Posted on Leave a comment

User Manual Guide for the Fuji High Voltage Inverter FRENIC4600FM6e Series

Introduction

The FRENIC4600FM6e series high voltage inverter from Fuji Electric is a device specifically designed to drive high-voltage motors, widely used in various industrial applications such as water pumps, fans, compressors, and more. This inverter not only provides efficient motor control but also offers a wealth of features and flexible configuration options. To ensure users can fully utilize the inverter’s functions, it is essential to understand and operate the user manual correctly. This article provides a detailed guide to using the FRENIC4600FM6e Series Inverter User Manual, covering wiring, parameter settings, control modes, fault diagnostics, parameter backups, and more, helping users operate and maintain the device more effectively.

FRENIC4600FM6e Structure Diagram

1. Inverter Wiring Guide

Wiring the inverter correctly is fundamental to ensuring its proper operation. For the FRENIC4600FM6e Series, users need to properly connect the power supply, motor, and various control terminals. The following are key points for wiring:

  1. Power Input: The inverter requires a three-phase high voltage input, commonly 3φAC 3.0kV, 3.3kV, 6kV, etc. When connecting the power supply, users must ensure that the input voltage matches the inverter’s rated voltage.
  2. Motor Connection: The inverter outputs three-phase voltage to the motor terminals U, V, and W, driving the motor. When wiring, it is important to ensure that the motor’s rated voltage matches the inverter’s output voltage.
  3. Control Terminals:
    • DI Terminals (Digital Input): Used for control signals such as start/stop, forward/reverse, etc.
    • DO Terminals (Digital Output): Outputs operational status, fault information, and more.
    • AI Terminals (Analog Input): Used for analog frequency command input signals.
    • AO Terminals (Analog Output): Outputs analog frequency, current, and other data.

When wiring, ensure all terminals are securely connected, and pay attention to the specific function of each terminal to avoid miswiring, which could lead to device failure.

RRENIC4600 version status display

2. Parameter Settings and Initialization

  1. Basic Parameter Settings
    • No.1~12: Set operating frequency, output voltage, and other parameters. Users can adjust these settings based on the motor and load requirements to ensure the device operates under optimal conditions.
    • No.28~40: Set acceleration and deceleration times, determining the smoothness of motor start and stop.
    • No.173: Set the function of external terminals (such as DI terminals) for start/stop, forward/reverse, and other control signals.
  2. Initialization Settings The FRENIC4600FM6e Series offers a factory reset function. Users can restore the inverter to its default settings using No.200, which resets the inverter’s parameters to their factory default configuration. This operation is useful when resetting parameters or correcting configuration errors.
  3. Parameter Backup Before performing initialization or other operations, it is advisable to back up the parameters to prevent losing important custom configurations. Users can back up and restore the parameter settings using Loader software. The steps are as follows:
    • Connect Loader to the inverter.
    • In Loader, select the option to back up current settings.
    • Choose a file location for storing the backup file. The backup file can be saved on a computer and used for future recovery operations.
    • To restore the parameters, load the backup file and restore the previous configuration.
RRENIC4600 parameter settings

3. Control Modes and Password Settings

The FRENIC4600FM6e supports multiple control modes, including panel control and external terminal control. Users can select the appropriate control mode based on their needs.

  1. Panel Control vs. External Terminal Control
    • Panel Control: Users can directly set frequency, start/stop the motor, and more via the LCD panel.
    • External Terminal Control: Through DI terminals, external control signals can start or stop the inverter. Users need to configure the terminal functions via No.173 to ensure proper signal transmission.
  2. Password Protection and Parameter Access Restrictions To prevent unauthorized operations, the inverter supports password protection and parameter access restrictions:
    • No.12: Set administrator and user passwords. Different passwords provide different access levels—administrators can modify all parameters, while users are restricted.
    • No.13~14: Set parameter access restrictions, preventing critical parameters from being accidentally changed or modified by unauthorized personnel.

By using password protection and access restrictions, users can effectively safeguard the operation and configuration of the inverter, preventing operational errors or unauthorized modifications.

FRENIC4600FM6e Structure Diagram

4. Fault Diagnostics and Solutions

During operation of the FRENIC4600FM6e Series, users may encounter various faults. The inverter provides LCD panel or fault codes to offer fault information, helping users quickly locate the problem.

  1. Common Fault Codes and Solutions:
    • E.F. Overload Fault: Check if the motor load is too high. Avoid overload conditions.
    • E.U. Phase Loss Fault: Check the power supply wiring to ensure there is no missing phase.
    • E.O. High Voltage Fault: Adjust the output voltage settings and check for motor problems.
    • E.C. Low Battery Voltage: Replace the internal battery of the inverter.
    • E.P. Over Temperature Fault: Check if the cooling system is working properly and clean the heat sinks.
  2. Troubleshooting Steps:
    • Check Power Supply and Cables: Ensure the power supply is stable, and the cable connections are secure and undamaged.
    • Check Motor Load: Ensure the motor load does not exceed the rated capacity.
    • Check Cooling System: Clean fans and heat sinks regularly to ensure the inverter operates within the appropriate temperature range.
RRENIC4600 shutdown status

5. Summary

The FRENIC4600FM6e High Voltage Inverter is a high-performance motor control device equipped with various features such as parameter settings, control modes, password protection, fault diagnostics, and more. By understanding and correctly operating the functions outlined in the user manual, users can effectively configure, operate, and maintain the device. Whether backing up parameters using Loader, setting password protection, diagnosing faults, or configuring control modes, making proper use of these functions ensures long-term stable operation, improved efficiency, and enhanced safety.

This guide aims to help users better understand and use the FRENIC4600FM6e Series Inverter, maximizing its performance advantages in real-world applications.

Posted on Leave a comment

Analysis and Solutions for Siemens S120/S150 Drive F07802 Fault Code

In Siemens SINAMICS S120 and S150 series drives, the F07802 fault code indicates that the rectifier unit or power module is not ready. This fault typically occurs during the drive’s startup process, signaling that the drive has not received a readiness feedback from the power module within the expected time frame. Understanding the meaning of this fault and its solutions is crucial for ensuring the drive operates correctly.

F07802 actual display

1. Fault Meaning

The F07802 fault code signifies that after the internal enable command, the drive has not received a readiness signal from the rectifier or power module. Possible causes include:

  • Short Monitoring Time: The drive’s waiting period for the power module to become ready is insufficient, leading to a timeout.
  • Absence of DC Bus Voltage: The DC bus voltage has not been established, preventing the power module from starting.
  • Faulty Rectifier or Power Module: The associated components have hardware faults, rendering them inoperative.
  • Incorrect Input Voltage Settings: The drive’s input voltage parameters are misconfigured, causing the power module to fail to start.
CU320-2

2. Fault Diagnosis and Solutions

To address the above potential causes, consider the following steps:

  • Extend Monitoring Time (P0857): In the drive’s parameter settings, appropriately increase the monitoring time for the power module to ensure there is sufficient time during startup for the power module to become ready.
  • Check DC Bus Voltage: Use a multimeter to measure the DC bus voltage, ensuring it is within the normal range. If the voltage is abnormal, inspect the DC bus wiring and connections for looseness or poor contact.
  • Inspect Rectifier and Power Module: Examine the status indicators of the relevant components to confirm they are functioning correctly. If indicators are abnormal or absent, the components may need replacement.
  • Verify Input Voltage Settings (P0210): In the drive’s parameter settings, confirm that the input voltage parameters match the actual supply voltage. Mismatched settings can prevent the power module from starting.

3. Preventive Measures

To prevent the occurrence of the F07802 fault, it is advisable to implement the following measures:

  • Regular Maintenance: Periodically inspect the drive’s electrical connections and component statuses to promptly identify and address potential issues.
  • Correct Parameter Configuration: Ensure all parameters, especially those related to voltage and monitoring time, are correctly configured in the drive’s settings.
  • Stable Power Supply: Maintain a stable power supply system for the drive, avoiding voltage fluctuations or power outages.
  • Operator Training: Provide regular training for operators to enhance their ability to identify and resolve drive faults.
F07802 processing method

4. Conclusion

The F07802 fault code is a common startup fault in Siemens SINAMICS S120 and S150 series drives. By appropriately extending the monitoring time, checking the DC bus voltage, verifying input voltage settings, and performing regular maintenance, this fault can be effectively prevented and resolved. During the troubleshooting process, always adhere to electrical safety protocols to ensure the safety of personnel and equipment.

Posted on Leave a comment

Schneider Inverter Error Code 0004Hex and Safety Function Error: What Is the Problem and How to Solve It?

During operation, Schneider inverters may display a “Safety Function Error” along with the error code “0004Hex.” This error code can cause confusion for many technicians. This article will provide a detailed explanation of the issue, common solutions, and possible hardware failure causes.

 Error Code 0004Hex

1. Meaning of Error Code 0004Hex

In Schneider inverter manuals, error code “0004Hex” typically indicates a “Safety Function Error.” This type of fault is often related to safety functions inside or outside the inverter, such as emergency stop, door protection, emergency braking, and other safety features. In this case, the inverter may disable or limit certain functions to ensure the safety of both equipment and personnel.

A “Safety Function Error” does not necessarily mean the inverter has a hardware failure. It may be caused by improper configuration, wiring errors, or the triggering of an external safety system. The specific cause of the fault needs to be determined by checking the inverter’s settings and the configuration of external safety circuits.

2. Meaning of Safety Function Error and Solutions

1. Parameter Issues

The first step is to verify if the error is due to incorrect configuration of the inverter’s safety function parameters. These parameters control how the inverter responds to safety features, such as emergency stops, door switches, etc. If these parameters are not configured correctly or are set to inappropriate values, the inverter may trigger the “Safety Function Error.” To resolve this issue, check and adjust the relevant safety parameters.

Common safety functions in Schneider inverters include:

  • SS1: Safety Stop
  • SS2: Safety Stop 2
  • SLS: Safe Limited Speed
  • SIL: Safety Integrated
  • SFC: Safety Function Control

These safety functions can typically be found in the parameter setting menu. For example, if the “Safety Stop” (SS1) function is not correctly enabled, or the safety stop time is set too short, it may trigger this error.

Solution:

  1. Enter the inverter’s programming mode.
  2. Navigate to the safety function parameters in the menu.
  3. Ensure that the relevant safety functions are enabled and that the parameters are set appropriately.
  4. Adjust the parameters and save the configuration.
2. External Terminal Wiring Issues

Another potential cause is an issue with external safety terminal wiring. Inverters often connect to external safety devices, such as emergency stop switches and door switches, through terminals. If the wiring to these external devices is faulty, the inverter may incorrectly interpret it as a safety issue and display the error.

To troubleshoot terminal wiring issues, first ensure that the relevant safety terminals are correctly connected and that the safety signals are being read properly. Common safety terminals and their corresponding functions are:

  • Terminal 10 (STO): Safe Stop
  • Terminal 11 (SS1): Safety Stop
  • Terminal 12 (SLS): Safe Limited Speed

When inspecting these terminals, pay special attention to:

  1. Terminal Short Circuits: If there is a short circuit between terminals, the inverter will consider the safety function to have been triggered, resulting in the error.
  2. Loose or Incorrect Wiring: Loose or incorrectly wired connections can cause the inverter to fail in detecting safety signals.

Steps to troubleshoot:

  1. Ensure that the wiring to terminals 10, 11, 12, etc., is secure and there are no short circuits.
  2. To test terminal functions, you can temporarily short-circuit certain terminals to check whether the inverter responds correctly.
  3. Clear the fault and restart the inverter to check if the safety function error persists.
3. Mainboard or Drive Board Hardware Faults

If the above methods do not resolve the issue, hardware failure could be the cause of the “Safety Function Error.” There may be issues with the circuits on the mainboard or drive board that are responsible for detecting safety functions. If these circuits fail (e.g., due to sensor damage, poor contact, etc.), the inverter may fail to properly recognize safety signals and trigger the error.

In this case, the solution includes:

  1. Inspecting the Hardware Circuits: Check the circuits on the mainboard or drive board related to safety functions, including sensors, wiring, and connectors, to ensure they are not damaged or loose.
  2. Replacing Faulty Components: If a component on the circuit board is damaged, try replacing it. For severe issues with the mainboard or drive board, replacing the entire board may be necessary.
  3. Conducting Board Diagnostics: Use Schneider’s diagnostic tools to check if the board is functioning correctly, especially the parts related to safety functions.

If hardware failure is confirmed and the board cannot be repaired, it is best to contact Schneider’s after-sales service for further assistance or to replace the parts.

ATV610

3. Conclusion

When a Schneider inverter displays a “Safety Function Error” and the error code “0004Hex,” the first step is to check for parameter configuration errors and external terminal wiring issues. If these checks do not resolve the problem, hardware failure in the mainboard or drive board may be the cause. Depending on the situation, solutions may include adjusting parameters, inspecting wiring, short-circuiting terminals, or replacing faulty hardware.

With thorough troubleshooting and proper handling, most “Safety Function Errors” can be resolved. If the issue persists, it is recommended to contact Schneider’s technical support for professional assistance.

Posted on Leave a comment

How to Handle BLF Fault in Schneider ATV71 Series Inverters?

1. Understanding the BLF Fault

The BLF (Brake Lift Failure) fault in Schneider ATV71 inverters is typically related to brake control logic. This fault indicates that the inverter has failed to reach the required current to release the brake. In other words, the inverter may not be triggering the brake release correctly, or the actual current is not reaching the preset release threshold.

BLF Fault

Possible causes of the BLF fault include:

  • Incorrect brake connection: There may be wiring issues or poor contact between the motor and brake.
  • Motor winding problems: Damaged motor windings could prevent the brake from being released properly.
  • Improper parameter settings: The inverter’s brake release current or brake frequency threshold parameters (such as Ibr, Ird, bEn, etc.) may not be correctly configured.
  • Hardware failure: The brake relay, drive circuit, or the brake itself may be faulty.

2. Resolving the BLF Fault Through Parameter Adjustment

If the BLF fault is caused by incorrect parameter settings, follow these steps to adjust them:

  1. Check and adjust the brake release current parameters
    • Access the inverter’s parameter settings and check Ibr (Brake Release Current – Forward) and Ird (Brake Release Current – Reverse).
    • These parameters define the current required to release the brake. If set too low, the brake may not disengage properly. Adjust these parameters within the appropriate range (0 to 1.32 In).
  2. Adjust the brake closing frequency
    • The bEn (Brake Closing Frequency) parameter controls the frequency threshold at which the brake engages. Ensure this parameter is correctly set, preferably to Auto Mode or a manually defined frequency (0–10Hz).
  3. Check the brake release time
    • Extend the brt (Brake Release Time) if necessary to ensure the brake has enough time to disengage.
  4. Verify zero-speed brake control
    • Ensure that bECd (Zero Speed Brake) is not mistakenly set to No, as this can affect the brake release logic.
  5. Confirm the motor control type
    • Go to the [Motor Control Type] (Ctt) parameter and ensure that the inverter’s control mode is appropriate for the motor and braking logic, especially for lifting applications.

3. Resolving BLF Faults Caused by Hardware Issues

If adjusting the parameters does not resolve the BLF fault, it may be caused by hardware failures. Follow these troubleshooting steps:

  1. Check motor and inverter connections
    • Turn off the power and inspect the motor wiring to ensure proper connections and no loose terminals.
    • Use a multimeter to measure the motor winding resistance to confirm there is no damage or short circuit.
  2. Inspect the brake relay
    • Use a multimeter to check the relay contacts for proper switching and continuity.
  3. Check the brake solenoid
    • If the motor uses an electromagnetic brake, verify that the brake is functioning correctly. Replace the brake coil if necessary.
  4. Examine the drive circuit
    • If there is a problem with the control board, such as a faulty relay drive circuit, the inverter’s control board may need repair or replacement.
  5. Replace damaged components
    • If any damaged components are identified, such as the brake system, control relays, or internal inverter parts, replace them accordingly.
ATV71 physical picture

4. Conclusion

The BLF fault in Schneider ATV71 inverters is mainly related to brake control and may be caused by incorrect parameter settings or hardware malfunctions. Adjusting parameters such as Ibr, Ird, bEn can resolve software-related issues, while hardware problems require thorough inspection of the motor, relays, brake system, and control circuits. A systematic troubleshooting approach will help pinpoint the root cause efficiently and ensure a proper repair solution.

Posted on Leave a comment

Analysis of the Causes and Solutions for PWM Fiber Optic Connection Errors and Motor Overload in Fuji High Voltage Inverter FRENIC 4600 Series

Introduction

The Fuji FRENIC 4600 series high-voltage inverters are widely used in industrial drive systems, playing a vital role in driving large power equipment due to their stable performance and efficient control capabilities. However, after long-term use or idle periods, inverters may experience some faults, particularly in cases of electrical connection issues or abnormal motor loads. Common faults include PWM fiber optic connection errors and motor overload alarms. These faults are often interrelated, and it is necessary to perform a thorough analysis to determine the root cause of the failures and take corrective actions.

This article will analyze the relationship between PWM fiber optic connection errors and motor overload faults, explore the fundamental causes behind these issues, and propose targeted solutions based on systematic troubleshooting methods.

FRENIC 4600 FM6e

1. Causes and Analysis of PWM Fiber Optic Connection Errors

1.1 Fiber Optic Connection Issues

PWM (Pulse Width Modulation) fiber optic connections are a critical path for signal transmission between the inverter’s internal control system and external devices. When there is instability or loss of the fiber optic connection, the inverter may fail to receive or transmit control signals correctly. Common fiber optic connection issues include:

  • Loose or Damaged Fiber Optic Connectors: Over time, after prolonged use or idle periods, the fiber optic connectors may become loose, oxidized, or physically damaged, resulting in unstable signal transmission.
  • Pollution or Obstruction of Fiber Optic Connectors: Dust, oil, and other substances can accumulate on fiber optic connectors, impacting the quality of signal transmission, which may lead to connection errors.
  • Electromagnetic Interference (EMI): In environments with strong electromagnetic interference, signals can be disrupted, causing errors in fiber optic communication.

When these issues occur, the inverter’s signal transmission is interrupted or distorted, preventing the control system from regulating the motor’s operation properly.

Inverter output breaker answer

1.2 Triggering Mechanism of Motor Overload

When a fiber optic connection error occurs, the inverter may fail to obtain accurate motor status information or adjust the output frequency correctly. Without proper regulation of the motor load and operating conditions, the inverter may generate unstable power or current output, resulting in motor overload.

  • Loss of Control Signals: With a fiber optic connection error, the inverter cannot receive feedback from the motor, leading to an inability to regulate the motor’s load properly, which causes excessive current and triggers the overload alarm.
  • Frequency Regulation Failure: If the inverter cannot correctly adjust the output frequency due to fiber optic signal loss, the motor may run at non-optimal settings for extended periods, leading to overload.
  • Excessive Inrush Current During Startup: Without proper communication through fiber optic signals, the inverter may fail to handle the large inrush current during motor startup, resulting in an overload fault.

2. Correlation Between Fiber Optic Connection Errors and Motor Overload

From the fault diagnosis experience, PWM fiber optic connection errors and motor overload are closely related. Fiber optic connection errors typically serve as the root cause, while motor overload is a direct consequence of this issue.

  1. Protection Mechanism Triggered by Signal Loss: If the inverter cannot obtain motor feedback due to a fiber optic connection issue, the system may enter a “protection mode” and activate overload protection. This prevents the system from operating normally, resulting in excessive current flowing through the motor and triggering an overload alarm.
  2. Incorrect Motor Load Detection: Without proper fiber optic feedback, the inverter may misinterpret the motor load, causing the system to falsely detect an overload condition and activate the protection mechanism unnecessarily.
Motor overload

3. Fault Analysis and Troubleshooting Steps

3.1 Power Off and Reset

Since a fiber optic connection issue can trigger the inverter’s internal protection mechanism, the first step is to perform a power off and reset operation. Disconnect the power, ensuring the system is completely powered off, then execute the inverter’s reset procedure to clear all alarm information.

3.2 Inspect Fiber Optic Connections

After the reset, the next step is to inspect the PWM fiber optic connections for any issues such as looseness, damage, or contamination. Prolonged use or idle periods may cause degradation in fiber optic connectors. Follow these steps to check the fiber optic connections:

  • Check the Connectors and Cables: Ensure that the fiber optic connectors are secure, free from oxidation, and that the cables are not damaged or broken.
  • Clean the Fiber Optic Connectors: Use cleaning tools to remove any dust or oil contaminants from the fiber optic connectors to ensure proper signal transmission.
  • Replace Fiber Optic Cables: If the fiber optic cables are damaged, they should be replaced immediately.

3.3 Inspect the Motor and Load

Once the fiber optic connection issue is resolved, inspect the motor and load for potential faults. Motor overload may also be caused by mechanical issues with the motor or abnormal load conditions. Check the motor’s condition and verify that the load is within normal operating limits:

  • Check the Motor Condition: Use a multimeter to test the motor’s winding resistance to ensure there are no short circuits or grounding faults.
  • Check the Load Equipment: Ensure that the load connected to the motor is not too heavy or jammed. Examine the mechanical components for signs of resistance or abnormal wear.

3.4 Check Inverter Control Parameters

If no issues are found with the motor or load, the next step is to check the inverter’s control parameters. Ensure that the overload protection and current limit settings on the inverter are correct and aligned with the motor’s rated specifications:

  • Adjust Overload Protection Settings: Modify the inverter’s overload protection parameters according to the motor’s rated power and load requirements to avoid overly sensitive triggering of the protection mechanism.
  • Set Frequency Limits: Verify that the inverter’s frequency settings are within the motor’s maximum operating frequency range to prevent overload conditions caused by excessive frequency.

3.5 Inspect Current Detection Circuit

Finally, check the inverter’s current detection circuit for functionality. A faulty current sensor or circuit could lead to incorrect readings, resulting in false overload alarms. Use the inverter’s diagnostic functions to inspect the current sensor and replace or repair it as needed.

Optical link error

4. Conclusion

The PWM fiber optic connection error and motor overload fault in the Fuji FRENIC 4600 series inverter are often interrelated, with the fiber optic connection issue serving as the root cause and the motor overload being a direct consequence. Fiber optic connection errors result in signal loss, which prevents the inverter from properly regulating the motor load and frequency, triggering an overload alarm. By systematically checking fiber optic connections, motor conditions, inverter parameters, and current detection circuits, these faults can be resolved, and the system can return to normal operation. Throughout the troubleshooting process, it is essential to prioritize high-voltage safety and follow proper electrical safety protocols to ensure the safety of both the equipment and personnel.

Posted on Leave a comment

Analysis and Solution for Ground Fault (fault 2330) in ABB ACS880 Inverter

I. Introduction

The ABB ACS880 inverter is widely used in industrial control systems due to its high performance and reliability. However, during practical applications, the inverter may encounter various faults, among which the ground fault (fault 2330) is a relatively common and severe one. This article provides an in-depth analysis of the mechanism behind the ground fault in ABB ACS880 inverters and proposes corresponding solutions.

II. Mechanism Analysis of Ground Fault in ABB ACS880 Inverter

1. The Nature of Ground Fault

A ground fault in the ABB ACS880 inverter manifests as the fault code 2330, essentially a serious overcurrent fault. When the inverter detects grounding issues in the motor or motor cables, such as three-phase imbalance, it triggers the ground fault protection mechanism. This fault can not only damage IGBT modules or drive circuits but also have a significant impact on the entire electrical system.

2. Causes of Ground Fault

(1) Damaged Motor or Motor Cables: Insulation damage, aging, or loose connections in motor windings or cables can lead to current leakage to ground, triggering a ground fault.
(2) External Factors: External factors such as lightning strikes or overvoltage can also cause insulation breakdown in motors or cables, resulting in ground faults.
(3) Hardware Faults: Faults in IGBT modules or drive circuits can also cause the inverter to falsely report a ground fault.

3. Detection Principle of Ground Fault

The ABB ACS880 inverter detects ground faults by monitoring the imbalance of motor currents. When the imbalance of the three-phase currents exceeds the preset value, the inverter identifies it as a ground fault and immediately stops output to protect the motor and the inverter itself.

III. General Solutions for Ground Fault

1. Hardware Inspection and Repair

(1) Check Motor and Cables: First, inspect the motor and cables for insulation damage, aging, or loose connections. If any issues are found, repair or replace them promptly.
(2) Check Inverter Hardware: Inspect the IGBT modules, drive circuits, and other components inside the inverter to confirm the absence of damage or abnormalities. If necessary, contact professional technicians for repairs.

2. Parameter Adjustment and Testing

After confirming that the hardware is functioning correctly, attempt to resolve the issue by adjusting relevant inverter parameters. However, it should be noted that parameter adjustments should be made under the guidance of professional technicians to avoid causing larger faults due to misoperation.

IV. Shielding Method for Ground Fault in ACS880 Inverter under Normal Hardware Conditions

1. Setting of Parameter 31.20

According to the user manual of the ABB ACS880 inverter, parameter 31.20 is used to select the inverter’s response when a ground fault is detected. Setting it to 0 can shield the ground fault alarm. However, it should be noted that shielding the ground fault alarm is only applicable when the hardware is confirmed to be functioning correctly. If there are hardware issues and the alarm is blindly shielded, it may lead to further damage to the inverter or motor.

2. Operating Steps

(1) Enter the Parameter Settings Interface: Access the parameter settings interface through the inverter’s control panel or professional debugging software.
(2) Locate Parameter 31.20: Find parameter 31.20 in the parameter list and set its value to 0.
(3) Save Settings and Restart Inverter: After setting is complete, save the parameter settings and restart the inverter to make the changes effective.

3. Precautions

(1) Confirm Hardware Functionality: Before shielding the ground fault alarm, ensure that the motor, cables, and inverter hardware are all functioning correctly.
(2) Monitor Operating Status: After shielding the alarm, closely monitor the inverter’s operating status and promptly address any abnormalities.
(3) Regular Maintenance Checks: Regularly perform maintenance checks on the inverter to detect and address potential issues in a timely manner, preventing faults from occurring.

V. Conclusion

When the ABB ACS880 inverter encounters a ground fault (fault 2330), hardware inspection and repair should be carried out first, followed by consideration of resolving the issue through parameter adjustments. Under normal hardware conditions, the ground fault alarm can be shielded by setting parameter 31.20 to 0. However, it should be noted that shielding the alarm is only applicable when the hardware is confirmed to be functioning correctly, and the inverter’s operating status should be closely monitored to avoid causing larger faults due to misoperation or neglecting potential issues. Through scientific and rational fault analysis and solutions, the stable operation and extended service life of the ABB ACS880 inverter can be effectively ensured.

Posted on Leave a comment

HOLIP Frequency Converter HLP-SV Series User Manual Operation Guide

I. Introduction to Operation Panel Functions and Parameter Settings

Introduction to Operation Panel Functions

The operation panel (LCP operator) of the HOLIP HLP-SV series frequency converter provides an intuitive interface for users to set parameters and monitor operations. The operation panel mainly includes a display screen, function keys, navigation keys, potentiometers, and indicators. The display screen shows current parameters, converter status, and other data. The function keys are used to select menus and execute operations. The navigation keys allow for setting, switching, and changing operations within parameter groups, parameters, and parameter internals. The potentiometer is used to adjust motor speed in manual mode. The indicators show the operating status of the converter, such as power access, warnings, and alarms.

HLP-SV power on standby state

Initializing Parameters

To initialize the converter parameters, users can set parameter 14-22 to 2 to restore the converter to factory defaults. This operation will reset all parameters except parameters 15-03 (operating hours counter), 15-04 (overheat count), and 15-05 (overvoltage count) to their factory default values. Before performing this operation, ensure that important parameter settings have been backed up.

Setting and Removing Passwords

To prevent unauthorized parameter modifications, users can set a password. Parameter 0-60 can be used to set a password for the main menu, with a range of 0-999. After setting the password, only by entering the correct password can protected parameters be modified. To remove the password, simply set parameter 0-60 to 0.

Physical image on the right side of HLP-SV

Setting Parameter Access Restrictions

The HOLIP frequency converter provides parameter access restriction functions. Users can control the activation and editing permissions of different menus by setting parameters 0-10, 0-11, and 0-12. For example, setting parameter 0-10 to 1 or 2 can activate Menu 1 or Menu 2, respectively. Setting parameter 0-11 to 1 or 2 allows editing of Menu 1 or Menu 2, respectively. Setting parameter 0-12 to 20 enables parameter association between Menu 1 and Menu 2, ensuring that parameters that cannot be changed during operation can be synchronized between the two menus.

II. Terminal Forward/Reverse Control and External Potentiometer Speed Regulation

Terminal Forward/Reverse Control

To achieve motor forward/reverse control, users need to connect external control signals to the digital input terminals of the converter. Typically, terminals 18 and 19 are used to control motor forward and reverse, respectively. The specific wiring method is as follows:

  • Forward: Connect the external control signal to terminal 18 (DI1) and the common terminal (COM).
  • Reverse: Connect the external control signal to terminal 19 (DI2) and the common terminal (COM).

Additionally, set the functions of terminals 18 and 19 to “Start” and “Reverse” in parameters 5-10 and 5-11, respectively. Also, set the motor rotation direction to “Bidirectional” in parameter 4-10.

External Potentiometer Speed Regulation

External potentiometer speed regulation is a commonly used speed control method. Users can change the motor speed by rotating the potentiometer. The specific wiring method is as follows:

  • Connect one end of the external potentiometer to the +10V power terminal of the converter (e.g., terminal 50).
  • Connect the other end of the external potentiometer to the analog input terminal of the converter (e.g., terminal 53) and ground (GND).

Then, select “Voltage Signal” as the input signal type for terminal 53 in parameter 6-19, and set the source of Reference Value 1 to “LCP Potentiometer” in parameter 3-15. By rotating the external potentiometer, users can adjust the motor speed in real-time.

HOLIP-SV standard wiring diagram

III. Fault Codes and Their Solutions

The HOLIP HLP-SV series frequency converter has comprehensive protection functions. When a fault occurs, the converter will display the corresponding fault code. The following are some common fault codes, their meanings, and solutions:

  • W/A 2: Signal Float Zero Fault
    • Meaning: This fault occurs when the converter detects that the float zero value of terminal 53 or 60 is less than 50% of the set value.
    • Solution: Check if the signal line connection is normal and ensure a stable signal source.
  • W/A 4: Power Phase Loss
    • Meaning: There is a phase loss or excessive voltage imbalance at the power supply terminal.
    • Solution: Check the power input line and power supply voltage for normalcy.
  • W/A 7: Overvoltage
    • Meaning: The intermediate circuit voltage (DC) exceeds the converter’s overvoltage limit.
    • Solution: Check if the power supply voltage is too high, connect a braking resistor, or activate “Braking Function/Overvoltage Control” in parameter group 2.
  • W/A 9: Converter Overload
    • Meaning: The converter’s electronic thermal protection indicates that the converter is about to disconnect due to overload.
    • Solution: Check if the mechanical system is overloaded, adjust the load, or increase the converter capacity.
  • W/A 10: Motor Overheat
    • Meaning: The electronic thermal relay (ETR) protection device indicates motor overheat.
    • Solution: Check the motor load and motor parameter settings for correctness, reduce the load, or improve the cooling conditions.
  • A 16: Output Short Circuit
    • Meaning: There is a short circuit in the motor terminal or motor.
    • Solution: Check if the motor insulation is damaged and eliminate the short circuit fault.

The above are only some fault codes and their solutions. Users can refer to the fault code table in the converter user manual for troubleshooting other faults encountered during use.

IV. Conclusion

The HOLIP HLP-SV series user manual provides detailed operation guides and troubleshooting methods for users. By familiarizing with the functions of the operation panel and parameter setting methods, users can easily initialize the converter, set passwords, restrict parameter access, achieve forward/reverse control and external potentiometer speed regulation, and more. At the same time, understanding common fault codes and their solutions helps users quickly troubleshoot and resolve converter faults, ensuring normal equipment operation.

Posted on Leave a comment

FANUC Servo Drive βISVSP A06B Maintenance Guide: Troubleshooting No Display Issues


FANUC servo drives, specifically the βISVSP A06B series, are widely used in various automated equipment, providing efficient and precise motor control. However, in practical use, various faults may arise, with one of the most common being the lack of display. A non-functional display is often caused by power issues, control circuit problems, or hardware malfunctions. This article explores the maintenance approach for resolving no display issues in FANUC servo drives, focusing on troubleshooting steps and solutions.

I. Fault Phenomenon: No Display

The no display fault in FANUC servo drives refers to a situation where the device powers on, but the panel displays no information. The indicator lights might be completely off, or the screen may be unresponsive, suggesting that there could be problems with the control circuits, display module, or power supply module inside the drive. If not addressed in a timely manner, this issue could prevent the device from starting or executing control instructions, which can negatively impact production efficiency.

II. Troubleshooting Approach

When encountering a no display issue in a servo drive, it’s essential to systematically check the device. Below are the common troubleshooting steps:

1. Check Power Supply Input

The first step is to verify if the power supply to the servo drive is functioning correctly. Power is the foundation for all electronic devices, and any instability or interruption in the power supply can prevent the drive from functioning properly.

  • Check the Power Voltage: Use a multimeter to check the voltage at the input terminals of the servo drive, confirming that it falls within the specified range. The FANUC servo drive typically requires a three-phase AC input voltage within a certain range.
  • Check Power Connections: Verify that the power supply cables are correctly connected and not damaged or disconnected. Poor power contact can lead to unstable voltage supply, which can result in no display issues.

2. Check Fuses and Circuit Breakers

Servo drives are equipped with fuses or circuit breakers to prevent damage from excessive current. If a fuse blows or the circuit breaker trips, the device will fail to operate properly.

  • Check the Fuse: Open the servo drive and inspect the fuses in the power section. If the fuse is blown, replace it with one of the same rating.
  • Check the Circuit Breaker: Some servo drives come with an internal circuit breaker that trips in case of voltage abnormalities or overcurrent. If the circuit breaker has tripped, reset it manually.

3. Check the Main Control Circuit

If the power supply is fine, the next step is to inspect the servo drive’s main control circuit. The control circuit acts as the brain of the servo drive, and any malfunction in this area could result in a non-responsive display.

  • Check the Control Chip: The control chip is usually located centrally on the circuit board and is responsible for processing input signals and controlling the operation of the drive. Look for signs of overheating, burning, or damage around the chip. Use an oscilloscope or multimeter to check the power supply voltage and signal output of the chip to ensure it’s functioning properly.
  • Check Circuit Connections: The circuit board in the servo drive is connected to various modules via connectors. Check if any connectors are loose or disconnected, as poor connections can prevent signals from transmitting correctly.

4. Check the Display Module and Signal Transmission

The display module is responsible for showing system status information to the operator. If the display module fails, it could lead to a no display situation.

  • Check the Display Screen: Inspect the power supply input terminals and signal transmission lines to the display screen to ensure they are properly connected. If the display module itself is faulty, it may need to be replaced.
  • Check Signal Transmission: If the display module appears intact, the issue could lie with the signal transmission. Inspect the signal lines between the main control board and the display module to ensure that signals are properly transmitted.

5. Check Capacitors and Power Filtering Circuits

Capacitors and filtering circuits help stabilize the voltage supply, especially for high-frequency currents. If the capacitors are damaged, the power supply could become unstable, affecting the drive’s operation.

  • Check the Capacitors: Look for signs of bulging, leakage, or aging in the capacitors. If a capacitor is faulty, it should be replaced with one of the same model.
  • Check the Filtering Circuits: The components in the filtering circuits may also be damaged, which can cause unstable voltage output. Inspect these components and replace them as necessary.

III. Common Fault Analysis and Solutions

1. Unstable Power Supply Leading to No Display

An unstable power supply voltage can prevent the drive from starting properly. In this case, check the stability of the power supply and ensure the voltage is within the specified range. If issues are found with the power supply, it may be necessary to replace the power module or reconnect the power supply.

2. Control Circuit Malfunction

A malfunctioning control circuit can prevent the system from starting or lead to a no display issue. Typically, this fault requires replacing damaged components. Commonly damaged components include control chips, integrated circuits, and resistors.

3. Display Module Failure

If the display module itself is faulty, it could be due to issues with the backlight, circuit board, or the display screen. Inspect the power input terminals and signal transmission lines to confirm the issue. If the display screen is damaged, replacing the display module will likely resolve the problem.

4. Capacitor or Filtering Circuit Issues

Damaged capacitors can cause unstable power, affecting the drive’s operation. Replacing faulty capacitors or repairing the filtering circuits should solve this issue.

IV. Conclusion

The no display issue in FANUC servo drives βISVSP A06B series is typically related to power problems, control circuit failures, or display module malfunctions. Through systematic troubleshooting and careful inspection, the problem can usually be pinpointed and resolved. During maintenance, special attention should be paid to power stability, circuit connections, and the condition of critical components. For more complex issues, professional diagnostic tools may be required, and damaged components should be replaced to restore the device to normal operation. Timely and effective maintenance ensures the long-term stability and performance of FANUC servo drives, helping to maintain production efficiency.

Posted on Leave a comment

User Manual Guide for Vacon NXS_NXP Series Inverters

I. Introduction to the Operating Panel Functions

The Vacon NXS_NXP series inverters are equipped with an intuitive and user-friendly operating panel, providing users with a convenient interface for operation and monitoring. The operating panel typically includes a display screen, multiple function buttons, and status indicators. The display screen is used to show the current operating status, parameter values, and fault information. The function buttons are used for navigating menus, modifying parameter values, resetting faults, and other operations. The status indicators display the running status of the inverter, such as running, stopped, alarming, and faulting.

NXP physical image

II. How to Initialize Parameters (Specific Parameters)

Before using the Vacon NXS_NXP series inverters, users may need to initialize the parameters to ensure all settings are at their default values. The initialization process usually includes restoring the factory settings of the inverter. Users can follow these steps to initialize the parameters:

  1. Enter the System Menu: First, access the system menu (usually labeled as M6) through the operating panel.
  2. Select Parameter Sets: In the system menu, find the parameter set option (typically labeled as S6.3.1).
  3. Restore Factory Defaults: In the parameter set option, select the “Load Factory Defaults” option and confirm the execution. This will restore all parameters of the inverter to their factory settings.

III. How to Set and Reset Passwords (Specific Parameters)

To protect the settings of the inverter from unauthorized changes, the Vacon NXS_NXP series inverters provide a password protection feature. Users can follow these steps to set and reset passwords:

  1. Setting a Password:
    • Enter the system menu (M6).
    • Find the password setting option (usually labeled as S6.5.1).
    • Enter the password value (typically ranging from 1 to 65535) through the buttons on the operating panel.
    • Confirm the password setting.
  2. Resetting a Password:
    • Enter the system menu (M6).
    • Find the password setting option (S6.5.1).
    • Enter the current password (if already set).
    • Set the password value to 0 and confirm the execution. This will disable the password protection feature.
NXS-NXP actual wiring diagram

IV. How to Set Parameter Access Restrictions (Specific Parameters and Operations)

In addition to password protection, the Vacon NXS_NXP series inverters also provide a parameter access restriction feature, allowing users to restrict access and modification of specific parameters. Users can follow these steps to set parameter access restrictions:

  1. Enter the System Menu (M6).
  2. Find the Parameter Lock Option (usually labeled as S6.5.2).
  3. Enable Parameter Lock: Set the parameter lock option to “Locked” and confirm the execution. This will restrict access and modification of most parameters.
  4. Disable Parameter Lock: When needing to modify locked parameters, first set the parameter lock option to “Unlocked” and confirm the execution.

V. How to Achieve External Terminal Forward/Reverse Control and External Potentiometer Speed Regulation

The Vacon NXS_NXP series inverters support motor forward/reverse control through external terminals and speed regulation through external potentiometers. Users need to set the following parameters and connect corresponding terminals:

  1. Forward/Reverse Control:
    • Parameter Settings: No specific parameter settings are required, but ensure the control signal source is set to external terminal control (P3.1=1).
    • Wiring: Connect the external forward button or switch to DIN1 (or the designated forward input terminal), and connect the external reverse button or switch to DIN2 (or the designated reverse input terminal).
  2. External Potentiometer Speed Regulation:
    • Parameter Settings: Ensure AI1 (or the designated analog input terminal) is set to accept analog voltage or current signals (specific settings depend on the potentiometer type).
    • Wiring: Connect the output end of the potentiometer to AI1 (or the designated analog input terminal), and connect the common terminal of the potentiometer to AI1- (or the corresponding common terminal).

VI. Fault Codes and Their Solutions

The Vacon NXS_NXP series inverters feature comprehensive fault diagnosis capabilities. When a fault is detected, the inverter will display the corresponding fault code and fault information. The following are some common fault codes, their meanings, and solutions:

  1. Fault Code F01: Overcurrent
    • Meaning: Motor current exceeds the rated value.
    • Solution: Check if the motor load is too heavy, and check for short circuits or grounding in the motor and cables.
  2. Fault Code F02: Overvoltage
    • Meaning: DC bus voltage is too high.
    • Solution: Check if the power supply voltage is too high, extend the deceleration time, or increase the braking resistor.
  3. Fault Code F03: Ground Fault
    • Meaning: Motor or cable grounding.
    • Solution: Check the insulation resistance of the motor and cables.
  4. Fault Code F05: Charging Switch Fault
    • Meaning: Charging switch failure.
    • Solution: Check the charging switch and its connection lines, and replace the charging switch if necessary.

(Note: The above are only examples of some fault codes. For a complete list of fault codes and solutions, please refer to the inverter user manual.)

Through this guide, we hope to help users better understand and use the Vacon NXS_NXP series inverter user manual, achieving efficient and safe frequency control.

Posted on Leave a comment

The Meaning and Solutions for AL-24 Alarm on FANUC αi Series Spindle Amplifiers

In the maintenance and repair of CNC machine tools, fault alarms are a common occurrence. For equipment using FANUC αi series spindle amplifiers, the AL-24 alarm is a typical code. This article will explore the meaning of this alarm, possible causes, and solutions, providing theoretical support and practical guidance for CNC servo system repairs.


AL-24

1. Meaning of the AL-24 Alarm

According to FANUC’s official documentation, the AL-24 alarm indicates that the serial communication data between the CNC (Computer Numerical Control system) and the spindle amplifier module contains errors. This alarm typically occurs when there is an abnormality in the communication link between the CNC and the spindle amplifier. It is important to note that this alarm does not necessarily indicate hardware failure; in most cases, it is caused by communication issues or external interference.

Scenarios Triggering the Alarm

  • The CNC is powered off while the spindle amplifier remains energized.
  • Serial communication is disrupted, causing data transmission errors.
  • Communication cables are loose, damaged, or poorly connected.

2. Possible Causes of the AL-24 Alarm

When diagnosing the AL-24 alarm, the investigation should focus on the communication link, cable conditions, and hardware status. Common causes include:

1. Communication Noise Interference

Serial data transmission between the CNC and the spindle amplifier may be disrupted by external electromagnetic noise, resulting in data errors and triggering the AL-24 alarm.

2. Cable Issues or Connection Problems

The communication cable is a critical link between the CNC and the spindle amplifier. Possible issues include:

  • Cable aging or internal breakage.
  • Loose or improperly secured connectors.
  • In the case of fiber optic communication, damaged optical connectors or modules.

3. Bundling of Communication and Power Cables

When communication cables are bundled with spindle or servo motor power cables, high-frequency currents may cause electromagnetic interference, affecting communication stability.

4. Hardware Malfunction

Hardware-related issues that may trigger the AL-24 alarm include:

  • Faulty internal circuit boards in the spindle amplifier module (SPM).
  • Damaged communication interface boards or modules in the CNC control system.

5. Parameter Configuration Issues

Incorrect communication parameter settings in the spindle amplifier or CNC can also lead to communication failures.


A06B-6140-h055

3. Solutions for the AL-24 Alarm

When addressing the AL-24 alarm, follow these steps for systematic troubleshooting:

1. Verify CNC Power Status

Check whether the CNC is properly powered. If the CNC is off, the spindle amplifier cannot establish communication, which is a normal reason for the alarm.

  • Action: Ensure the CNC is fully powered and there are no additional alarm codes.

2. Inspect Communication Cables

Communication cables are crucial for the connection between the CNC and the spindle amplifier. Diagnosing cable issues is a key step.

  • Steps:
    • Inspect the cable’s exterior for damage or aging.
    • Ensure connectors are securely plugged in.
    • For fiber optic communication, check the cleanliness of the optical connectors and the condition of the optical modules.
  • Actions:
    • Replace the communication cable and reconnect.
    • If optical modules are faulty, contact the supplier for replacement.

3. Address Noise Interference

Communication stability can be compromised by noise interference, particularly when communication cables are bundled with power cables.

  • Steps:
    • Check the routing of communication cables to ensure they are separated from power and servo cables.
    • Use well-shielded cables or add shielding to existing cables.
  • Actions: Separate communication cables from power cables to maintain a safe physical distance.

4. Examine the SPM Module

The internal circuit board of the spindle amplifier (SPM) may fail due to aging or external impact.

  • Actions:
    • Inspect the SPM module for physical damage or burn marks.
    • Contact FANUC support for repair or replacement if the module is faulty.

5. Validate CNC Hardware

If the SPM is functioning correctly, check the communication interface boards or modules on the CNC side.

  • Actions:
    • Replace the relevant communication boards and test.
    • Check the CNC’s alarm log for related issues.

6. Correct Parameter Settings

Incorrect communication parameters may prevent successful communication between the CNC and the SPM.

  • Actions:
    • Reconfigure communication parameters based on the equipment model and manual.
    • Ensure communication speed, protocols, and other settings match between the SPM and CNC.

4. Preventive Measures

To reduce the likelihood of AL-24 alarms, consider the following preventive measures:

  1. Regular Cable Inspection:
    • Ensure communication cables are free from aging, breakage, or damage.
    • Use durable, high-quality shielded cables.
  2. Optimize Cable Routing:
    • Keep communication cables separate from power lines to avoid interference.
  3. Routine Hardware Maintenance:
    • Inspect the SPM and CNC hardware regularly and replace aging components promptly.
    • Clean amplifier and cable interfaces to prevent dust accumulation.
  4. Environmental Control:
    • Minimize strong electromagnetic interference around the equipment.
    • Provide adequate cooling for amplifiers and control cabinets.

Conclusion

The AL-24 alarm, a common fault code in FANUC αi series spindle amplifiers, primarily reflects communication abnormalities between the CNC and the spindle amplifier. By understanding its meaning, identifying causes, and following a structured troubleshooting process, maintenance personnel can quickly resolve the issue. Additionally, implementing preventive measures can significantly reduce the occurrence of such alarms, ensuring long-term stability and performance of the equipment.