Posted on 2 Comments

User Guide for Inovance Inverters MD280 Series Manual


I. Introduction

The Inovance MD280 series inverter is a powerful and user-friendly universal inverter widely applied in various automation equipment such as textile, papermaking, and machine tools. This guide will detail the operation panel functions, terminal start/stop configuration, external potentiometer speed regulation settings, and fault code troubleshooting for the MD280 inverter.

Function diagram of  Inovance Inverters MD280 operation panel

II. Operation Panel Functions and Usage

The MD280 inverter’s operation panel serves as the primary interface between the user and the inverter, providing functionality such as run, stop, reset, and speed adjustment.

  • RUN Key: Pressing this key starts the inverter.
  • STOP/RES Key: Used to stop the inverter or reset it in case of a fault.
  • Multi-Function Key (MF.K): Depending on the setting, this key can switch command sources, toggle between forward and reverse rotation, or initiate jogging.
  • Speed Adjustment Potentiometer (if equipped): Rotating the potentiometer directly adjusts the inverter’s output frequency for speed regulation.

The LED display on the panel shows the inverter’s operating status, frequency, current, and other parameters, facilitating real-time monitoring.

 Inovance Inverters MD280 Control Circuit Wiring Diagram

III. Terminal Start/Stop and External Potentiometer Speed Regulation

The MD280 inverter supports start/stop control through external terminals and speed regulation using an external potentiometer. Here are the detailed setup and wiring instructions:

1. Terminal Start/Stop Configuration

First, set the control command source through the inverter parameters. Navigate to the inverter parameter settings and set F0-00 to “1” (terminal command channel). Then, configure the DI terminal functions using the F2 group parameters, for example:

  • Set F2-00 to “1” to assign DI1 as the forward run terminal.
  • Set F2-01 to “2” to assign DI2 as the reverse run terminal.
  • Set F2-04 to “8” to assign DI4 as the free stop terminal.

When wiring, connect the external start, stop buttons, or contactors to the DI1, DI2, and DI4 terminals (depending on specific requirements), ensuring the common terminals are connected to the inverter’s COM terminal.

 Inovance Inverters MD280 Label

2. External Potentiometer Speed Regulation

The MD280 inverter supports analog speed regulation via the AI2 terminal using an external potentiometer. First, set the J2 jumper on the control board to “V” (voltage input mode). Then, connect the three pins of the external potentiometer to AI2, GND, and +10V (or an equivalent voltage source from an external power supply).

In the parameter settings, ensure F0-01 is set to “1” (AI1 analog input) or “2” (AI2 analog input), depending on which AI terminal the potentiometer is connected to. Additionally, configure the AI input minimum and maximum values, along with the corresponding output frequency range, using parameters F2-09 to F2-12.

IV. Fault Code Meanings and Solutions

During operation, the MD280 inverter may encounter various faults and display corresponding fault codes on the LED screen. Here’s an explanation and solution for ERR02:

ERR02: Acceleration Overcurrent

  • Meaning: The inverter detects an overcurrent during acceleration.
  • Possible Causes:
    • Excessive motor load.
    • Too short acceleration time setting.
    • Improper V/F curve configuration.
  • Solutions:
    • Check if the motor load exceeds the rated capacity and reduce the load if necessary.
    • Increase the acceleration time (adjust parameter F0-09).
    • Optimize the V/F curve settings by adjusting parameters like F1-05 (torque boost).
    • Inspect the motor and connecting cables for short circuits or ground faults.

By following these steps, you can effectively resolve the ERR02 fault encountered during MD280 inverter operation, ensuring stable equipment performance.

 Inovance Inverters experiences Error02 fault

V. Conclusion

The Inovance MD280 series inverter, with its robust functionality and user-friendly operation, holds a significant position in various automation equipment. This guide aims to enhance your understanding of the inverter’s operation panel functions, terminal start/stop and external potentiometer speed regulation settings, as well as fault code troubleshooting. By mastering these concepts, you can fully leverage the inverter’s performance advantages, boosting production efficiency.

Posted on Leave a comment

Analysis and Solution for OC Alarm Code in ZONCN Inverter NZ200 Series

In industrial automation control systems, inverters serve as critical devices for power transmission control, and their stability and reliability are directly related to the continuous operation of production lines. The Zhongchen Inverter NZ200 series, as a high-performance option, may encounter specific alarm codes during operation, particularly the OC (Over-Current) alarm.

Normal display content on the operation panel when ZONCN VFD is working

For short-duration, high-current OC alarms in the NZ200 series, the primary causes generally stem from issues within the current detection circuit of the drive board or potential damage to the module itself. These alarms may recur even after a reset due to underlying issues. Typically, the root causes can be attributed to the following scenarios:

  1. Excessively Long Motor Cables: Long motor cables can introduce excessive leakage current, potentially triggering the OC alarm.
  2. Inadequate Cable Selection: Choosing marginal cable types can also result in higher leakage currents, especially under high load conditions.
  3. Loose Cable Connections and Damage: Loose cable connections or damaged cables can cause arcing effects when the load current surges, triggering the OC protection mechanism.

Recommended Solutions:

ZONCN inverter OC3 alarm
  • Inspect and Shorten Motor Cables: Review the cable length and ensure it meets the manufacturer’s recommendations. If possible, shorten the cable length to reduce leakage current.
  • Upgrade Cable Quality: Replace existing cables with higher-quality, appropriately rated ones to minimize leakage current issues.
  • Tighten Cable Connections and Check for Damage: Thoroughly inspect all cable connections for tightness and integrity. Replace any damaged cables immediately.
  • Monitor and Adjust Load Conditions: Keep track of load changes and adjust inverter settings accordingly to avoid excessive current surges.
  • Inspect and Replace Drive Board/Module: If the issue persists despite the above measures, consider replacing the drive board or entire inverter module, as the internal circuitry may have been damaged.

By addressing these potential causes and implementing preventive maintenance practices, operators can significantly reduce the likelihood of OC alarms in their Zhongchen Inverter NZ200 series, ensuring the smooth and reliable operation of their industrial automation systems.

Posted on Leave a comment

Analysis and Solution of INI Alarm in ZONCN VFD NZ200T

I. Analysis of INI Alarm Causes

Image of zoncn inverter displaying INI alarm
  1. Literal Interpretation of INI Alarm
    • In VFDs, the “INI” alarm likely indicates issues or errors encountered during the device’s initialization process. This can stem from various reasons, including improper parameter settings, hardware failures, firmware issues, or external device connection errors.
    • For VFDs like the NZ200T, which employs open-loop vector control, the “INI” alarm may signify the VFD’s failure to correctly complete its initialization process upon startup or reset. This could result from unsatisfied specific hardware or software conditions, leading to the interruption or failure of the initialization process.
  2. Initial Position Error
    • The INI alarm in ZONCN VFDs typically indicates an initial position error. This may occur when the VFD fails to accurately detect the motor’s initial position at startup, preventing the control program from executing subsequent commands accurately. Initial position errors can arise from various factors, including incorrect motor parameter settings, current circuit faults, or signal transmission issues.
  3. Improper Motor Parameter Settings
    • The NZ200T VFD requires accurate setting of various motor parameters, such as rated voltage, rated current, and power factor. Inaccurate settings, particularly a low rated current setting, will prevent the VFD from effectively adjusting to the motor’s actual load conditions, thereby triggering the INI alarm.
  4. Current Matching Fault or Signal Transmission Issue
    • The NZ200T VFD operates in open-loop vector control mode, necessitating precise current detection for accurate model analysis. Damage to the current transformer or issues with the signal transmission lines, such as poor contact or signal interference, will affect the VFD’s accurate determination of the motor’s position, subsequently triggering the INI alarm.
  5. Control Mode Mismatch
    • The NZ200T VFD is designed for use with synchronous motors. When connected to a standard asynchronous motor or if the control mode is not correctly set, the INI alarm may also appear. This is because different types of motors exhibit distinct operational characteristics and control requirements, necessitating corresponding adjustments to the VFD’s control strategy based on the motor type.

II. Solutions

  1. Recheck Motor Parameters
    • Firstly, carefully verify the settings of all motor parameters, ensuring consistency with the data on the motor’s nameplate. Pay particular attention to key parameters such as rated current, which should be set according to the motor’s actual specifications to avoid INI alarms caused by improper parameter settings.
  2. Inspect Current Transformer and Signal Transmission Lines
    • Check the current transformer for damage or looseness, and replace it if necessary. Simultaneously, inspect the connection of the current transformer’s signal transmission lines to ensure good contact and absence of signal interference. If aged or damaged lines are found, promptly replace them with new ones.
  3. Adjust Control Mode
    • If the NZ200T VFD is connected to a standard asynchronous motor, adjust the control mode to V/F control mode. Refer to the VFD user manual for specific setting methods: set parameter P0-02 to 2 and P1-04 to 50 (V/F control). This allows the VFD to directly control the standard asynchronous motor by adjusting the frequency for speed regulation, without altering other parameters. Additionally, ensure that the VFD’s software version matches the motor type to avoid control issues due to software incompatibility.
  4. Seek Professional Technical Support
    • If the above methods fail to resolve the INI alarm issue, it is recommended to contact longi’s technical support team or professional maintenance personnel for fault troubleshooting and repair. When contacting technical support, provide a detailed description of the equipment’s operating environment, operation process, and alarm phenomena to enable technicians to quickly identify the problem and provide solutions.

In summary, the causes of INI alarms in the NZ200T VFD are diverse and require case-by-case investigation and resolution. By reasonably setting parameters, regularly inspecting equipment status, and seeking professional technical support, the incidence of INI alarms can be effectively reduced, ensuring stable equipment operation.

Posted on Leave a comment

User Guide for Great Inverter VC8000 Series

I. Operation Panel Functions and Instructions

The operation panel of the Great Inverter VC8000 series serves as the primary interface for user interaction with the inverter. It mainly consists of a display area and functional keys. Below are the main functions of the operation panel:

Schematic diagram of Greet VFD VC8000 series operation panel
  1. Display Area
    • Digital Display: Shows the current working status, frequency setting value, operating parameters, and other information of the inverter.
    • Function Indicators:
      • FWD/REV: Forward/Reverse indicator. Light off indicates forward operation, light on indicates reverse operation.
      • RUN: Running indicator. Light off indicates stop, light on indicates running.
      • LOCAL/REMOT: Command source indicator. Light off indicates panel control, light on indicates terminal control, flashing indicates communication control.
      • TUNE/TC: Tuning/Torque Control/Fault indicator. Light off indicates normal operation, light on indicates torque control, slow flashing indicates tuning status, fast flashing indicates fault status.
  2. Functional Keys
    • PRG/Programming: Enters or exits the menu for parameter modification.
    • ENTER/Confirm: Enters the menu, confirms parameter settings.
    • ▲ Increment: Increments data or function codes.
    • ▼ Decrement: Decrements data or function codes.
    • < Shift: Selects parameter modification digits and display content.
    • RUN/Run: Starts the inverter.
    • STOP/RESET: Stops or resets the inverter.
    • MF/Multi-Function: Multi-function selection key, with specific functions determined by the P7-01 function code.

II. Wiring Instructions for Terminal Start/Stop and Potentiometer Debugging

Gelite VFD VC8000 series terminal wiring diagram
  1. Wiring Instructions
    • Start/Stop Control Wiring:
      • Start Terminal: Typically, the start signal is connected to DI1 (or another specified digital input terminal) and configured as a forward running command (e.g., P4-00=1).
      • Stop Terminal: Connected to DI2 (or another specified digital input terminal) and configured as a fault reset or stop command (e.g., P4-01=9).
    • Potentiometer Debugging Wiring:
      • If an external potentiometer is used for frequency adjustment, connect +10V and GND to the power terminals of the potentiometer, and connect the center tap to AI1 (analog input 1).
  2. Parameter Settings
    • To meet control requirements, set the following parameters:
      • P4-00: Set DI1 as the forward running command (e.g., set to 1).
      • P4-01: Set DI2 function according to needs, typically as fault reset or stop command.
      • AI1-related Parameters: Ensure AI1 is configured to receive frequency settings (e.g., set P0-03 to AI1).
      • Other Necessary Parameters: Set relevant parameters in P0 group (basic function parameters), P2 group (vector control parameters), etc., according to specific needs.

III. Fault Code Analysis and Solutions

When faults occur in the Gelite Inverter VC8000 series, fault codes prefixed with “ERR” will be displayed. Below are analyses and solutions for some common fault codes:

  1. ERR01 – Inverter Unit Protection
    • Cause: May be due to inverter overheating, short circuit, or drive board failure.
    • Solution: Check if the inverter module is overheating, check for short circuits in the motor and cables, and if the problem persists, contact the manufacturer for repair.
  2. ERR02/ERR03/ERR04 – Acceleration/Deceleration/Constant Speed Overcurrent
    • Cause: Excessive motor load, short acceleration time setting, output short circuit, etc.
    • Solution: Check the motor load, appropriately extend the acceleration time, and check for short circuits in the output circuit.
  3. ERR05 – Constant Speed Overvoltage
    • Cause: Excessive power supply voltage, abnormal braking unit, etc.
    • Solution: Check the power supply voltage and confirm if the braking unit is working normally.
  4. ERR08 – Control Power Fault
    • Cause: Abnormal control power, such as unstable voltage or power cut.
    • Solution: Check the control power supply voltage and ensure stable power supply.
  5. ERR19 – Overload
    • Cause: Motor operating under overload for an extended period.
    • Solution: Reduce the motor load and check for abnormalities in the mechanical parts.

Note: The above are only analyses and solutions for some fault codes. During actual use, please refer to the specific fault code manual for operation. For faults that cannot be resolved, please promptly contact longi technical support.

Posted on Leave a comment

​User Guide for Fuling VFD BD330 Series Manual

Operation Panel Key Descriptions:

Functional description of Fuling inverter BD330 operation panel
  • PRGM/ESC: Program setting and exit key. PRGM is used to enter programming mode or set parameters, while ESC is used to exit the current setting or return to the previous menu.
  • FUNCTION/DATA: Function selection and data key. FUNCTION is used to enter the function selection interface, and DATA is used to modify data values during parameter setting.
  • FORWARD/REVERSE: Forward and reverse control key. Controls the forward or reverse rotation of the motor.
  • JOG/>>: Jog and page turning key. JOG is used for jog control, and >> may be used for page turning or increasing parameter values (specific functions may vary depending on the model).
  • RUN: Run key. Controls the startup of the VFD.
  • STOP/RST: Stop and reset key. STOP is used to stop the VFD operation, and RST is used to reset the VFD and clear fault states.
  • UP/DOWN: Up and down adjustment key. Used to increase or decrease values during parameter setting.

Terminal Start/Stop and Potentiometer Debugging Wiring Instructions:

Terminal Start/Stop:

  • Parameter Setting: Ensure parameter F0.02 is set to 1, selecting terminal control mode.
  • Wiring Instructions:
    • Connect the external start signal to the S1 terminal of the VFD.
    • Short-circuit the S1 terminal with the common terminal DCM to send a start signal, causing the VFD to begin operation.
    • Disconnect the short-circuit between S1 and DCM to send a stop signal, causing the VFD to stop operation.

Potentiometer Debugging:

  • Parameter Setting: Ensure parameter F0.03 is set to 1, selecting external potentiometer speed adjustment mode.
  • Wiring Instructions:
    • Connect the center tap (sliding contact) of the potentiometer to the AVI terminal of the VFD.
    • Connect the two ends of the potentiometer to the 10V (or similar positive power supply) and ACM (or similar common terminal) of the VFD, respectively.
    • Adjust the position of the potentiometer to change the voltage value of the AVI terminal, thereby controlling the output frequency of the VFD.
Fuling inverter BD330 wiring diagram

Fault Code Analysis and Solutions:

Fault Codes:

  • E001: DC bus fault. Possible causes include abnormal input power, faulty bus capacitors, etc. Solution: Check if the power input is normal, inspect the bus capacitors for damage, and replace if necessary.
  • E002: Acceleration overvoltage. Possible causes include excessively short acceleration time, sudden load changes, etc. Solution: Adjust the acceleration time and check for load stability.
  • E003: Constant speed overvoltage. Similar to E002 but occurs during constant speed operation. Solution is the same.
  • E004: Acceleration overcurrent. Possible causes include motor stall, excessive load, etc. Solution: Inspect the motor and load conditions, reduce the load, or optimize motor operating conditions.
  • E005: Deceleration overcurrent. Possible causes include excessively short deceleration time, large load inertia, etc. Solution: Adjust the deceleration time and consider using a braking unit and braking resistor.

Please note that the above content is based on the information you provided. During actual operation, please refer to the VFD manual and related materials. If you have any questions, please contact Longi Electromechanical’s technical support or professional maintenance personnel promptly.

Posted on Leave a comment

Fault Analysis and Resolution of ‘INH’ Alarm on Nidec Unidrive M300 and HS30 Servo Drive

Analysis and Solution for “INH” Alarm in Nidec Unidrive M300 and HS30 Series Servo Drive

Fault Analysis

INH' Alarm on Nidec Unidrive M300 and HS30 Servo Drive
  • Safety Input Trigger:
    • The Unidrive M300 and HS30 supports various safety functions, such as Safe Torque Off (STO). Activation of safety inputs, like STO signals, will place the drive in an inhibit state, preventing unintended motor rotation.
  • Control Parameter Settings:
    • Parameter P06.015 (Drive Enable) is one of the key control parameters, used to enable or disable drive output. When P06.015 is set to 0 (disabled), the drive will be in an inhibit state.
  • External Control Signals:
    • Incorrect configuration or faults in other external control signals, such as remote control signals, may also cause the drive to enter an inhibit state.
  • Drive Faults:
    • Although uncommon, internal drive faults or software issues may also result in “INH” alarms.

Solution Methods

Detailed description of STO function
  • Check Safety Inputs:
    • Confirm that all safety inputs (e.g., STO signals) are correctly connected and in the desired state. Check if external safety devices (e.g., emergency stop buttons) have been reset.
  • Verify Control Parameters:
    • Check the setting of parameter P06.015 through the drive’s Human Machine Interface (HMI) or configuration software. Ensure the parameter is set to 1 (enabled) to allow drive output.
  • Inspect External Control Signals:
    • Verify the wiring and logic of all external control signals (e.g., remote control signals). Ensure no erroneous signals are causing the drive to enter an inhibit state.
  • Restart the Drive:
    • After confirming all configurations are correct, attempt to restart the drive. Sometimes a simple restart can resolve issues due to software hangs or communication errors.
  • View Fault Records:
    • Use the drive’s fault diagnosis function to check for any other related fault records. These records may provide additional clues leading to the “INH” alarm.
  • Contact Technical Support:
    • If the above steps fail to resolve the issue, it is recommended to contact Nidec’s technical support team for further assistance.

Special Attention to Parameter P06.015

M300 servo wiring diagram and STO external wiring
  • Pre-modification Confirmation:
    • Before modifying P06.015 or any critical control parameters, ensure an understanding of the specific role and impact of the parameter, and consult relevant documentation or technical support.
  • Safe Operation:
    • Before making any modifications, ensure the drive and motor are in a safe state to avoid unexpected start-ups or damage to the equipment.

By following these steps, you should be able to diagnose and resolve the “INH” alarm issue on the Unidrive M300 servo drive. If the problem persists, consider seeking professional assistance from Longi Electromechanical.

Posted on Leave a comment

Theta VFD T8 Series User Guide

I. Procedure for Viewing and Modifying Function Codes on the T8 Series VFD Operator Panel

  1. Starting the Operator Panel:
    • After powering on the VFD, press the power button (labeled “POWER” or similar symbol) on the operator panel to activate it.
  2. Viewing and Modifying Function Codes:
    • Use the directional keys (↑↓←→) on the operator panel to select the desired function code for viewing or modification.
    • Press the “ENTER” key to enter edit mode, where you can input new parameter values using the numeric keys or view the current values.
    • After making changes, press “ENTER” again to confirm the modifications and exit edit mode.
    • Note: Access to some advanced function codes may require entering a password.
  3. Parameter Structure and Status Parameter Review and Setting:
    • VFD parameters are typically grouped, such as motor parameters (P0 group), control parameters (P1 group), and protection parameters (P2 group).
    • To review specific parameters, refer to the parameter table in the manual to find the corresponding parameter number (e.g., P0.01, P1.05) and parameter description.
    • Status parameters (e.g., current frequency, current, voltage) can be directly viewed through specific function codes, providing real-time insights into the VFD’s operating status.
Operation panel buttons and display instructions diagram

II. Explanation of Control Circuit Terminals and Wiring Methods for the T8 VFD

  1. Explanation of Control Circuit Terminals:
    • FWD/REV (Forward/Reverse Control Terminals): Connect to external buttons or switches to control the VFD’s forward and reverse rotation.
    • RUN/STOP (Run/Stop Control Terminals): Control the VFD’s start and stop functions.
    • AI1/AI2 (Analog Input Terminals): Receive analog signals from potentiometers, PLCs, etc., for frequency adjustment.
    • FAULT (Fault Output Terminal): Outputs a signal to external devices when the VFD detects a fault.
    • RUN (Run Indicator Light): Illuminates when the VFD is in the running state.
  2. Wiring Methods for the Control Circuit:
    • Connect the corresponding control signal wires to the designated terminals based on actual control requirements.
    • When using terminal start and potentiometer adjustment, ensure:
      • Analog input parameters are set correctly, including input type (voltage/current) and range.
      • The frequency setting method is selected as “Analog Input.”
      • Forward/reverse control parameters are set according to actual needs.

III. Explanation and Resolution of VFD Fault Codes

T8 inverter control circuit wiring diagram

Based on the specific instructions in the “Theta VFD T8 Series Manual,” here are some common fault codes and their resolutions:

  • OC (Overcurrent Fault): Check if the motor and load are excessively large, optimize motor parameters or load distribution; inspect motor insulation for integrity.
  • OV (Overvoltage Fault): Verify input voltage stability, use a voltage stabilizer if necessary; inspect power lines for abnormalities.
  • UV (Undervoltage Fault): Check the input power source for normalcy, troubleshoot power supply issues; inspect power lines for poor contact.
  • OH (Overheat Fault): Improve ventilation conditions, reduce ambient temperature; check for blocked heat sinks and clean dust inside the VFD.
  • EF (External Fault): Verify the normalcy of the external fault signal source; inspect the wiring of external devices for secure connections.

Please note that this content is a summary of the user guide based on select sections of the “Theta VFD T8 Series Manual.” Always refer to the original manual for detailed steps, precautions, and any additional information. For questions or further assistance, consult the manual or contact longi VFD’s technical support department.

Posted on Leave a comment

CHF100A Series Vector Universal VFD Usage Guide:Usage of Operation Panel, Startup and Debugging of VFD Terminal Mode, Analysis and Solutions for VFD Fault Codes

I. Operation Panel (Keyboard) Usage

The operation panel (keyboard) of the CHF100A Series Vector Universal VFD serves as the primary interface for VFD control and parameter setting. Here are the basic keyboard operation methods:

  1. Power-on and Display:
    • Upon connecting the VFD’s power supply, the display on the operation panel will illuminate, showing the current status or default parameters.
  2. Key Functions:
    • PRG: Programming key, used to enter or exit parameter setting mode.
    • SHIFT: Shift key, combined with numeric keys to select or modify high-order digits of parameters.
    • ESC: Escape key, used to exit the current setting or menu.
    • ENT: Enter key, used to confirm current settings or selections.
    • DATA: Data toggle key, used in some settings to switch between displaying different data items.
  3. Parameter Setting Procedure:
    • Press the PRG key to enter parameter setting mode.
    • Use arrow keys (if equipped) or SHIFT + numeric keys to select the desired parameter number.
    • Press the ENT key to enter the parameter’s setting interface.
    • Modify the parameter value using arrow keys or numeric keys.
    • Press the ENT key again to confirm the setting.
    • Press the ESC key to exit parameter setting mode.
INVT VFD CHF100A keyboard operation diagram

II. VFD Terminal Startup and Potentiometer Speed Regulation Wiring

  1. Terminal Startup Wiring:
    • Refer to the electrical wiring diagram in the manual (typically around page 75) to locate the input terminals related to startup (e.g., S1, S2).
    • Connect the external startup signal (e.g., pushbutton switch, PLC output) to the corresponding startup terminals.
    • Configure parameters as needed to ensure the VFD recognizes and responds to these startup signals.
  2. Potentiometer Speed Regulation Wiring:
    • Locate the analog input terminals (e.g., AI1, AI2) on the VFD, which receive analog signals from the potentiometer.
    • Connect the wiper of the potentiometer to the AI1 or AI2 terminal, and the fixed terminal to the common ground (e.g., COM).
    • Adjust the potentiometer to vary the output signal, thereby controlling the VFD’s output frequency and motor speed.
CHF100A inverter wiring diagram

III. VFD Fault Code Analysis and Troubleshooting

When a CHF100A Series VFD encounters a fault, it displays the corresponding fault code on its screen. Here are some common fault codes, their analysis, and troubleshooting methods:

  1. OC (Overcurrent):
    • Cause: Excessive motor or load, output short circuit, faulty cabling or wiring.
    • Solution: Check the motor and load to ensure they are within normal ranges; inspect cabling and wiring for correctness; increase deceleration time or reduce acceleration current.
  2. OV (Overvoltage):
    • Cause: Excessive input voltage, inadequate deceleration time.
    • Solution: Verify that the input voltage meets specifications; increase deceleration time.
  3. UV (Undervoltage):
    • Cause: Insufficient input voltage, power supply failure.
    • Solution: Check the power supply voltage for normalcy; inspect power lines and fuses for integrity.
  4. OH (Overheating):
    • Cause: Elevated ambient temperature, poor ventilation, clogged heat sink.
    • Solution: Improve ventilation to enhance cooling, reduce ambient temperature; clean dust and debris from the heat sink.

Please note that these are exemplary analyses and solutions. Always refer to actual circumstances and detailed instructions in the manual. When dealing with any electrical fault, adhere strictly to safety procedures and consider power disconnection to avoid electrical shock risks.

Posted on Leave a comment

User Guide for Delta VFD MS300 Series: Operation Panel Usage, Startup and Debugging of VFD Terminal Mode, Analysis and Solutions for VFD Fault Codes

Delta VFD MS300 Series User Guide

I. Operating Panel Usage

  1. Power-On and Display
    • Upon powering on, the VFD automatically conducts a self-test and then enters standby mode. The display on the operating panel shows the current status and parameters.
  2. Function Key Operations
    • RUN/STOP Button: Press RUN to start the VFD and STOP to halt its operation.
    • Direction Selection (FWD/REV): Used to select forward or reverse rotation for the motor.
    • Frequency Adjustment Keys: Adjust the output frequency using the up and down arrow keys. In automatic mode, these keys may be disabled.
    • MENU Button: Enters the main menu, allowing access and modification of various settings.
    • ENTER Button: Confirms the current selection or enters setup mode.
    • ESC Button: Exits the current setup or returns to the previous menu level.
  3. Parameter Settings
    • Navigate to the parameter settings menu, use the arrow keys to select the parameter to modify, press ENTER to enter edit mode, adjust the parameter value with the up/down arrow keys, and confirm with ENTER.
digital keypad KPC-CC01 Functional Description

II. Wiring for Terminal Start and Potentiometer Speed Control

  1. Starting Terminal Wiring
    • Forward Start (FWD): Connect the external control signal to the VFD’s forward start terminal (e.g., FWD).
    • Reverse Start (REV): For reverse rotation, connect the signal to the reverse start terminal (e.g., REV). Typically, forward and reverse cannot be activated simultaneously.
    • Stop: Connect the stop signal to the VFD’s stop terminal to interrupt output.
  2. Potentiometer Speed Control Wiring
    • Connect a potentiometer to the analog input terminal (e.g., AVI or ACI) of the VFD. Attach the two fixed ends of the potentiometer to the VFD’s power supply (e.g., +10V and GND), and connect the sliding end to the VFD’s analog input terminal.
    • According to the parameter settings in the manual (e.g., parameter 03-00), configure the relevant parameter to “frequency command” so that the VFD can adjust its output frequency based on the voltage signal from the potentiometer.
MS300 vfd standard wiring diagram

III. Parameter Configuration

  1. Basic Parameter Settings
    • Maximum Operating Frequency (Parameter 01-00): Set the maximum output frequency based on the motor specifications.
    • Acceleration/Deceleration Time (Parameters 01-12 through 01-19): Configure appropriate acceleration and deceleration times to avoid mechanical shocks and overcurrents, tailored to your application’s needs.
    • Starting Frequency (Parameter 01-09): Set the initial frequency at startup to mitigate starting surges.
  2. Input/Output Terminal Configuration
    • Multi-function Input Terminals (Parameters 02-01 through 02-07): Assign each terminal’s function according to your control requirements, such as start, stop, and direction control.
    • Analog Input Configuration (e.g., Parameter 03-00): Specify the function of AVI, ACI, and other analog input terminals, such as frequency reference or torque control.
  3. Protection Parameters
    • Overcurrent Protection (Parameters 06-03 through 06-04): Configure the overcurrent protection threshold and duration to safeguard the motor and VFD.
    • Overvoltage/Undervoltage Protection (Parameters 06-00, 06-01): Set voltage protection thresholds to ensure stable operation amidst voltage fluctuations.

IV. Fault Code Analysis and Resolution

  1. Overcurrent (OC)
    • Cause: Excessive motor load, too short acceleration time, motor malfunction, etc.
    • Resolution: Inspect the motor and load conditions, adjust the acceleration time, and check for motor damage.
  2. Overvoltage (OV)
    • Cause: Excessive input voltage, too short deceleration time, insufficient braking resistance, etc.
    • Resolution: Verify the input voltage, adjust the deceleration time, and consider adding braking resistance.
  3. Undervoltage (LV)
    • Cause: Low input voltage, voltage drop due to long power lines, etc.
    • Resolution: Check the power supply voltage and optimize power line layout.
  4. Overheating (OH)
    • Cause: High ambient temperature, poor heat dissipation, excessive load, etc.
    • Resolution: Improve cooling conditions, reduce the load, and inspect and clean the cooling fan.
  5. Communication Fault
    • Cause: Communication line issues, incorrect parameter settings, address conflicts, etc.
    • Resolution: Examine the communication lines, verify communication parameter settings, and ensure unique device addresses.

By following this guide, you can effectively use and maintain the Delta VFD MS300 series, ensuring stable operation and optimal performance.

Posted on Leave a comment

JACT AT500 Inverter Operation Guide and Fault Handling Summary

AT500 Inverter Operation Guide and Fault Handling Summary


I. AT500 Inverter Operation Panel Usage

  1. Operation Panel Layout and Indicator Description:
    • Introduces the display, buttons (RUN, STOP/RES, MK, Λ, V, >>, etc.) on the operation panel and their functions.
    • Explains the meanings of various indicators (Run, Alm, Hz, A, V, %, rpm, F/R, etc.).
  2. Menu and Parameter Settings:
    • Describes the three-level menu mode (function parameter group, function code, function code modification) and its operation method.
    • Elaborates on how to view and modify various inverter parameters through the operation panel.
  3. Operation Mode Control:
    • Introduces starting the inverter via the RUN button and stopping it via the STOP/RES button.
    • Explains the jog operation function and its debugging applications.
Function diagram of AT500 inverter operation panel buttons

II. Terminal Control and External Potentiometer Debugging Mode Setup

  1. Terminal Control Setup:
    • Guides users to enter the F0 parameter group and set F0.02 to 1 to enable terminal control.
    • Demonstrates how to assign functions to each input terminal through the F2 parameter group and explains wiring requirements.
  2. External Potentiometer Debugging Mode:
    • Teaches users to set F0.03 or F0.04 to AI3 (keyboard potentiometer) to adjust the output frequency by rotating the potentiometer knob.
JACT AT500 inverter wiring diagram

III. Inverter Fault Code Classification and Troubleshooting Methods

  1. Overcurrent Faults (Err02-Err04):
    • Lists possible causes (output circuit short circuit, too short acceleration/deceleration time, etc.).
    • Provides solutions (check output circuit, adjust acceleration/deceleration time, etc.).
  2. Overvoltage Faults (Err05-Err07):
    • Analyzes fault causes (excessively high input voltage, external force during deceleration, etc.).
    • Offers remedies (adjust input voltage, eliminate external force during deceleration, etc.).
  3. Undervoltage Fault (Err09):
    • Describes fault causes (instantaneous power failure, low input voltage, etc.).
    • Suggests solutions (check input power supply, adjust voltage range, etc.).
  4. Overload Faults (Err10-Err11):
    • Indicates faults may be caused by excessive load, motor stall, etc.
    • Proposes reducing the load, checking the motor and mechanical conditions, etc.
  5. Input/Output Phase Loss Faults (Err12-Err13):
    • Analyzes fault causes (input power phase loss, faulty output wires or motor, etc.).
    • Offers advice on checking power and motor, troubleshooting peripheral faults, etc.
  6. Module Overheating Fault (Err14):
    • Explains fault causes (high ambient temperature, blocked air ducts, etc.).
    • Emphasizes the importance of reducing ambient temperature, cleaning air ducts, replacing fans, etc.
  7. Communication Fault (Err16):
    • Mentions possible causes (incorrect communication parameter settings, faulty communication cables, etc.).
    • Suggests checking communication parameters, cables, and the host computer.