution: Check control panel connections, communication settings, and cables.

Please follow this guide for operation and adjust parameters and wiring according to actual conditions. If any issues arise, please contact us technical support promptly.

Posted on Leave a comment

Understanding and Resolving FAULT 7086 Alarm in ACS380 and ACS Series (ACS180, ACS530, ACS580, ACS880) Inverters

Introduction

When using ABB’s ACS series inverters, including ACS180, ACS530, ACS580, and ACS880, users may encounter the FAULT 7086 alarm code, which is not explicitly mentioned in the manuals for these models. This article delves into the reasons behind this alarm and provides comprehensive solutions to help users quickly identify and resolve the issue.

Fault 7086 of ABB drive

Background of FAULT 7086 Alarm

Although the operation manuals for ACS180, ACS530, ACS580, and ACS880 do not directly mention FAULT 7086, the explanation for this alarm code is found in the ACS380 (specifically designed for crane applications) manual. FAULT 7086 indicates “AI Overvoltage in I/O Module,” meaning that an overvoltage has been detected at the analog input (AI) port.

Cause Analysis

AI Port Overvoltage: When the input voltage at the AI port exceeds the set upper limit (typically 10VDC or a configurable value such as 7.5VDC), the inverter triggers the FAULT 7086 alarm to protect internal circuits from damage.

AI Signal Mode Change: If the AI signal level exceeds the acceptable range, the inverter may attempt to automatically switch the AI to voltage mode. If this fails, it will trigger the alarm.

Circuit Board Component Issues: Although the circuit board designs of ACS180, ACS530, ACS580, and ACS880 differ, they share a core control system. Issues with the mainboard, drive board connections, or related components can also lead to unexpected FAULT 7086 alarms.

The posistion of I/O module

Solutions

1.Check AI Voltage:

(1)Use a multimeter to measure the actual input voltage at the AI port and confirm if it exceeds the set upper limit.

(2)Adjust the AI port’s voltage upper limit setting, if necessary, to suit the current operating 2.environment.

(1)Inspect External Connections:

Verify that the external signal source for the AI port is normal, with no abnormal fluctuations or damage.

(2)Check the connection cables and plugs for the AI port to ensure they are securely connected and free from looseness.

3.Examine Circuit Boards and Modules:

(1)If suspecting a circuit board or module failure, first inspect the cables and plugs between the mainboard and drive board, cleaning dust and ensuring good contact.

(2)If possible, try replacing suspected circuit boards or modules to verify if the issue is resolved.

4.Refer to Relevant Documentation:

(1)Although the ACS180, ACS530, ACS580, and ACS880 manuals do not directly mention FAULT 7086, refer to the ACS380 manual for more information on handling AI overvoltage.

(2)Contact our technical team for free technical consultation and assistance

5.Reset the Inverter:

After ruling out external hardware issues, attempt to reset the inverter to see if the alarm clears.

I/O extension module of acs380

Conclusion

The FAULT 7086 alarm in ACS series inverters, including ACS180, ACS530, ACS580, and ACS880, can occur under specific circumstances not directly mentioned in their manuals. By thoroughly analyzing the alarm’s background and causes, and implementing appropriate solutions, users can effectively identify and resolve the issue. During the process, ensure safe operation and back up important data to prevent unexpected losses.

Posted on Leave a comment

ABB Inverter ACS530 Series Fault 2310: Causes and Solutions

The ACS530 series inverter from ABB, a leading player in industrial automation, is widely utilized across various industries. However, during operation, users may encounter various fault alarms, with fault code 2310 being a common one, indicating an overcurrent fault. Based on the provided documentation, this article delves into the causes and corresponding solutions for ABB Inverter ACS530 series alarm 2310.

I. Causes of Fault 2310

1. Excessive Motor Load

When the motor load exceeds its rated capacity, it can lead to a sharp increase in current, triggering the overcurrent protection. This may be due to an overly heavy load driven by the motor, mechanical jams, or motor stalls.

2. Incorrect Inverter Parameter Settings

The parameter settings of the inverter significantly impact its operational performance. Improper settings for acceleration time, deceleration time, or low current limits and overload protections can cause excessive current during motor startup or operation, resulting in an overcurrent alarm.

3. Unstable Power Supply Voltage

Fluctuations in power supply voltage directly affect the output voltage and current of the inverter. Unstable power supply can prevent the inverter from operating steadily, causing the output current to exceed normal ranges and trigger the overcurrent protection.

4. Motor or Cable Faults

Internal motor shorts, open windings, or grounding faults in motor cables can lead to excessive current. Additionally, contactors in the motor cable that are opening or closing can generate instantaneous high currents during switching, causing an overcurrent alarm.

5. Internal Inverter Faults

Damage or aging of internal components such as power modules, drive circuits, or current detection circuits in the inverter can result in unstable output currents, triggering an overcurrent alarm.

II. Solutions

1. Check Motor Load

First, inspect if the motor’s driven load is excessive. If so, attempt to reduce the load or replace the motor and inverter combination with higher capacities. Additionally, check for mechanical jams or stalls and address them promptly.

2. Review and Adjust Inverter Parameters

Examine the inverter’s parameter settings, particularly acceleration time, deceleration time, current limits, and overload protections. Ensure these settings are appropriate for the motor’s actual operational requirements. Adjust them if found to be incorrect.

3. Stabilize Power Supply Voltage

Use a multimeter or similar tools to check the stability of the power supply voltage. If significant fluctuations are present, implement measures to stabilize it, such as installing voltage stabilizers or UPS systems.

4. Inspect Motor and Cables

Examine the motor and motor cables for faults. Check for short circuits or open windings in the motor, verify the insulation resistance of the cables, and ensure no power factor correction capacitors or surge absorbers are present in the cables that could contribute to abnormal currents.

5. Check Internal Inverter Components

If all the above checks are normal, the overcurrent alarm may be due to internal inverter component damage. Contact professional technicians for inspection or replacement of faulty internal components.

III. Preventive Measures

To avoid the occurrence of ABB Inverter ACS530 series fault 2310, adopt the following preventive measures:

Regular Inspections and Maintenance: Conduct periodic inspections and maintenance of the motor and inverter to ensure their smooth operation.

Appropriate Parameter Settings: When setting inverter parameters, base them on the motor’s actual conditions to prevent incorrect settings from causing overcurrent faults.

Stable Power Supply Voltage: Maintain stable power supply voltage to prevent its fluctuations from affecting the inverter’s performance.

Suitable Motor and Inverter Selection: Choose motors and inverters that match the actual load requirements to prevent overcurrent faults due to excessive loads.

In conclusion, ABB Inverter ACS530 series fault 2310 is a critical fault alarm that requires attention. By thoroughly examining motor loads, adjusting inverter parameters, stabilizing power supply voltage, inspecting motors and cables, and checking internal inverter components, this issue can be effectively resolved, ensuring the inverter’s smooth operation. Furthermore, implementing preventive measures can reduce the likelihood of overcurrent faults and enhance the reliability and stability of the equipment.