Posted on Leave a comment

User Guide for Botain A900 Series Inverter Manual

The Botain A900 series inverter is a high-performance, feature-rich industrial-grade device widely used in various industrial scenarios. To help users better understand and operate this inverter, this article provides a detailed introduction to the control panel functions, parameter initialization, password setting and locking, parameter copying, external terminal control, and fault code analysis and troubleshooting methods.


1. Introduction to the Control Panel Functions

Actual working diagram of A900

The A900 series inverter’s control panel is designed intuitively, with the following main buttons and display areas:

  1. RUN Key: Starts the inverter operation.
  2. STOP/RESET Key: Stops the operation or resets faults.
  3. Arrow Keys (Up, Down, Left, Right): Used for browsing parameters or adjusting settings.
  4. ENTER Key: Confirms parameter settings.
  5. ESC Key: Exits the current menu.
  6. LED Numeric Display Screen: Displays current frequency, operating status, fault codes, etc.

How to Restore Parameter Initialization?

To reset the inverter to factory settings, follow these steps:

  1. Enter the parameter setting mode and locate parameter P0-00.
  2. Set P0-00 to 1 and press ENTER to confirm.
  3. The inverter will automatically restore all parameters to their factory default values.

How to Set Passwords and Lock Parameters?

To prevent parameters from being accidentally operated or changed, follow these steps to set a password:

  1. Locate parameter P0-14 and set a 4-digit password.
  2. After confirmation, some parameters will be locked.
  3. To unlock, enter the correct password in P0-15.

How to Copy Parameters to Another Inverter?

The parameter copy function allows users to quickly transfer the settings of the current inverter to another one. Follow these steps:

  1. Insert the control panel into the current inverter and enter the parameter setting mode.
  2. Set P0-50 to 1 to save parameters to the panel.
  3. Insert the control panel into the target inverter, set P0-50 to 2, and load the parameters from the panel to the inverter.
  4. Once parameter copying is complete, the inverter will reset automatically.

A900 standard wiring diagram

2. External Terminal Control and Speed Adjustment Settings

How to Achieve External Terminal Forward/Reverse Control?

To control forward/reverse rotation via external terminals, complete the following wiring and parameter settings:

  1. Wiring Requirements:
    • Forward Control: Connect the control signal to terminal FWD.
    • Reverse Control: Connect the control signal to terminal REV.
    • Common Terminal: Connect to terminal COM.
  2. Parameter Settings:
    • Set P0-02 to 1 (External Terminal Control Mode).
    • Set P3-01 and P3-02 for the logic input definitions of forward and reverse rotation.

How to Achieve Frequency Adjustment with an External Potentiometer?

  1. Wiring Requirements:
    • Connect the middle terminal of the potentiometer to AI1 (Analog Input 1).
    • Connect the two side terminals of the potentiometer to +10V and GND, respectively.
  2. Parameter Settings:
    • Set P0-03 to 1 (Analog Voltage Input).
    • Adjust P1-01 and P1-02 to the minimum and maximum frequency values to ensure that the potentiometer adjustment range meets actual needs.

Through the above settings, you can achieve forward/reverse control via external terminals and adjust output frequency via the potentiometer for precise speed control.


3. Fault Codes and Troubleshooting Methods

During operation, the inverter may encounter faults for various reasons. Below are common fault codes, their meanings, and troubleshooting methods:

Fault CodeFault DescriptionTroubleshooting
E001Overcurrent ProtectionCheck if the motor is overloaded or if the output line is short-circuited.
E002Overvoltage ProtectionCheck if the power supply voltage is abnormal or if feedback is too high.
E003Undervoltage ProtectionCheck if the power supply voltage is too low or if there is a loose connection.
E004Overtemperature ProtectionCheck if the inverter’s cooling system is working properly and clean the heat sink.
E005Phase Loss ProtectionCheck if the three-phase power input is normal and if the motor has a disconnection.
E006Ground FaultCheck if the grounding line is properly connected or if there is a short circuit.
E007External Fault TriggeredCheck the signal source and cause of the external fault input terminal.

If the above faults occur, follow the fault code and analysis methods to troubleshoot and take appropriate measures step by step.


4. Conclusion

The Botain A900 series inverter offers powerful functions and flexible control methods. By familiarizing yourself with the control panel functions, parameter initialization, password setting and locking, and parameter copying, you can quickly master its basic operations. Additionally, with correct external terminal and potentiometer wiring and parameter settings, forward/reverse control and speed adjustment can be easily achieved, significantly improving the efficiency and reliability of industrial equipment.

Furthermore, understanding the meanings and solutions of common fault codes will help users quickly identify issues and take effective measures in case of faults, avoiding production interruptions.

With this user guide, users can operate the Botain A900 series inverter more efficiently, ensuring the smooth operation of industrial automation equipment.

Leave a Reply

Your email address will not be published. Required fields are marked *