Posted on Leave a comment

User Manual Guide for KRC9 Series Inverter (Koreachuan)

I. Detailed Explanation of Operation Panel Functions

1. Overview of Operation Panel Functions
The operation panel of the Koreachuan KRC9 series inverter integrates functions such as parameter setting, status monitoring, and operation control. The core key functions are as follows:

  • Programming Key: Enters or exits the menu.
  • Enter Key (ENTER): Confirms parameters or navigates to the next menu level.
  • Increment/Decrement Keys: Adjust parameter values.
  • Shift Key: Switches display interfaces or parameter positions.
  • Run/Stop/Reset Key: Controls start/stop or resets the inverter.
  • Multi-function Selection Key (MP3): Switches between functional modes.

2. Password Management

  • Set Password: Press the MP3 key to select password setting, enter the password, and confirm with ENTER.
  • Clear Password: Enter the correct password and press MP3 to exit the password setting mode.

3. Parameter Access Permissions

  • Set Restrictions: Enter the parameter setting interface, select parameters, and set permissions (e.g., read-only/write-only).
  • Remove Restrictions: Restore permissions to default settings.

4. Factory Parameter Management

  • Restore Factory Settings: Set PP-01 to 1 to reset parameters to factory defaults.
  • Backup/Restore Parameters: Set PP-01 to 4 to backup parameters, or to 501 to restore from backup.

KRC9 front image

II. External Control Setup Guide

1. External Terminal Forward/Reverse Control

  • Wiring Instructions:
    • Forward Rotation: Connect to DI1 terminal.
    • Reverse Rotation: Connect to DI2 terminal.
  • Parameter Configuration:
    • P0-02: Set to 1 (terminal control).
    • P4-00: Set to 1 (forward rotation).
    • P4-01: Set to 2 (reverse rotation).

2. External Potentiometer Speed Control

  • Wiring Instructions: Connect the potentiometer output to AI1 or AI2 terminal.
  • Parameter Configuration:
    • P0-03: Set to 2 (AI1 setting) or 3 (AI2 setting).
    • P4-13/P4-14: Set the potentiometer input range and corresponding frequency range.

III. Fault Codes and Troubleshooting Solutions

1. Common Fault Codes

Fault CodeDescriptionPossible Causes
Err02Acceleration OvercurrentOutput circuit grounded/shorted
Err03Deceleration OvercurrentOutput circuit grounded/shorted
Err04Steady-state OvercurrentOutput circuit grounded/shorted
Err05Acceleration OvervoltageInput voltage too high
Err06Deceleration OvervoltageOvervoltage suppression settings improper

2. Troubleshooting Process

  1. Identify the Fault: Locate the cause based on the fault code.
  2. Check Peripheral Devices: Inspect motors, cables, contactors, etc.
  3. Adjust Parameters: Optimize overcurrent/overvoltage suppression settings.
  4. Restart the Device: After resolving the fault, restart to confirm normal operation.

IV. Conclusion

KRC9 side image

The Koreachuan KRC9 series inverter is a high-performance and reliable device suitable for various industrial applications. By mastering the operation panel functions, parameter settings, external control, and fault handling, users can fully leverage its capabilities and enhance productivity. This guide aims to provide practical references for the use and maintenance of the device.

Posted on Leave a comment

User Manual Guide and DC BR Fault Analysis & Resolution for the Edley Inverter AS Series

I. Introduction to the Operation Panel Functions and Basic Settings of the Inverter

The ADLEEPOWER AS series inverter is a high-performance, multifunctional inverter with an intuitive operation panel and rich features. The operation panel mainly includes the following function keys:

  • FWD/RUN: Forward run key. Pressing this key will rotate the motor in the forward direction.
  • REV/RUN: Reverse run key. Pressing this key will rotate the motor in the reverse direction.
  • SHIFT: Shift key. Used to switch the position of digits during parameter setting.
  • UP/DOWN: Up/down keys. Used to increase or decrease values during parameter setting.
  • PROG: Memory key. Used to save the currently set parameters.
  • FUNC: Function key. Used to select the function to be set.
  • STOP: Stop key. Pressing this key will stop the motor and return it to standby mode.

Restoring Factory Default Parameters

To restore the inverter’s parameters to factory defaults, follow these steps:

  1. Press the PROG key to enter parameter setting mode.
  2. Use the UP/DOWN keys to find the CD52 parameter (regional version).
  3. Press the FUNC key to enter parameter modification mode.
  4. Use the UP/DOWN keys to set the CD52 parameter to USA (for the US version) or Eur (for the European version), then press the PROG key to save.
  5. Power off and restart the inverter. The parameters will be restored to factory defaults.
AS2-IPM

Setting and Removing Passwords

The AS series inverter supports password protection to prevent unauthorized parameter modifications. To set a password, follow these steps:

(Note: The specific password setting method may vary depending on the model. The following are general steps.)

  1. Enter parameter setting mode.
  2. Find the parameter related to password setting (refer to the user manual of the specific model for the exact parameter number).
  3. Use the UP/DOWN keys to set the password, then press the PROG key to save.

To remove the password, simply set the password parameter to the default value or leave it blank.

Setting Parameter Access Restrictions

The AS series inverter also supports parameter access restriction functions, which can limit users’ access and modification permissions for certain parameters. To set parameter access restrictions, follow these steps:

  1. Enter parameter setting mode.
  2. Find the parameter related to parameter access restrictions (refer to the user manual of the specific model for the exact parameter number).
  3. Use the UP/DOWN keys to set the access level, then press the PROG key to save.

II. Terminal Forward/Reverse Control and External Potentiometer Frequency Setting for Speed Regulation

Terminal Forward/Reverse Control

The AS series inverter supports forward/reverse control of the motor through external terminals. The specific wiring and parameter settings are as follows:

  • Wiring:
    • Connect the forward control signal terminal of the external control signal to the FWD terminal of the inverter.
    • Connect the reverse control signal terminal of the external control signal to the REV terminal of the inverter.
    • Ensure that the common terminal of the external control signal is connected to the COM terminal of the inverter.
  • Parameter Settings:
    • Enter parameter setting mode.
    • Find the CD12 parameter (terminal or keyboard selection).
    • Set the CD12 parameter to 1, indicating that the forward/reverse control of the motor is through the terminals.

External Potentiometer Frequency Setting for Speed Regulation

The AS series inverter also supports speed regulation by setting the frequency through an external potentiometer. The specific wiring and parameter settings are as follows:

  • Wiring:
    • Connect the signal output terminal of the external potentiometer to the FA1 or FA2 terminal of the inverter (the specific terminal to be used depends on the parameter setting).
    • Ensure that the common terminal of the external potentiometer is connected to the GND terminal of the inverter.
  • Parameter Settings:
    • Enter parameter setting mode.
    • Find the CD10 parameter (analog or digital setting).
    • Set the CD10 parameter to 1, indicating that the frequency is set through an analog signal (i.e., an external potentiometer).
    • Set the CD44 or CD45 parameter (multi-function analog FA1 or FA2 setting) as needed to select the FA1 or FA2 terminal as the frequency setting input terminal.
DCBR

III. DC BR Fault Analysis and Solution

Meaning of DC BR Fault

When the AS series inverter displays a “DC BR” fault, it usually indicates a DC braking fault. DC braking is a function of the inverter that injects DC current into the motor during shutdown to quickly decelerate or stop the motor. If there is a problem with the DC braking circuit, it may cause a “DC BR” fault.

Possible Causes of the Fault

  1. Damage to the DC Braking Resistor: The DC braking resistor is an important component in the DC braking circuit. If the resistor is damaged or aged, it may cause abnormal braking current, triggering the fault.
  2. Failure of the Braking Transistor: The braking transistor is responsible for controlling the on/off of the DC braking current. If the transistor is damaged or its performance degrades, it may also cause a braking fault.
  3. Improper Parameter Settings: If the parameters related to DC braking (such as braking time, braking current, etc.) are set improperly, it may result in poor braking performance or trigger a fault.

Solutions

  1. Check the DC Braking Resistor: Use a multimeter or other tools to check the resistance value of the DC braking resistor. If the resistor is damaged or aged, replace it with a new one.
  2. Check the Braking Transistor: Use a multimeter or other tools to check the performance of the braking transistor. If the transistor is damaged or its performance degrades, replace it with a new one.
  3. Check Parameter Settings: Recheck whether the parameters related to DC braking are set correctly. Adjust the parameter values according to the actual situation of the motor and braking requirements.
  4. Contact Technical Support: If the above methods cannot solve the problem, it is recommended to contact the technical support team or professional maintenance personnel of ADLEEPOWER inverters for further inspection and repair.

IV. Conclusion

The ADLEEPOWER AS series inverter, as a high-performance, multifunctional inverter product, has been widely used in the field of industrial automation. Through the introduction in this guide, users can better understand the operation panel functions, basic setting methods, terminal control and external speed regulation functions, as well as fault solution methods of the inverter. It is hoped that this guide can provide help and guidance to users when using the AS series inverters.

Posted on Leave a comment

Analysis and Handling of Er050 Fault in Hilectro HI300 Series Servo System


The Hilectro HI300 series servo system is a high-performance servo drive widely used in industrial automation, renowned for its high precision and reliability. However, in practical applications, the fault code “Er050” may occur. This article provides a detailed analysis of the meaning of the “Er050” fault, its causes, as well as on-site inspection, handling, and specific maintenance methods to help technicians quickly restore equipment operation and summarize preventive measures to reduce the occurrence of similar faults.


1. Meaning of Er050 Fault

In the Hilectro HI300 series servo system, the “Er050” fault code indicates Software Overcurrent. This is a protective mechanism triggered when the servo drive’s software detects that the current value exceeds the preset safety threshold. Unlike hardware overcurrent (such as “Er056”), “Er050” is primarily detected and alarmed by software algorithms, usually related to control parameters, feedback signals, or external wiring issues. When this fault occurs, the system stops running and displays “Er050” on the digital display, accompanied by related indicator lights (such as “RDY” or “VCC”) lighting up, prompting the operator to take action.


2. Causes of Er050 Fault

The occurrence of “Er050” is not due to a single reason but is the result of multiple potential issues. The common causes are as follows:

  1. Excessive Current Loop PI Parameters
    The current control of the servo system relies on a Proportional-Integral (PI) controller, adjusted through parameters such as proportional gain (Kp, typically corresponding to CI.00) and integral gain (Ki, typically corresponding to CI.02). If these parameters are set too high, the controller may overreact to current changes, causing current fluctuations to exceed the normal range and trigger the software overcurrent protection.
  2. Short Circuit or Grounding on the Motor Output Side
    A short circuit in the motor’s internal windings or a ground fault in the output cable can cause a sharp increase in current. The software detects this anomaly and immediately alarms to protect the drive and motor.
  3. Encoder Wiring Issues
    The encoder provides feedback on the motor’s position and speed. If the encoder wiring is loose, disconnected, or short-circuited, the servo system cannot accurately obtain feedback data, leading to current control instability and eventually causing an overcurrent fault.
  4. Incorrect Motor Parameter Settings
    The servo drive needs to be precisely controlled based on the motor’s electrical parameters (such as inductance Ls). If the parameter configuration does not match the actual motor, the drive may output incorrect current commands, resulting in overcurrent.
  5. Environmental or Power Supply Interference
    Power supply voltage fluctuations or high ambient temperatures may affect current stability. Especially under long-term operation or harsh conditions, the software may misjudge it as overcurrent.

These causes may interact with each other. For example, an encoder fault may lead to current control errors, which in turn amplify the impact of PI parameters, ultimately triggering “Er050.”


er050

3. On-Site Inspection and Handling Methods

When the equipment displays “Er050,” technicians need to follow a systematic inspection process to quickly identify the problem and take preliminary measures. The specific steps are as follows:

1. Check Current Loop Parameters

  • Operation Method: Use the servo drive’s control panel or host computer software to enter the parameter setting interface and check the values of current loop parameters (such as CI.00 and CI.02).
  • Judgment Standard: If the parameter values are significantly higher than the recommended range (refer to the equipment manual), it may be the cause of the fault.
  • Handling Measures: Gradually reduce the Kp and Ki values (recommended to adjust by 10%-20% each time), save the settings, restart the system, and observe if the fault is resolved.

2. Check Motor Insulation and Wiring

  • Operation Method: Turn off the power and wait for the capacitor to discharge (about 5-10 minutes). Use a multimeter or insulation resistance tester to measure the insulation resistance between motor phases and to ground.
  • Judgment Standard: The normal insulation resistance should be greater than 10MΩ. If it is lower, it indicates a short circuit or grounding.
  • Handling Measures: Inspect the motor cables and terminals, repair or replace damaged parts.

3. Check Encoder Wiring

  • Operation Method: Ensure the encoder cable connections are secure and the shielding is properly grounded. Use a multimeter to test the continuity of the lines or an oscilloscope to observe the feedback signal waveform.
  • Judgment Standard: Signal interruption or abnormal waveform (such as excessive noise) indicates an encoder fault.
  • Handling Measures: Tighten loose connectors or replace damaged cables.

4. Check Motor Parameters

  • Operation Method: Verify the motor parameters set in the drive (such as inductance Ls) against the motor nameplate or manual data.
  • Judgment Standard: Significant parameter deviations may be the cause of the fault.
  • Handling Measures: Correct the parameters based on the actual motor data, save, and test.

5. Environmental and Power Supply Check

  • Operation Method: Use a voltmeter to measure the stability of the input power supply (380V-480V) and check the temperature and ventilation inside the control cabinet.
  • Judgment Standard: Voltage fluctuations exceeding the standard (±10%) or high temperatures (>40°C) may cause faults.
  • Handling Measures: Install a voltage stabilizer or improve cooling conditions.

4. Specific Maintenance Recommendations

Based on the on-site inspection results, take the following targeted maintenance measures:

  1. Parameter Adjustment
    If the PI parameters are too large, gradually reduce the values of CI.00 and CI.02, testing after each adjustment to observe the system response. Avoid excessive reduction that may lead to control instability.
  2. Wiring Repair
    For encoder or motor wiring issues, tighten loose connectors or replace damaged cables. Ensure the shielding is properly grounded to reduce electromagnetic interference.
  3. Component Replacement
  • Motor Fault: If insulation tests show a short circuit or grounding, replace the motor or repair the insulation.
  • Encoder Damage: Replace with the same model encoder and recalibrate the system.
  1. Hardware Maintenance
    If internal current sensors or power modules (such as IGBT) are suspected to be faulty, have a professional inspect and possibly replace the damaged components.
  2. Safety Operations
    Ensure the power is off and capacitors are discharged before maintenance. Use insulated tools and protective equipment. If the issue is complex, contact Hilectro technical support with the serial number and fault details for guidance.

5. Preventive Measures and Routine Maintenance

To prevent the recurrence of “Er050” faults, implement the following preventive measures:

  1. Regular Inspections
    Check motor, encoder, and power supply wiring quarterly to ensure there is no looseness or aging.
  2. Parameter Management
    Regularly back up parameter settings and monitor current waveforms during operation to ensure they are within normal ranges.
  3. Environmental Optimization
    Keep the control cabinet clean and dry, install ventilation or dehumidification equipment to prevent overheating and moisture accumulation.
  4. Personnel Training
    Train operators to recognize early anomalies (such as motor noise or overheating) and report them promptly for handling.

6. Conclusion

The “Er050” fault in the Hilectro HI300 series servo system, indicating software overcurrent, is a common protective alarm typically caused by excessive current loop parameters, wiring faults, or incorrect motor parameters. Through systematic on-site inspections (such as parameter verification, insulation testing, and encoder checks) and targeted maintenance (such as adjusting parameters or replacing components), technicians can effectively resolve the issue. Preventive maintenance and a deep understanding of the fault mechanisms are key to ensuring long-term stable operation of the equipment. We hope this article provides practical guidance for on-site operations. For further assistance, refer to the equipment manual or contact professional technical support.


Posted on Leave a comment

Diagnosis and Resolution of “Free Stop” Fault in ENC EDH2200 High-Voltage Inverter: Impact of S1# Function Configuration

Introduction

The ENC EDH2200 series high-voltage inverter is commonly used in industrial applications for motor control. However, during operation, it may enter a “free stop (emergency stop)” state due to faults, rendering it unable to restart. Based on an actual case, this article analyzes the causes of the inverter’s “free stop” fault, focusing on the impact of the input terminal S1# function configuration (P05.00), and summarizes solutions and preventive measures.

Fault Background

The inverter control panel (Attachment 5.jpg) displays an “actual alarm POFF state,” with operational parameters at 0 (input/output voltage 0V, current 0A, frequency 0Hz), indicating the system is in a non-operational state. The operation log (Attachment 1.jpg) shows S3# as “self-generated accident (total accident),” initially considered the root cause. However, after adjusting the S1# terminal function (P05.00) from “1: Lift given” to “0: No function,” the system returned to normal, and the inverter successfully restarted.

Emergency stop state

Fault Cause Analysis

Based on the operation log and the actual resolution process, the following is a detailed analysis of the fault causes:

  1. Impact of S1# Function Configuration
    • P05.00 (S1# function selection) was originally set to “1: Lift given,” likely used to receive signals from external devices (e.g., pump lift control signals).
    • If the external device fails to provide a correct signal (e.g., signal loss, abnormality, or interference), the system may misjudge it as a fault and trigger a protection mechanism, leading to “free stop.”
    • Changing P05.00 to “0: No function” removes S1# from control, and the system exits the protection state, indicating that the S1# configuration is the core issue.
  2. Correlation with S3# “Self-Generated Accident”
    • S3# (P05.02) displays “self-generated accident (total accident),” which may be a chain reaction triggered by S1# malfunction.
    • The inverter’s protection logic may be designed to trigger a total accident (S3#) and enter emergency stop mode when an abnormality is detected on a terminal (e.g., S1#).
  3. Possible External Factors
    • S1# may be connected to external devices (e.g., pumps or sensors). If the device malfunctions or there are wiring issues (e.g., loose connections, short circuits), it may cause signal abnormalities.
    • Environmental interference (e.g., electromagnetic interference) may also affect S1# signal transmission.
  4. Hardware and Parameter Configuration
    • Circuit board images (Attachments 3.jpg and 4.jpg) show relays K4/K5 and terminal connections. If S1#-related hardware is damaged, it may cause signal errors.
    • Improper configuration of P05 group parameters (input terminal function selection) may lead to system misjudgment.
Control circuit inside the high-voltage inverter cabinet

Resolution Process

  1. Problem Identification
    • The control panel displays “POFF state,” and the operation log shows S3# as “self-generated accident.” However, the “lift given” function of S1# raises concerns.
    • Referencing the P05 group parameter table (Attachment 6.jpg), it is confirmed that S1# (P05.00) is set to “1: Lift given.”
  2. Parameter Adjustment
    • Change P05.00 from “1” to “0” (no function) to remove S1# from control.
    • After adjustment, use the control panel’s “reset” function to clear the alarm.
  3. System Recovery
    • Press the “start” button, and the inverter successfully restarts with operational parameters returning to normal (voltage, current, frequency, etc., no longer 0).

Summary of Solutions

  • Core Solution Steps: Change P05.00 (S1# function) from “1: Lift given” to “0: No function,” remove S1#’s control function, clear the alarm, and restart the system.
  • Preventive Measures:
    • Check S1#’s wiring and external devices to ensure normal signal transmission.
    • Regularly maintain hardware to prevent loose connections or component damage.
    • Record parameter adjustments for future troubleshooting.

Unexpected Findings

  • The S3# “self-generated accident” record may only be a result, not the cause. The actual issue stems from the S1# configuration. This highlights the need to consider all relevant terminals and parameters when troubleshooting inverter faults, rather than focusing solely on alarm records.
  • The control panel brand is FLEXEM, while the inverter is ENC, which may involve terminological or logical differences. For example, the “POFF” state is defined in FLEXEM but not explicitly mentioned in the ENC manual.
EDH2200 terminal board

Table: Fault Causes and Solutions

Fault PhenomenonPossible CauseSolution
Free stop, unable to startS1# function (lift given) mis-triggerChange P05.00 to “0: No function”
S3# displays self-generated accidentChain reaction from S1# abnormal signalClear alarm after resolving S1# issue
System displays POFF stateProtection mechanism triggers power-offRestart system after clearing alarm
External device signal abnormalityLoose wiring or device faultCheck S1# wiring and external devices

Conclusion

The “free stop (emergency stop)” issue in the ENC EDH2200 high-voltage inverter is caused by improper configuration of the S1# terminal function (P05.00), potentially triggered by abnormal external signals. By changing the S1# function to “no function,” the system returns to normal. Users are advised to regularly check terminal wiring and external devices, optimize parameter configurations, and take preventive measures to avoid recurrence of similar issues.

Posted on Leave a comment

Analysis and Solutions for Fan Overheating Fault in ENC EDH2200 High-Voltage Inverter

Introduction

Variable Frequency Drives (VFDs) are critical devices for controlling motor speed and torque in modern industrial applications. However, fan overheating alarms are a common fault during inverter operation. This document provides a comprehensive analysis of the fan overheating alarm issue in the ENC EDH2200 series high-voltage inverter, covering its meaning, possible causes, solutions, and operational log analysis to guide users in troubleshooting and resolving the problem.


Fault Meaning

fan overheating alarm indicates that the cooling fan of the inverter has exceeded its temperature threshold, potentially affecting normal device operation. As a key component for internal temperature control, the fan’s failure to cool the system effectively will lead to temperature rises, trigger protection mechanisms, and may even damage electronic components or cause system failures.
Key Detail: The operational log shows the alarm occurred at 13:34:02 on March 25, 2023, with a recovery time recorded as 14:31:58 on September 7, 2024. The abnormally long alarm duration requires urgent attention.


The alarm for fan overheating

Possible Causes

  1. Excessive Ambient Temperature
    • The operating environment temperature exceeds the inverter’s default threshold of 75°C, causing the fan to run continuously for extended periods and overheat.
    • Manual Parameter: P08.27 sets the ambient temperature alarm threshold; verify if the actual temperature exceeds the limit.
  2. Fan Malfunction
    • Damage to the fan motor or obstruction of blades leads to insufficient cooling.
    • Manual Parameter: P23 group parameters (e.g., P23.20 and P23.21) control fan start/stop temperatures; these may fail if the fan malfunctions.
  3. Ventilation Blockage
    • Dust, debris, or internal accumulations block ventilation ports, impeding airflow.
    • Preventive Measure: Regularly clean the ventilation system.
  4. Overload
    • The connected load exceeds the inverter’s rated capacity, increasing heat generation and burdening the fan.
    • Solution: Ensure the load is within the inverter’s specifications.
  5. Improper Parameter Settings
    • Incorrect configuration of temperature control parameters results in inappropriate fan start/stop conditions.
    • Manual Parameter: Adjust P23.03 (overheat warning temperature 1, default 90°C) and P23.04 (default 110°C) based on actual conditions.

Solutions

  1. Check and Control Ambient Temperature
    • Measure the current ambient temperature and ensure it remains below the 75°C threshold.
    • If the temperature is too high, install air conditioning or improve ventilation (e.g., add exhaust fans).
  2. Maintain and Inspect the Fan
    • Ensure the fan operates normally and check for damage or wear to the motor and blades.
    • If a fault is detected, replace damaged components by referring to Section 8.5 of the manual.
    • Regularly clean the fan to remove dust or blockages.
  3. Optimize the Ventilation System
    • Ensure sufficient space around the inverter to meet ventilation requirements in the manual.
    • Clean ventilation ports and surrounding areas to prevent dust accumulation.
  4. Verify Load and Inverter Capacity
    • Check if the current load exceeds the inverter’s rated capacity; if so, reduce the load or upgrade the inverter.
    • Ensure compatibility between the motor and the inverter.
  5. Adjust Parameter Settings
    • Modify P23 group parameters based on actual needs (e.g., increase P23.03 to an appropriate value, but do not exceed 135°C).
    • Ensure P23.20–P23.23 settings align with actual operating conditions.

Operational Log Analysis

  • Key Log Entries:
    • March 25, 2023, 13:34:02: Fan overheating alarm triggered. Recovery time recorded as September 7, 2024, 14:31:58, indicating an abnormally long alarm duration that may not have been resolved promptly.
    • Multiple ambient temperature exceedance warnings (e.g., repeated records on February 7, 2024) support the hypothesis of excessive ambient temperature.
  • Unexpected Detail: Inconsistent dates in the log (recovery time later than the alarm time) suggest a potential error in the system’s logging mechanism.
    • Recommendation: Check the system clock and logging function to ensure data accuracy.

EDH2200

Conclusion

Resolving the fan overheating alarm in the ENC EDH2200 series high-voltage inverter requires a systematic investigation of potential causes and the implementation of the following measures to manage and prevent issues:

  • Control ambient temperaturemaintain the fanoptimize ventilationverify load, and adjust parameters.
    Regular maintenance and monitoring are critical to ensuring the long-term reliability of the inverter.

Key Highlight: Prioritize addressing the inconsistent dates in the operational log to avoid misdiagnosis caused by logging errors.

Posted on Leave a comment

SHZHD.V680 Variable Frequency Drive E-06 Fault Analysis and Solutions

1. Fault Overview

The E-06 fault indicates a deceleration overvoltage, a common issue that can occur during the deceleration process of the SHZHD.V680 variable frequency drive. When the output voltage exceeds the safe range during deceleration, the drive triggers a protection mechanism, leading to equipment shutdown or alarms. This fault is often related to motor load characteristics, parameter settings, and over-excitation control.

2. Fault Cause Analysis

  • Improper Over-Excitation Settings: Low over-excitation gain settings can cause the voltage to rise too quickly during deceleration.
  • Load Characteristics: Loads with high inertia can generate excessive reverse electromotive force during deceleration.
  • Unreasonable Parameter Settings: Short deceleration times can cause the voltage to rise too quickly during deceleration.
E-05

3. Solutions

3.1 Adjust Over-Excitation Gain
  • Parameter P3-10 (VF Over-Excitation Gain): Increase this value to better suppress voltage rise during deceleration. Recommended range: 0 ~ 200. Gradually increase based on actual conditions until the fault is resolved.
3.2 Optimize Deceleration Time Settings
  • Parameter P0-18 (Deceleration Time 1): Extend the deceleration time to make the deceleration process smoother. Gradually increase based on actual load characteristics until the fault is resolved.
3.3 Check Load Characteristics
  • If the load has high inertia, additional braking measures, such as adding a braking resistor or using a regenerative system, may be necessary during deceleration.
3.4 Check Motor and Drive Compatibility
  • Ensure that the motor and drive parameters are matched to avoid overvoltage issues due to mismatched parameters.

4. Precautions

  • Adjust parameters gradually to avoid introducing other issues.
  • Conduct trial runs after adjustments to confirm that the fault has been resolved.
  • If the problem persists, consult technical support or a professional repair technician for further diagnosis.
SHZHEND.V680

5. Conclusion

By appropriately adjusting the over-excitation gain, optimizing deceleration time settings, checking load characteristics, and ensuring motor and drive compatibility, the E-06 deceleration overvoltage fault in the SHZHD.V680 variable frequency drive can be effectively resolved. Proper parameter settings and regular maintenance are key to ensuring the efficient operation of the drive.

Posted on Leave a comment

M900 Inverter err64 Fault: Meaning, Root Cause Analysis, and Solutions

M900 Inverter err64 Fault: Meaning, Root Cause Analysis, and Solutions

(This article discusses the background of the “err64” fault in M900 series inverters, its potential causes, deeper hardware-level analyses, and practical troubleshooting steps. The goal is to help electrical maintenance personnel target the problem more effectively. This text, of over 1,000 words in its Chinese original, covers both theoretical and hands-on repair perspectives.)


I. Background and Meaning of err64

In typical inverter applications, the most common faults involve overcurrent, overvoltage, undervoltage, overload, and cooling fan issues. However, in certain cases—especially after repairs or the replacement of internal components—M900 inverters may display a “err64” fault code. According to the manufacturer’s technical support, “err64” is not listed in the usual user manual but indicates a communication failure between the main control board and the driver board.

In other words, the inverter’s primary control circuitry (often referred to as the “master” or “main” board) and its power drive unit (“driver” board) cannot exchange data, causing the control system to fail to operate properly and thus triggering a fault protection.

To understand this issue, one must note that an M900 inverter typically consists of at least two major sections: a control board (hosting the microcontroller or DSP as the core of the logic) and a driver board (housing the power modules, IGBTs, or related gate driver circuitry). These boards communicate via a dedicated interface or set of pins. Sometimes, there may also be a small power supply board or other auxiliary boards, but the communication link between the main board and the driver board is central to the entire system. Once that link is broken or corrupted, the inverter will report a “board-to-board communication error” such as “err64” and shut down to protect itself.


II. Common Causes of err64

  1. Loose or Faulty Ribbon Cable/Connector
    During maintenance or reassembly, a ribbon cable or connector might not have been fully seated, or its metal pins could be bent, oxidized, or otherwise damaged. This often leads to poor signal transmission or no transmission at all, and is one of the most frequent root causes for communication errors.
  2. Damaged Hardware Chips
    • Burned-out Transceiver/Bus Chip: The communication between the control and driver boards usually involves specialized transceiver components (e.g., RS485 driver chips, optical isolators, or TTL level transceivers). If subjected to excessive heat, current surge, or electrostatic discharge, these chips can fail and interrupt the data link.
    • Main CPU or Driver DSP Failure: Though less common, serious power surges, extended over-temperature conditions, or short-circuit mishandling can damage the main controller or DSP on either board. When that happens, the inverter can no longer exchange valid data, triggering the err64 alarm.
  3. Auxiliary Power Supply Issues
    The main board and driver board typically rely on a regulated power supply—often +5V or +3.3V—to operate their digital circuits. If this low-voltage supply is weak or unstable, or if a regulator (LDO, DC-DC converter) on either board is failing, then even intact chips may produce garbled signals and fail to establish proper communication.
  4. Secondary Damage During Fan or Relay Replacement
    Many reported err64 errors occur soon after a user replaces a fan or relay. This suggests that the process may introduce secondary problems:
    • An incompatible relay or altered circuit parameters causing abnormal power conditions;
    • Accidental short-circuits or soldering damage during the repair;
    • The inverter may already be partially degraded from prior overheating, so additional stress completes the failure pathway.

III. Root Cause Analysis and Troubleshooting

At its core, “err64” represents an internal communication failure. This communication is usually a low-level or custom protocol rather than a typical external fieldbus (like Modbus). As a result, the inverter’s diagnostic does not offer many granular details. Because the issue can lie in various hardware points, it is best to follow a structured approach:

  1. Physical Inspection and Connector Checks
    • First, turn off power and wait long enough for internal capacitors to discharge (generally at least 10 minutes).
    • Open the inverter casing to inspect all connectors, paying particular attention to the flat cables and sockets between the main board and driver board. Look for signs of looseness, oxidation, broken plastic housings, or bent pins.
    • Clean off any dust or grime with an appropriate solution such as isopropyl alcohol. Dry thoroughly, re-seat the connectors firmly, then restart and see if the error persists.
    • This preliminary step is simple but can resolve many “false” faults that arise after vibrations or reassembly.
  2. Supply Rails and Signal Tests
    • Use a multimeter to check the low-voltage rails (+5V, +3.3V, etc.) on both the control and driver boards. Confirm stable, correct output levels.
    • If available, use an oscilloscope to observe the communication pins (TX, RX, or RS485 differential signals) for pulses or signals. If the line is held at a steady voltage with no pulses, it indicates that the transmitter is not functioning (which could mean the transceiver or even the CPU is compromised).
    • If the signal is noisy or the amplitude is too low, consider the possibility of defective coupling resistors, capacitors, or the transceiver chip itself.
  3. Suspecting Transceiver or MCU Failure: The Swap/Replacement Method
    • After verifying connectors, supply rails, and passive components, you may try replacing the communication transceiver chip with one of the same model if you suspect it is burned out.
    • If replacing the transceiver chip does not help, the fault may lie in the main CPU, driver DSP, or other major components on the board. Diagnosing or replacing these can require specialized tools and is best handled by trained professionals.
  4. Reset to Factory Defaults or Firmware Update
    • Occasionally, firmware or software anomalies can also trigger internal communication timeouts.
    • Attempt a factory reset (restoring default parameters) and then power up again to see if the fault clears. If the manufacturer provides a firmware update procedure, you can try upgrading the system firmware. However, if the hardware is physically damaged, these software-level attempts typically will not resolve an err64 alarm.

IV. Precautions and Preventive Measures

  1. Prompt Cooling System Maintenance
    If the M900 inverter’s cooling fan stops working or its venting is blocked, the internal boards can operate at high temperatures, accelerating aging. Quick repair or replacement of fans can prevent serious damage that leads to communication issues.
  2. Standardized Repair Operations
    • Always allow adequate discharge time after powering off the inverter to avoid electric shock or component damage.
    • When replacing a relay or other parts, match the specifications (coil voltage, contact ratings, etc.) exactly.
    • Proper soldering tools and techniques are crucial—poorly done solder joints or bridging can damage sensitive PCB traces and components.
  3. Cleanliness and Protective Practices
    • In dusty or humid environments, regularly open the inverter casing for an internal check and cleaning.
    • If connectors or components show corrosion or rust, replace or clean them promptly.
    • Perform these repairs or inspections in as clean an environment as possible, avoiding metal particles, oil, or fine dust contamination on open circuit boards.
  4. Fault Log and Data Recording
    • If the inverter can store internal logs or provide real-time data, document those details as soon as a fault appears.
    • Observing the inverter’s normal operating waveforms versus the state just before a failure can guide you to the precise area of malfunction.

Conclusion

In summary, an M900 inverter reporting “err64” indicates a lost or compromised communication link between its main control board and driver board. This can stem from something as simple as a partially inserted ribbon cable or can be as severe as a failed bus transceiver chip or main CPU.

The recommended troubleshooting approach is systematic:

  1. Inspect and re-seat cables and connectors;
  2. Verify supply voltages and signals;
  3. Replace suspect transceiver and check associated passive parts;
  4. Finally, if those attempts fail, look toward the main CPU, DSP, or more advanced board-level repairs.

Meanwhile, ensuring proper cooling, following proper service procedures, and regularly cleaning the inverter’s internals will significantly lower the likelihood of such communication failures. If all methods are exhausted, contacting a professional repair center or the manufacturer is advisable for advanced diagnostics. By fully understanding the root cause and progression of “err64” faults, you can remedy them swiftly and maintain the M900 inverter’s reliability for critical industrial processes.

Posted on Leave a comment

JTE Inverter JT26N Usage Guide and ERR10 Fault Resolution

The JTE Inverter JT26N series is a high-performance general-purpose inverter widely used in various industrial control scenarios. This article provides a detailed introduction to the usage of this inverter, including panel startup and speed adjustment settings, external terminal forward/reverse and external potentiometer speed adjustment settings, parameter copying and initialization methods, as well as the meaning and resolution of the ERR10 fault.

JT26N physical image

I. Basic Settings for the JTE Inverter JT26N

1. Panel Startup and Speed Adjustment Settings

The panel startup and speed adjustment settings for the JTE Inverter JT26N are relatively straightforward. Users can complete basic startup and speed adjustment operations through the buttons and display on the control panel. Here are the specific steps:

  1. Startup Settings:
  • Press the “PRGM” key to enter programming mode.
  • Use the “Δ” and “∇” keys to select the function code F0-02, and confirm that the command source is set to the control panel command channel (value 0).
  • Press the “ENTER” key to confirm the setting.
  1. Speed Adjustment Settings:
  • In programming mode, select the function code F0-03 and set the main frequency source X to panel potentiometer speed adjustment (value 1).
  • Adjust the frequency by rotating the potentiometer on the panel to achieve speed control.

2. External Terminal Forward/Reverse and External Potentiometer Speed Adjustment Settings

The JTE Inverter JT26N supports forward/reverse control and external potentiometer speed adjustment functions through external terminals. Here are the specific wiring and setup methods:

  1. Forward/Reverse Control:
  • Wiring: Connect the external control signal to the digital input terminals of the inverter (such as MI1, MI2, etc.).
  • Settings: In programming mode, select the function code F0-09 and set the running direction to forward (value 0) or reverse (value 1).
  1. External Potentiometer Speed Adjustment:
  • Wiring: Connect the signal line of the external potentiometer to the analog input terminals of the inverter (such as AI1, AI2, etc.).
  • Settings: In programming mode, select the function code F0-03 and set the main frequency source X to external potentiometer speed adjustment (value 2, 3, or 4, depending on the specific terminal).

II. Parameter Copying and Initialization

1. Parameter Copying

The JTE Inverter JT26N supports parameter copying, allowing users to copy parameters from one inverter to another. Here are the specific steps:

  1. Prepare a blank storage card or USB drive and insert it into the parameter copying interface of the inverter.
  2. Press the “PRGM” key to enter programming mode and select the parameter copying function.
  3. Follow the prompts to copy the parameters to the storage card or USB drive.
  4. Insert the storage card or USB drive into another inverter and follow the prompts to copy the parameters to the new inverter.

2. Parameter Initialization

In some cases, users may need to initialize the inverter parameters. Here are the specific steps:

  1. Press the “PRGM” key to enter programming mode.
  2. Select the function code F0-27 and set the parameter initialization option to fully initialize parameters (value 03).
  3. Press the “ENTER” key to confirm, and the inverter will reset to factory settings.

III. Meaning and Resolution of the ERR10 Fault

1. Meaning of the ERR10 Fault

The ERR10 fault is a common fault code for the JTE Inverter JT26N, indicating an overload condition. An overload occurs when the output current of the inverter exceeds its rated current, which may be caused by the following reasons:

  1. The load is too large, exceeding the rated capacity of the inverter.
  2. There is a mechanical fault in the motor or other load equipment, causing abnormal current increases.
  3. The parameter settings of the inverter are incorrect, leading to overload protection activation.

2. Handling the ERR10 Fault

When the ERR10 fault occurs on-site, users should follow these steps to address it:

  1. Check the Load: Ensure that the load is within the rated capacity range of the inverter, reducing the load if necessary.
  2. Inspect the Motor and Equipment: Check the motor and other load equipment for mechanical faults, such as jamming or excessive resistance.
  3. Verify Parameter Settings: Ensure that the inverter’s parameter settings are correct, especially those related to the load.
  4. Restart the Inverter: After confirming that the load and equipment are normal, restart the inverter and observe if the ERR10 fault still occurs.

3. Repair Methods for the ERR10 Fault

When repairing the internal circuit board of the inverter after an ERR10 fault, users should follow these steps:

  1. Inspect Under Power-Off Conditions: Open the inverter’s casing in a power-off state and inspect the internal circuit board for any visible damage or burnout.
  2. Clean the Circuit Board: Use a clean cloth or cotton swab dipped in isopropyl alcohol to gently wipe the surface of the circuit board, removing dust and dirt.
  3. Replace Damaged Components: If any damaged or burned components are found on the circuit board, replace them with new components of the same model.
  4. Reassemble: After ensuring that the circuit board has no visible faults, reassemble the inverter and perform a functional test.
ERR10

IV. Conclusion

The JTE Inverter JT26N is a powerful and easy-to-operate inverter suitable for various industrial control scenarios. By correctly setting up panel startup and speed adjustment, external terminal forward/reverse, and external potentiometer speed adjustment, users can easily achieve basic control functions of the inverter. Additionally, the inverter supports parameter copying and initialization functions, making it convenient for users to manage parameters. In the event of an ERR10 fault, users should promptly check the load and equipment and follow the correct procedures for handling and repair to ensure the normal operation of the inverter.

Posted on Leave a comment

Causes and Solutions for the E0006 Fault in HPMONT HD09 Series Inverters

1. Fault Overview

The E0006 fault in the HPMONT HD09 series inverter corresponds to a “DC bus constant-speed overvoltage fault.” This means that the DC bus voltage in the inverter exceeds the safety limit during constant-speed operation. Such faults can cause equipment shutdowns, affecting production and normal operation.

HP09 physical picture
oplus_32

2. Fault Mechanism Analysis

  1. Causes of DC Bus Overvoltage: The DC bus voltage in the inverter is converted from AC through a rectifier. If the input voltage is too high or too low, it can cause instability in the bus voltage. During load operation, especially during rapid stops, large load inertia, or abnormal braking systems, the DC bus voltage may rise sharply, triggering overvoltage protection.
  2. Constant-Speed Overvoltage Scenario: The inverter operates at a constant speed, maintaining a stable motor frequency. If the input power supply voltage is too high, or if the acceleration/deceleration times are improperly set, overvoltage can occur. Furthermore, if the braking system is improperly configured or not correctly installed, excessive voltage can be generated during deceleration.
  3. Potential Circuit Reasons:
    • High input voltage: Especially in areas where the grid voltage fluctuates significantly, the inverter may detect overvoltage.
    • Abnormal braking system: If the braking unit or brake resistor is incorrectly configured, or if it is not equipped in systems with heavy loads, excessive voltage can be generated during deceleration.
    • System overload: If the load is too heavy or has significant inertia, the inverter may not be able to decelerate effectively, leading to overvoltage faults.

3. On-Site Fault Handling Methods

  1. Check Input Voltage:
    • Use a multimeter to check whether the input voltage to the inverter is within the normal range. If the input voltage exceeds the specified range (e.g., too high), consider using a voltage regulator or check the stability of the power grid.
  2. Check Acceleration/Deceleration Time Settings:
    • Refer to the inverter’s user manual and check the acceleration and deceleration times (parameters such as F03.01, F03.02, etc.). Too short a deceleration time can cause a sharp fluctuation in the bus voltage. It is recommended to extend the deceleration time to avoid overvoltage.
  3. Check Braking System:
    • For loads requiring deceleration, inspect the braking unit and brake resistor configuration to ensure they are appropriately sized for the load. If necessary, add a braking unit or adjust the brake resistor’s power and resistance.
  4. Inspect and Check the Circuit:
    • Inspect the internal circuitry of the inverter for loose connections, poor contact, or damage, especially in the power and braking resistor wiring terminals.

4. Specific Circuit Repair Methods

  1. Input Voltage Issues:
    • If the input voltage is too high, consider adding measures to stabilize the grid power, such as using overvoltage protection devices. For areas with significant voltage fluctuations, it is recommended to use appropriate power protection equipment, such as overvoltage protectors.
  2. Braking System Faults:
    • If the braking system is causing overvoltage, first verify whether the braking resistor is correctly specified. If the braking resistor is inadequate or damaged, select a properly rated resistor according to the load requirements. Check that the braking unit is properly connected, and ensure the braking circuit is securely wired.
  3. Capacitor Issues:
    • If the capacitor is aging or damaged, it could cause the DC bus voltage to be unstable. In this case, replace the damaged capacitors and verify whether the capacitor’s capacity matches the requirements.
  4. Reconfigure Deceleration Time:
    • For loads with high inertia or large power, it is necessary to increase the deceleration time. This can be achieved by adjusting parameters such as F03.02 to prevent overvoltage faults. Ensure that the deceleration process is smooth and does not lead to a sharp voltage change.
E6000
oplus_32

5. Conclusion

The E0006 fault is typically caused by high input voltage, braking system issues, or improper acceleration/deceleration time settings. When addressing this fault, it is essential to check key parameters such as input voltage, acceleration/deceleration times, and the braking system. Specific circuit repair actions, such as replacing capacitors, adjusting the braking system configuration, and extending deceleration times, can restore normal operation of the inverter.

Posted on Leave a comment

V&T V6-H Inverter User Manual Guide and Solution to E.FAL Fault

I. Introduction to the V&T V6-H Inverter Operation Panel Functions

E.FAL

1.1 Overview of Operation Panel Functions

The V&T V6-H inverter is equipped with an intuitive and user-friendly operation panel, providing convenient control and monitoring of the inverter’s operations. The operation panel features various buttons and indicators that allow users to perform various tasks such as setting parameters, monitoring operational status, and troubleshooting faults.

1.2 Setting and Resetting Passwords

Setting a Password:

  1. Enter the Password Function Code: Press the PRG button to enter the menu, and navigate to the password function code (P0.00).
  2. Set the Password: Enter the desired four-digit password and confirm it by pressing the PRG button again. The display will show “P.Set” indicating that the password has been successfully set.

Resetting a Password:

  1. Enter the Password Function Code: Press the PRG button to enter the menu, and navigate to the password function code (P0.00).
  2. Enter the Current Password: Enter the current password.
  3. Clear the Password: Set the password to “0000” and confirm by pressing the PRG button twice. The display will show “P.Clr” indicating that the password has been successfully reset.
V6-h standard wiring diagram

1.3 Setting Parameter Viewing Levels

The V6-H inverter provides different menu modes to control the visibility of parameters, allowing users to customize the level of access based on their needs.

Menu Modes:

  • Basic Menu Mode (P0.02 = 0): Displays all parameters.
  • Quick Menu Mode (P0.02 = 1): Displays only commonly used parameters, ideal for quick setup.
  • Non-Factory Default Menu Mode (P0.02 = 2): Displays only parameters that have been changed from their factory defaults.
  • Recent Changes Menu Mode (P0.02 = 3): Displays the last 10 parameters that have been changed.

To change the menu mode, navigate to the function code P0.02, select the desired menu mode, and confirm by pressing the PRG button.

1.4 Restoring Factory Defaults

Restoring the inverter to its factory default settings can be useful when troubleshooting or resetting the inverter to its initial configuration.

Steps to Restore Factory Defaults:

  1. Enter the Function Code for Restoring Defaults: Navigate to the function code P0.01.
  2. Select the Restore Option: Set P0.01 to “2” to restore all parameters (except motor parameters) to their factory defaults. Alternatively, set P0.01 to “5” to restore all parameters, including those in the reserved areas.
  3. Confirm the Operation: Press the PRG button to confirm the setting. The inverter will then restart and load the factory default parameters.
V6-H

1.5 Setting the Maximum Frequency to 3000Hz

The V6-H inverter supports a maximum output frequency of up to 3000Hz, making it suitable for applications requiring high-speed motor control.

Steps to Set the Maximum Frequency:

  1. Enter the Basic Function Parameters: Navigate to the function code P0.11.
  2. Set the Maximum Output Frequency: Enter “3000” and confirm by pressing the PRG button. This sets the maximum output frequency of the inverter to 3000Hz.

II. Implementing Terminal Forward/Reverse Control

The V&T V6-H inverter provides multiple methods for controlling the direction of rotation of the motor, including through terminal inputs. This section describes how to set up terminal forward/reverse control.

2.1 Terminal Configuration for Forward/Reverse Control

To control the motor’s direction of rotation using terminal inputs, the inverter’s control terminals must be properly configured.

Steps to Configure Terminal Forward/Reverse Control:

  1. Identify the Forward and Reverse Terminals: Typically, the forward and reverse terminals are labeled as FWD and REV, respectively.
  2. Set the Terminal Function: Navigate to the function codes P5.00 to P5.06 (corresponding to terminals X1 to X7) in the multi-function input parameters (P5 group). Set the desired terminal (e.g., X1) to function “9” (forward/reverse control).
  3. Connect the Terminals: Connect the forward and reverse control signals from the external control system to the corresponding terminals on the inverter.
  4. Configure the Run Command Source: Ensure that the run command source is set to terminal control (P0.06 = 1). This allows the inverter to respond to the forward and reverse control signals from the terminals.

2.2 Operating the Inverter in Forward/Reverse Mode

Once the terminal configuration is complete, the inverter can be operated in forward/reverse mode by controlling the signals applied to the forward and reverse terminals.

Operating the Inverter:

  • Forward Rotation: Apply a signal to the FWD terminal to start the motor in the forward direction.
  • Reverse Rotation: Apply a signal to the REV terminal to start the motor in the reverse direction.
  • Stopping the Motor: Remove the signal from both the FWD and REV terminals to stop the motor.

By following these steps, users can easily configure and operate the V&T V6-H inverter for terminal forward/reverse control, enabling precise motor control in a wide range of applications.

III. Solution to E.FAL Fault

The E.FAL fault code on the V&T V6-H inverter indicates a problem with the fan, specifically a fan alarm. This fault can occur due to various reasons such as fan malfunction, overheating, or wiring issues.

3.1 Troubleshooting Steps for E.FAL Fault

Steps to Troubleshoot and Resolve E.FAL Fault:

  1. Check the Fan Operation: Visually inspect the inverter’s cooling fan to ensure it is spinning properly. If the fan is not operating, it may need to be replaced.
  2. Check the Fan Wiring: Verify that the fan wiring is correct and free of damage. Loose or damaged wires can prevent the fan from receiving power.
  3. Check the Fan Sensor: The inverter may have a sensor to monitor fan operation. Ensure that the sensor is functioning correctly and not obstructed.
  4. Environmental Conditions: Consider the ambient temperature and ensure that the inverter is not overheating due to poor ventilation or high ambient temperatures.
  5. Reset the Inverter: If no issues are found with the fan or wiring, try resetting the inverter by turning it off and on again. This may clear the fault code if it was caused by a temporary issue.

3.2 Preventive Measures

To prevent future occurrences of the E.FAL fault, consider the following preventive measures:

  • Regular Maintenance: Schedule regular maintenance checks to inspect the fan and other cooling components.
  • Cleanliness: Keep the inverter and its surroundings clean to prevent dust and debris from obstructing the fan or cooling system.
  • Ventilation: Ensure adequate ventilation around the inverter to prevent overheating.
  • Monitoring: Use the inverter’s monitoring features to keep track of operating temperatures and fan status.

By following these guidelines and troubleshooting steps, users can effectively use the V&T V6-H inverter’s operation panel, configure terminal forward/reverse control, and resolve the E.FAL fault when it occurs.